| Plan Review Stops For Permit 20090158 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-01-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-08 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-08 |
Time |
12:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-11-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-11-23 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-11-23 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2020-11-23 07:55:57 | DOCK | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DOCK DRAWINGS SHOWS WIND DESIGN EXPOSURE "B" - | | | SHOULD BE EXPOSURE "D" PER FBC R301 | | | 2) SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. | | | 3) PLEASE COMPLETE A BUILDING PERMIT APPLICATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-09-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-09-22 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-09-22 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2020-09-22 15:33:28 | DOCK | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DOCK DRAWINGS NEED TO SHOW THE DESIGN PARAMETERS | | | USED (2017 FBC, WIND SPEED, EXPOSURE, ETC) FBC 1603. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
N |
Date |
2021-02-22 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-02-22 |
Time |
22:51 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-02-22 |
Time |
22:08 |
Sent To |
|
|
| Notes |
| 2021-02-22 22:52:35 | NO ELECTRICAL WORK REVIEWED OR APPROVED. PLANS TO BE | | | SUBMITTED BY ELECTRICAL CONTRACTOR. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2021-01-11 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-01-11 |
Time |
20:06 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-01-11 |
Time |
19:41 |
Sent To |
|
|
| Notes |
| 2021-01-11 20:06:40 | INITIAL PLAN REVIEW COMMENTS HAVE NOT BEEN SATISFIED. | | | PLEASE SEE INITIAL COMMENTS BELOW: | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL DRAWING FOR REVIEW, DIGITALLY | | | SIGNED BY A DESIGN PROFESSIONAL WITH THIRD-PARTY | | | VERIFICATION OR SIGNED BY THE ELECTRICAL CONTRACTOR | | | QUALIFIER. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1, | | | 107.3.5 | | | | | | 2. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF BOAT LIFT | | | MOTOR AND ALL ASSOCIATED EQUIPMENT (BOAT MOTOR | | | CONTROLLERS, LIGHTING, ETC). FBC 107.2.1 NEC 110.2 | | | 110.3B | | | | | | 3. PROVIDE LOAD CALCULATION OF EXISTING SERVICE SHOWING | | | ALL LOADS BOTH NEW AND EXISTING. NEC 220 FBC 107.2.1 | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-11-21 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-11-21 |
Time |
21:21 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-11-21 |
Time |
19:44 |
Sent To |
|
|
| Notes |
| 2020-11-21 21:21:54 | SEE LAST PLAN REVIEW COMMENTS. NONE OF THE COMMENTS | | | WERE ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-09-13 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-09-13 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-09-13 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2020-09-13 12:30:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL DRAWING FOR REVIEW, DIGITALLY | | | SIGNED BY A DESIGN PROFESSIONAL WITH THIRD-PARTY | | | VERIFICATION OR SIGNED BY THE ELECTRICAL CONTRACTOR | | | QUALIFIER. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1, | | | 107.3.5 | | | | | | 2. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF BOAT LIFT | | | MOTOR AND ALL ASSOCIATED EQUIPMENT (BOAT MOTOR | | | CONTROLLERS, LIGHTING, ETC). FBC 107.2.1 NEC 110.2 | | | 110.3B | | | | | | 3. PROVIDE LOAD CALCULATION OF EXISTING SERVICE SHOWING | | | ALL LOADS BOTH NEW AND EXISTING. NEC 220 FBC 107.2.1 | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2021-02-16 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-02-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2021-02-16 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
ENG-P |
ENGINEERING PLANNING REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-02-24 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-02-24 |
Time |
12:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG-P |
ENGINEERING PLANNING REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-12-08 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2020-12-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2020-12-08 |
Time |
|
Sent To |
I |
|
| Notes |
| 2020-12-08 07:50:31 | 1) PROVIDE SWPPP INCLUDING DETAILS ON TURBIDITY | | | BARRIERS. SHOW OUTFALLS, AND ANY RELATED UTILITY | | | INFRASTRUCTURE IN VICINITY OF PROPOSED WORK. | | | 2) DOCK MODIFICATIONS REQUIRE FORM SIGNED BY THE | | | PROPERTY OWNER ACKNOWLEDGING RESPONSIBILITIES OF OWNER | | | IN THE EVENT OF SEAWALL REPLACEMENT BY THE CITY. | | | CONTACT THE CITY OF WPB BUILDING DIVISION OR THIS | | | OFFICE FOR A PDF COPY OF RESOLUTION AND FORM FOR | | | SIGNATURE. | | | | | | THANKS, | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL | | | 33401 | | | DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE: | | | (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | 2020-12-08 07:41:28 | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-02-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-02-17 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-01-04 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2021-01-07 12:56:33 | DRAWINGS 1 OF 3 TRHU 3 OF 3 SUBMITTED. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-12-08 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-12-08 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-11-16 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-09-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-09-22 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-09-02 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2020-09-11 15:06:58 | CONVERTED TO DIGITAL. JG. | | 2020-09-05 14:30:02 | ROUTED TO BLDG. MISC 1 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-01-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-01-07 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-01-07 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2021-01-07 12:55:22 | DRAWINGS 1OF 3 TRHU 3 OF 3 WITH ENGINEER'S ORIGINAL | | | SEAL/SIGNATURE. JG. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-11-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-11-23 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-11-23 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2020-11-23 07:57:36 | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP | | | BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS | | | ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE | | | REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN | | | REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING | | | [email protected] AND ASKING FOR THE FORM. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-09-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-09-11 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-09-11 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2020-09-11 15:08:52 | DOCK & LIFT SHEETS 3 OF 3 HAVE ENGINEER'S ORIGINAL | | | SEAL/SIGNATURE. JG. | | | BOAT LIFT SHEETS 2 OF 2 HAVE ENGINEER'S ORIGINAL | | | SEAL/SIGNATURE. JG. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-11-23 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-11-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2020-11-23 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2020-09-22 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-09-22 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2020-09-22 |
Time |
|
Sent To |
I |
|
| Notes |
|
|