| 2020-09-08 11:13:29 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE |
| | INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| | WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| | SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| | EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE |
| | E3606.3 |
| | 2.PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 3.250.50 ALL PRESENT ELECTRODES |
| | 4.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A |
| | DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL |
| | CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | PHIL PETTY |
| | ELECTRICAL PLANS EXAMINER |