Plan Review Details - Permit 20090143
Plan Review Stops For Permit 20090143
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-19 Cont ID  
Sent By rmcdouga Date 2020-10-19 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2020-10-19 Time 14:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By rmcdouga Date 2020-09-24 Time 16:40 Rev Time 0.00
Received By rmcdouga Date 2020-09-24 Time 16:40 Sent To  
Notes
2020-09-24 16:45:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW ON THE SURVEY/SITE PLAN THAT THE GENERATOR
 EXHAUST IS LOCATED A MINIMUM OF 10' FROM ANY OPENINGS
 INTO THE BUILDING. FBC M501.3
  
 THE HONEYWELL GENERATOR IS NOT LISTED ON THE PREFAB
 GENERATOR PAD ENGINEERING, HOWEVER, ITS DIMENSIONS AND
 WEIGHT MATCH THE REQUIREMENTS OF THE PAD AND WINDLOADS.
 THIS IS ACCEPTABLE.
  
  
  
  
  
2020-09-08 14:03:45VALUE APPEARS LOW. CT

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-09 Cont ID  
Sent By cthroop Date 2020-10-09 Time 13:27 Rev Time 0.00
Received By cthroop Date 2020-10-09 Time 13:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-08 Cont ID  
Sent By cthroop Date 2020-09-08 Time 14:33 Rev Time 0.00
Received By cthroop Date 2020-09-08 Time 14:01 Sent To  
Notes
2020-09-08 14:36:53PLAN REVIEW GENERATOR / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2) VALUE
 CITY OF WPB CHPT. 1 VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR,
 MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE
 OF WORK.
 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY
 THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
 PLEASE INCREASE THE VALUATION ACCORDINGLY.
  
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By ccole Date 2020-10-13 Time 16:59 Rev Time 0.00
Received By ccole Date 2020-10-13 Time 08:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-15 Cont ID  
Sent By ccole Date 2020-09-15 Time 17:17 Rev Time 0.00
Received By ccole Date 2020-09-15 Time 15:04 Sent To  
Notes
2020-09-15 17:18:171ST REVIEW FBC-2017 RES.
 PERMIT- 20090143
 9/15/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING:
 A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
 B) PROVIDE THE BTUH LOAD OF THE GENERATOR AND THE TOTAL
 BTUH LOAD OF THE SYSTEM, INTERIOR APPLIANCES AND NEW
 GENERATOR COMBINED- SECTIONS G2412.3, G2412.4, &
 G2413.2 FBC RES. A) INDICATE THE TYPES, LENGTHS, AND
 SIZES OF THE MAIN PIPE FROM THE METER, THE BRANCH PIPE
 INTO THE HOUSE, AND THE BRANCH DROPPING INTO THE
 UNDERGROUND PE- SECTIONS G2413.4.1 & G2413.4.2.
 C) PROVIDE THE PIPE SIZING TABLES FOR THE MAIN AND
 BRANCH LINES FROM THE METER, AND THE PE. PLEASE NOTE
 THE SUBMITTED COPY OF TABLE 402.4(32) IS FOR LP GAS-
 THIS IS A NAT. GAS SYSTEM. REFER TO TABLES G2413.4(1)
 THROUGH G2413.4(8) FBC RES. RELATIVE SIZING TABLES FROM
 THE FBC FG MAY BE SUBSTITUTED.
 D) THE REDUCED (11 IN. W.C.) OUTLET PRESSURE AT THE
 REGULATOR FOR THE GENERATOR IS INCORRECT. THE REQUIRED
 INLET PRESSURE AT THE GENERATOR PER THE SUBMITTED SPECS
 IS (3.5- 7 IN. W.C.) FOR NAT. GAS- PLEASE CORRECT.
 E) INDICATE ON THE RISER WHICH B42 REGULATOR MODELS
 WILL BE INSTALLED- MODEL R, N, OR H AND SUBMIT
 HIGHLIGHTED OR MARKED UP SPEC SHEETS SHOWING THE MAX
 INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA,
 SPRING COLOR OUTLET PRESSURE RANGE AND ORIFICE SIZE-
 SECTION G2421.1 & G2421.2 FBC RES.
 E) PLEASE IDENTIFY THE SHUTOFF VALVE FOR THE GAS SUPPLY
 TO THE GENERATOR, AND THE REQUIRED PIPE UNIONS AT THE
 REGULATORS- SECTIONS G2420.4, G2420.5, AND G2421.2(7).
 THE DRAWING APPEARS TO BE USING THE SAME X SYMBOL FOR
 REGULATORS AND VALVES AT THE GENERATOR AND THE METER.
 F) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
 G) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO
 THE UG PE PIPING- SECTION G2415.17.3
 H) INDICATE HOW THE PE PIPING RISER WILL CONNECT TO THE
 FLEX CONNECTOR AND TO THE SCHEDULE 40 METALLIC PIPE PER
 SECTIONS G2415.17.1 & G2415.17.2. PLEASE NOTE THAT
 SPECS FOR ANODELESS RISERS AND PE/METALLIC PIPE
 CONNECTORS SHALL BE LISTED AND LABELED.
 I) SHOW THE LOCATION OF THE DRIP LEG- SECTION G2419.2
 FBC RES.
  
 2) PLEASE SUBMIT INSTALLATION GUIDELINES FROM GENERAC
 TO VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS
 SHOWN ON THE PLAN AND SURVEY ARE CONSISTENT WITH THE
 MANUFACTURER'S SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-19 Cont ID  
Sent By rmcdouga Date 2020-10-19 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2020-10-09 Time 11:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By rmcdouga Date 2020-09-24 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2020-09-04 Time 07:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-13 Cont ID  
Sent By ccole Date 2020-10-13 Time 09:31 Rev Time 0.00
Received By ccole Date 2020-10-13 Time 07:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-15 Cont ID  
Sent By ccole Date 2020-09-15 Time 17:20 Rev Time 0.00
Received By ccole Date 2020-09-15 Time 15:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-19 Cont ID  
Sent By rmcdouga Date 2020-10-19 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2020-10-19 Time 15:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-08 Cont ID  
Sent By cthroop Date 2020-09-08 Time 14:37 Rev Time  
Received By cthroop Date   Time   Sent To  
Notes
2020-09-08 14:42:51PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NON-DESIGN PROFESSIONALS
  
 1. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON PLAN SHEETS UNDER THEIR
 AUTHORITY ?
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 2. UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL WITH
 SIGNATURE OF DESIGNER AS APPLICABLE; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT.
  
 OPTION
  
 EITHER UPLOAD A SIGNED DOCUMENT OR DROP OFF (OR MAIL)
 ONE PAPER ORIGINAL:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By rthermid Date 2020-09-15 Time   Rev Time  
Received By rthermid Date 2020-09-15 Time   Sent To I
Notes
***NONE***