Plan Review Details - Permit 20090083
Plan Review Stops For Permit 20090083
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2021-02-18 Cont ID  
Sent By jwitmer Date 2021-02-18 Time 15:49 Rev Time 0.00
Received By jwitmer Date 2021-02-18 Time 15:32 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2021-01-05 Time 08:46 Sent To  
Notes
2021-01-05 09:46:44TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-11-16 Cont ID  
Sent By jwitmer Date 2020-11-16 Time 12:33 Rev Time 0.00
Received By jwitmer Date 2020-11-16 Time 10:45 Sent To  
Notes
2020-11-16 12:32:46COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jwitmer Date 2020-09-23 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2020-09-23 Time 13:05 Sent To  
Notes
2020-09-23 16:56:17COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-02-18 Cont ID  
Sent By jwitmer Date 2021-02-18 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2021-02-18 Time 15:31 Sent To  
Notes
2021-02-18 15:39:52WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090083
 ADD: 301 SOUTHERN BLVD.
 CONT: TBD/ TO BE ANNOUNCED
 TEL: ???
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: THURS. FEB. 18TH/2021
 ACTION: PASSED / BUILDING PROVISOS
  
 1) BUILDING PROVISO: DUMPSTER ENCLOSURE TO BE SUBMITTED
 UNDER SEPARATE PERMIT.
 SHEET A1.4. DUMPSTER DO TAKE A SEPARATE PERMIT REVIEW
 AND ASSOCIATED FEES. DETAIL # 3 STATES FOOTING DETAIL
 AND CMU WALL BOTH REFER TO STRUCTURAL SHEETS. SUBMIT
 THE STRUCTURAL SHEET WITH DETAILS FOR REVIEW. BUILDING
 PROVISO / TO BE REVIEWED BY ENGINEERING/ PUBLIC WORKS.
  
 2) BUILDING PROVISO: SHEET S102 SHOWS NEW OPEN WEB
 STEEL JOIST, DECK AND NEW C15X 33.9 STEEL BEAMS. WELDED
 OR BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 3) DEFERRED SUBMITTALS/ BUILDING PROVISO: THE SHEET
 A-01 INDICATES DEFERRED SUBMITTAL INDICATES SEE SHEET
 A6.0 FOR PRODUCT APPROVALS. A FULL LIST OF REQUIRED
 PRODUCT APPROVALS FOR COMPONENTS AND CLADDING SEE
 BELOW:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS, CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) BUILDING PROVISO: DEFERRED SUBMITTALS AS REQUESTED
 ON SHEET A-01. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2021-01-05 Time 08:46 Sent To  
Notes
2021-01-05 09:41:10WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090083
 ADD: 301 SOUTHERN BLVD.
 CONT: TBD/ TO BE ANNOUNCED
 TEL: ???
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JAN. 05/2021
 ACTION: PASSED / BUILDING PROVISOS
  
 1) BUILDING PROVISO: DUMPSTER ENCLOSURE TO BE SUBMITTED
 UNDER SEPARATE PERMIT.
 SHEET A1.4. DUMPSTER DO TAKE A SEPARATE PERMIT REVIEW
 AND ASSOCIATED FEES. DETAIL # 3 STATES FOOTING DETAIL
 AND CMU WALL BOTH REFER TO STRUCTURAL SHEETS. SUBMIT
 THE STRUCTURAL SHEET WITH DETAILS FOR REVIEW. BUILDING
 PROVISO / TO BE REVIEWED BY ENGINEERING/ PUBLIC WORKS.
  
 2) BUILDING PROVISO: SHEET S102 SHOWS NEW OPEN WEB
 STEEL JOIST, DECK AND NEW C15X 33.9 STEEL BEAMS. WELDED
 OR BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 3) DEFERRED SUBMITTALS/ BUILDING PROVISO: THE SHEET
 A-01 INDICATES DEFERRED SUBMITTAL INDICATES SEE SHEET
 A6.0 FOR PRODUCT APPROVALS. A FULL LIST OF REQUIRED
 PRODUCT APPROVALS FOR COMPONENTS AND CLADDING SEE
 BELOW:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS, CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) BUILDING PROVISO: DEFERRED SUBMITTALS AS REQUESTED
 ON SHEET A-01. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-16 Cont ID  
Sent By jwitmer Date 2020-11-16 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2020-11-16 Time 10:45 Sent To  
Notes
2020-11-16 14:00:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090083
 ADD: 301 SOUTHERN BLVD.
 CONT: TBD/ TO BE ANNOUNCED
 TEL: ???
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 16TH/ 2020
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3A) COMPLIED.
  
 3B) SEMI-COMPLIED/ 2ND REQUEST. SHEET A1.3 THE NEW
 DETAIL 3 DOES SHOW A DOUBLE LINE DETAIL BUT NOT
 CONFORMANCE WITH . WEST PALM MUNI-CODE ARTICLE XV
 PARKING DETAIL, 94-485 ILLUSTRATES WITH MEASUREMENTS
 FOR DOUBLE STRIPE STALL PAINTING. MISSING THE THICKNESS
 OF THE PAINTED LINES AND THE DISTANCE BETWEEN THE
 DOUBLE PAINTED LINES.
  
 1ST ROUND OF COMMENTS. THE SITE PLAN SHOWS THE PARKING
 SPACES WITH A SINGLE LINE. ACCESSIBLE PARKING SPACE /
 STALL PAINTING. 2017 ACCESSIBILITY CODE SECTION 502.2
 VEHICLE SPACES. EACH PARKING SPACE MUST BE AT LEAST 12
 FEET WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND
 SHALL HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH
 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
  
 4A) BUILDING PROVISO: DUMPSTER ENCLOSURE TO BE
 SUBMITTED UNDER SEPARATE PERMIT.
 SHEET A1.4. DUMPSTER DO TAKE A SEPARATE PERMIT REVIEW
 AND ASSOCIATED FEES. DETAIL # 3 STATES FOOTING DETAIL
 AND CMU WALL BOTH REFER TO STRUCTURAL SHEETS. SUBMIT
 THE STRUCTURAL SHEET WITH DETAILS FOR REVIEW.
  
 4B) BUILDING PROVISO / TO BE REVIEWED BY ENGINEERING/
 PUBLIC WORKS.
  
 4C) NOTED, NO ACTION REQUIRED. OTHER PERMITS THAT ARE
 NOT INCLUDED IN THIS REVIEW ARE FIRE SPRINKLER, FIRE
 ALARM, RACK STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR
 ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK
 IN COOLERS & FREEZERS, ALL LOW VOLTAGE PERMITS,
 GENERATORS & FUEL TANKS, GAS PERMIT, POOL, JACUZZI AND
 ASSOCIATED SUB-PERMITS, AWNING, SCREEN ENCLOSURES,
 CANOPY, FENCE, LANDSCAPE, IRRIGATION, AUGER CAST PILE
 AND OR FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE
 SEPARATE REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
  
 5-6) COMPLIED.
  
 7)BUILDING PROVISO: SHEET S102 SHOWS NEW OPEN WEB STEEL
 JOIST, DECK AND NEW C15X 33.9 STEEL BEAMS. WELDED OR
 BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 8) COMPLIED.
  
 9) NOTICE ONLY, NO ACTION NEEDS TO BE TAKEN. SHEET S001
 INDICATES THE WALL AND ROOF PRESSURES IN VASD, THEY ARE
 GOOD!!!!
  
 10-13 DEFERRED SUBMITTALS/ BUILDING PROVISO: THE SHEET
 A-01 INDICATES DEFERRED SUBMITTAL INDICATES SEE SHEET
 A6.0 FOR PRODUCT APPROVALS. A FULL LIST OF REQUIRED
 PRODUCT APPROVALS FOR COMPONENTS AND CLADDING SEE
 BELOW:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS, CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 11)BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 12)BUILDING PROVISO: DEFERRED SUBMITTALS AS REQUESTED
 ON SHEET A-01. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jwitmer Date 2020-09-23 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2020-09-23 Time 13:05 Sent To  
Notes
2020-09-23 16:58:37WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090083
 ADD: 301 SOUTHERN BLVD.
 CONT: TBD/ TO BE ANNOUNCED
 TEL: ???
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 23RD/ 2020
 ACTION: DENIED
  
 1) SHEET A0.1 PLEASE CLARIFY UNDER THE HEADING SUMMARY
 OF WORK THE NOTES THE ONLY BUILDING DEMOLITION TO TAKE
 PLACE IS THE 2ND STORY ADDITION WHERE BELOW THE DRIVE
 THRU WAS WHEN THIS BUILDING WAS A BANK. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2A) SHEET A0.1 PLEASE CLARIFY UNDER THE HEADING SUMMARY
 OF WORK THE NOTES THE REMODEL OF EXISTING SINGLE-STORY
 STRUCTURE.
 PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE STATES
 THERE IS A BASEMENT, IS THERE A BASEMENT OR IS THERE A
 MEZZANINE IN THE SINGLE-STORY PORTION OF THE BUILDING?
 YEARS AGO WHEN IT WAS A BANK IT APPEARED TO HAVE A
 MEZZANINE? NOT A BASEMENT? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2B) PLEASE BREAK OUT THE EITHER BASEMENT OR MEZZANINE
 SQUARE FOOTAGE AND OCCUPANT LOAD FOR THIS AREA. IT
 APPEARS THE SQ. FOOTAGE IS APPROXIMATELY 1,695 SQ. FT.
 EVEN WHEN YOU DIVIDE THE TOTAL 1695/300= 5.65 OCCUPANTS
 WHICH ROUNDS UP TO 6 OCCUPANTS REQUIRING VERTICAL
 ACCESSIBILITY. PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY
 CODE SECTION 201.1.1.(3). FLORIDA ACCESSIBILITY GRAY
 BOX.
  
 2C) THE PLANS INDICATE SHEET A1.5 A 1ST FLOOR WITH
 BASEMENT SHEET A0.1 DOES NOT GIVE WHAT TYPE OF STORAGE
 IS GOING TO BE IN THE BASEMENT S1 OR S2 FBC-B TABLE
 508.4 DOES NOT REQUIRE SEPARATION FOR A S1 STORAGE ON
 THE 1ST OR ANY OTHER SAME FLOOR. A S-2 STORAGE WOULD
 REQUIRE FIRE SEPARATION. PLEASE REVIEW FIRE BARRIER
 SEPARATION BUILD. CODE FOR HORIZONTAL FIRE BARRIER
 SEPARATION TABLE 7073.10S1 WOULD REQUIRE 3 HOUR AND S2
 WOULD REQUIRE 2 HR.
  
 2D) SHEET A0.1 DOES NOT GIVE THE TABLE FOR TRAVEL
 DISTANCE WITH ONLY ONE EXIT. EXIT ACCESS CAN TRAVEL
 MORE THAN ONE ADJACENT STORY FBC-B 1006.3 YOU DO NOT
 USE TABLE 1006.2.1 THAT IS FOR GRADE. PLEASE REVIEW IN
 THE 2017 FBC-B TABLE 1006.3.2(2) FOR FIRST STORY ABOVE
 OR BELOW GRADE PLANE THE MAXIMUM COMMON PATH OF TRAVEL
 OF EGRESS TRAVEL DISTANCE IS LIMITED TO 75 FEET. WHEN
 VIEWING SHEET A2.0 WITH THE OUTLINE OF THE BASEMENT
 USING THE MEASURING TOOL IN THE PROGRAM AND CALIBRATING
 THE TOOL THE TRAVEL DISTANCE IS OVER 120 FT. WITHOUT
 ACCOUNTING FOR THE STAIR INCLINE.
  
 3A) SHEET A1.3 THE SITE PLAN APPEARS TO BE 26 PARKING
 SPACES AND ONLY ONE IS ACCESSIBLE. PLEASE REVIEW THE
 2017 FBC-ACCESSIBILITY CODE TABLE 208.2. WHEN THERE ARE
 26 TO 50 PARKING SPACES THEN 2 HAVE TO BE ACCESSIBLE
 PARKING SPACES.
  
 3B) THE SITE PLAN SHOWS THE PARKING SPACES WITH A
 SINGLE LINE. ACCESSIBLE PARKING SPACE / STALL PAINTING.
 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES.
 EACH PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL
 BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN
 ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
  
 4A) SHEET A1.4. DUMPSTER DO TAKE A SEPARATE PERMIT
 REVIEW AND ASSOCIATED FEES. DETAIL # 3 STATES FOOTING
 DETAIL AND CMU WALL BOTH REFER TO STRUCTURAL SHEETS.
 SUBMIT THE STRUCTURAL SHEET WITH DETAILS FOR REVIEW.
  
 4B) DUMPSTER ENCLOSURES. DUMPSTERS NEED TO BE ABLE TO
 BE ROLLED OUT BY THE CURB SIDE ON YOUR SERVICE DAYS.
 PLEASE PROVIDE THE DETAILED SPECS. FOR THE ENCLOSURE TO
 ENSURE COMPLIANCE WITH THE PUBLIC WORKS LATEST
 SPECIFICATIONS SEE THE LINK LISTED BELOW:
 LINK TO DUMPSTER ENCLOSURE SPECIFICATIONS:
 HTTPS://WPB.ORG/GETATTACHMENT/DEPARTMENTS/ENGINEERING-P
 UBLIC-WORKS/ENGINEERING-STANDARDS-DETAIL/DUMP
 STER-ENCLOSURE-SPEC-_GC-8_REVISED-6-13-19.PDF;?LANG=EN-
 US
  
 4C) OTHER PERMITS THAT ARE NOT INCLUDED IN THIS REVIEW
 ARE FIRE SPRINKLER, FIRE ALARM, RACK STORAGE, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & FREEZERS,
 ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL TANKS, GAS
 PERMIT, POOL, JACUZZI AND ASSOCIATED SUB-PERMITS,
 AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, LANDSCAPE,
 IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR
 STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND
 ASSOCIATED FEES WITH EACH PERMIT.
  
 5) SHEET A2.0:
 5A) (1) DOOR 109 PLEASE REVIEW IN THE 2017 FBC-ACCESS.
 CODE FIGURE 404.2.4.3 MANEUVERING CLEARANCES AT
 RECESSED DOORS.
  
 5A)(2) 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS
 OF EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 6) SHEET A2.1 ENLARGED RESTROOM PLAN & DETAILS:
 6A) THE BACK WALL OF THE RESTROOM IS NOT DIMENSIONED TO
 SEE IF THE RESTROOMS ARE CODE COMPLIANT.
 CLEARANCES AT WATER CLOSETS. 604.3 CLEARANCE.
 CLEARANCES AROUND THE WATER CLOSETS AND IN TOILET
 COMPARTMENTS SHALL COMPLY WITH 604.3. 604.3.1. SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR WALL.
 NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE 7 FOOT
 1 INCH WHEN THE LAV IS CENTERED AT 15 INCHES FROM THE
 SIDE WALL. PLANS SHOW THE LAV CENTERED AT 16 ? INCHES.
  
 6B) ACCESS. CODE SECTION 603.2.3 DOOR SWING AND
 EXCEPTION 2. I BELIEVE THIS HOW YOU ARE STRIVING TO
 SHOW CODE COMPLIANCE. WHAT IS MISSING IS THE REQUIRED
 CLEAR FLOOR SPACE BEYOND THE ARC OF THE DOOR. IT IS
 USUALLY SHOWN AT A 45-DEGREE ANGLE TO THE ENTRY DOOR.
  
 6C) DETAIL # 8 THE TOILET PAPER DISPENSER NEEDS
 ADJUSTMENT. TOILET PAPER DISPENSERS. 604.7. THE TOILET
 PAPER DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 7) SHEET S102 SHOWS NEW OPEN WEB STEEL JOIST, DECK AND
 NEW C15X 33.9 STEEL BEAMS. WELDED OR BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 8) SHEET S301 SHOW THE ROOF HEIGHT AT 17 FEET 9 INCHES
 HOW WILL ACCESS BE MADE FOR THE ROOF TOP MECHANICAL
 EQUIPMENT?
 2017 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
 WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE
 LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A
 BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER
 THAN 16 FEET (4877 MM) ABOVE GRADE TO ACCESS SUCH
 EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS
 OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS HAVING A
 SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL NOT
 REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS
 INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL
 BE MEASURED TO THE TOP OF THE PARAPET WALL.
  
 9) NOTICE ONLY, NO ACTION NEEDS TO BE TAKEN. SHEET S001
 INDICATES THE WALL AND ROOF PRESSURES IN VASD, THEY ARE
 GOOD!!!!
  
 10) THE SHEET A-01 INDICATES DEFERRED SUBMITTAL
 INDICATES SEE SHEET A6.0 FOR PRODUCT APPROVALS. A FULL
 LIST OF REQUIRED PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING SEE BELOW:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 11) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 12) DEFERRED SUBMITTALS AS REQUESTED ON SHEET A-01.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-02-25 Cont ID  
Sent By jleahy Date 2021-02-25 Time 10:09 Rev Time 0.00
Received By jleahy Date 2021-02-25 Time 10:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-01-12 Cont ID  
Sent By jleahy Date 2021-01-12 Time 12:12 Rev Time 0.00
Received By jleahy Date 2021-01-11 Time 07:59 Sent To  
Notes
2021-01-12 12:15:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF PERMIT FOR BUILD OUT IS LOW. YOU MUST
 INCLUDE ALL MATERIALS IN THE VALUE EVEN WHEN SUPPLIED
 BY OWNER, WHICH IS STATED ON PLANS FOR ELECTRIC, AND
 MECHANICAL MATERIALS AND EQUIPMENT.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-12-07 Cont ID  
Sent By jleahy Date 2020-12-07 Time 14:51 Rev Time 0.00
Received By jleahy Date 2020-12-07 Time 14:43 Sent To  
Notes
2020-12-07 14:51:47CONTRACT IS FOR BOYNTON BEACH STORE. JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-16 Cont ID  
Sent By jleahy Date 2020-10-16 Time 13:47 Rev Time 0.00
Received By jleahy Date 2020-10-15 Time 07:55 Sent To  
Notes
2020-10-16 13:50:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE OF PERMIT SHOWN IS LOW FOR THE SIZE OF THIS
 PROJECT. (350,000)
  
 PLEASE SUBMIT A BREAK DOWN OF ALL SYSTEMS THAT ARE
 INCLUDED IN THIS PERMIT PACKAGE NOT JUST FOR ELECTRIC.
  
 INTERIOR WALLS, CEILING, CABINETS, PLUMBING, GAS,
 MECHANICAL, DATA/TELEPHONE, FIRE ALARM, CCTV, LOW
 VOLTAGE, ECT. ECT.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-01-14 Cont ID  
Sent By rrossano Date 2021-01-14 Time   Rev Time 0.00
Received By rrossano Date 2021-01-14 Time   Sent To I
Notes
2021-01-14 11:26:11NO FURTHER COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-12-08 Cont ID  
Sent By rrossano Date 2020-12-08 Time   Rev Time 0.00
Received By rrossano Date 2020-12-08 Time   Sent To I
Notes
2020-12-08 08:09:18UNDER ENGINEERING FORRMAL REVIEW - PERMIT E20100016.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-18 Cont ID  
Sent By pleduc Date 2020-11-18 Time   Rev Time 0.00
Received By pleduc Date 2020-11-16 Time 16:00 Sent To  
Notes
2020-11-18 13:47:41FIRE PROVISO:
  
 AFTER CAREFUL REVIEW OF PREVIOUS DISCUSSIONS AND HAVING
 NO ACCESS TO THE ADANDONED SPACE, RESTRICTED ACCESS IS
 NEEDED.
  
 PROVIDE AN ACCESS DOOR TO ABANDONED SPACE;
  
 PROVIDE LOCK & SIGNAGE NO ADMITTANCE, ADANDONED SPACE.
  
 PLACE KEY FOR SPACE IN FD KNOX BOX
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By pleduc Date 2020-09-21 Time   Rev Time 0.00
Received By pleduc Date 2020-09-17 Time 10:11 Sent To  
Notes
2020-09-21 13:19:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.5 - A BASEMENT WITH STORAGE ROOMS IS
 INDICATED.
  
 THERE ARE NO DIMENSIONS NOR SQ FT INDICATED.
  
 PER NFPA 1, CH 13
  
 13.3.2.2 BASEMENTS EXCEEDING 2500 FT2 (232 M2) IN NEW
 BUILDINGS
 SHALL BE PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC
 SPRINKLER
 SYSTEM.
  
 PLEASE PROVIDE
  
  
 2) SHEET A 1.5 - THERE IS ONLY ONE EXIT INDICATED FROM
 THE BASEMENT.
  
 A TRAVEL DISTANCE IS INDICATED AS 89'6"
  
 PER NFPA 101 CH 7
  
 36.2.4 NUMBER OF MEANS OF EGRESS.
 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH
 36.2.4.5:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
  
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 36.2.4 NUMBER OF MEANS OF EGRESS.
 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH
 36.2.4.5:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET A 1.5 - THE STORAGE OCCUPANCY DOES NOT APPEAR
 TO BE SEPARATED BY ANY FIRE RATING.
  
 PER NFPA 101, CH 6
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF
 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 THE CODE REQUIRES A 2 HOUR FIRE RATED SEPARATION.
  
 IS THIS A MIXED OR SEPARATED OCCUPANCY?
  
 PLEASE ALSO BE AWARE OF THE HAZARD CLASSIFICATION AND
 PROTECTION
  
 6.2 HAZARD OF CONTENTS.
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL
 BE THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE,
 THE DANGER OF
 SMOKE OR GASES GENERATED, AND THE DANGER OF EXPLOSION
 OR OTHER
 OCCURRENCE POTENTIALLY ENDANGERING THE LIVES AND SAFETY
 OF THE
 OCCUPANTS OF THE BUILDING OR STRUCTURE.
 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE
 REGISTERED
 DESIGN PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE
 AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL
 ON THE BASIS
 OF THE CHARACTER OF THE CONTENTS AND THE PROCESSES OR
 OPERATIONS
 CONDUCTED IN THE BUILDING OR STRUCTURE.
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF
 HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A
 BUILDING OR STRUCTURE,
 THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION,
 UNLESS
 HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED
 IN SECTION
 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH
 43.
  
 CH 8
  
 8.7 SPECIAL HAZARD PROTECTION.
 8.7.1 GENERAL.
 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF
 HAZARD
 GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF
 THE
 BUILDING OR STRUCTURE SHALL BE PROVIDED BY ONE OF THE
 FOLLOWING
 MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT
 HAS A 1-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH
 SECTION 8.3
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN
 ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE
 OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 THROUGH 43
  
 8.7.1.3 DOORS IN BARRIERS REQUIRED TO HAVE A FIRE
 RESISTANCE RATING
 SHALL HAVE A MINIMUM ?-HOUR FIRE PROTECTION RATING AND
 SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING IN ACCORDANCE WITH
 7.2.1.8.
  
 PLEASE REVIEW AND CORRECT.
  
 4) PER #3 ABOVE WHAT IS THE TYPE AND CLASSIFICATION OF
 THE STORGE CONTENTS.
  
 PER CH 6
  
 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS.
 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY
 BUILDING OR
 STRUCTURE SHALL BE CLASSIFIED AS LOW, ORDINARY, OR HIGH
 IN
 ACCORDANCE WITH 6.2.2.2, 6.2.2.3, AND 6.2.2.4.
 6.2.2.2* LOW HAZARD CONTENTS. LOW HAZARD CONTENTS SHALL
 BE
 CLASSIFIED AS THOSE OF SUCH LOW COMBUSTIBILITY THAT NO
 SELFPROPAGATING
 FIRE THEREIN CAN OCCUR.
 6.2.2.3* ORDINARY HAZARD CONTENTS. ORDINARY HAZARD
 CONTENTS SHALL
 BE CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH
 MODERATE RAPIDITY OR
 TO GIVE OFF A CONSIDERABLE VOLUME OF SMOKE.
 6.2.2.4* HIGH HAZARD CONTENTS. HIGH HAZARD CONTENTS
 SHALL BE
 CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH
 EXTREME RAPIDITY OR FROM
 WHICH EXPLOSIONS ARE LIKELY. (FOR MEANS OF EGRESS
 REQUIREMENTS, SEE
 SECTION 7. 11.)
  
 PLEASE PROVIDE DETAILS.
  
  
 5) SHEET A 1.5 - THERE IS A DOUBLE DIRECTION SWING DOOR
 # 104 THAT SWINGS IN BOTH DIRECTION.
  
 A REQUIRED EXIT DOOR SHALL SWWING IN THE DIRECTION OF
 EXIT TRAVEL.
  
 CH 7
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 THE INTENT OF THE ABOVE CODE IS THAT A DOOR MUST SWING
 IN THE DIRECTION OF TRAVEL BUT CAN SWING IN THE
 OPPISITE DIRECTION IF LESS THAN 50; IT CAN NOT SWING
 BOTH WAYS. ONE OR THE OTHER.
  
 PLEASE REIVIEW AND CORRECT.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-09-25 Cont ID  
Sent By fmittner Date 2020-09-25 Time 10:36 Rev Time 0.00
Received By fmittner Date 2020-09-25 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-03-01 Cont ID  
Sent By shill Date 2021-03-01 Time 06:46 Rev Time 0.00
Received By shill Date 2021-02-10 Time 11:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-14 Cont ID  
Sent By lmarchan Date 2021-01-14 Time 11:58 Rev Time 0.00
Received By lmarchan Date 2020-12-18 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-11 Cont ID  
Sent By jleahy Date 2020-12-11 Time 10:37 Rev Time 0.00
Received By jleahy Date 2020-11-12 Time 14:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-16 Cont ID  
Sent By jleahy Date 2020-10-16 Time 13:53 Rev Time 0.00
Received By jleahy Date 2020-09-11 Time 14:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2021-03-25 Cont ID  
Sent By lmarchan Date 2021-03-25 Time 08:44 Rev Time 0.00
Received By lmarchan Date 2021-02-16 Time 11:43 Sent To  
Notes
2021-03-22 11:15:06RECEIPT MU-2021-08880 - $66,491.19 - PAID
2021-02-16 11:43:332/16/21 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-11-16 Cont ID  
Sent By jwitmer Date 2020-11-16 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2020-11-16 Time 10:47 Sent To  
Notes
2020-11-16 10:47:28IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jwitmer Date 2020-09-23 Time 17:00 Rev Time 0.00
Received By jwitmer Date 2020-09-23 Time 13:23 Sent To  
Notes
2020-09-23 17:00:20IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-12-22 Cont ID  
Sent By medwards Date 2020-12-22 Time 16:57 Rev Time 0.00
Received By medwards Date 2020-12-22 Time 16:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-11-24 Cont ID  
Sent By medwards Date 2020-11-24 Time 12:16 Rev Time 0.00
Received By medwards Date 2020-11-24 Time 12:16 Sent To  
Notes
2020-11-24 12:16:251ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20090083
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) OUTSIDE AIR CALCULATIONS APPEAR TO BE WRONG.
 7.5 X 48 + 0.12 X 3193 = 743.16 743.16 / 0.8 = 928.95
 FBC 403.3.1.1
  
 2) SHEET M1.0; IT APPEARS THAT RTU-2 IS SUPPLYING 2000
 CFM TO THE DINING AREA BUT I DO NOT SEE THE RETURN AIR
 GRILLES MENTIONED IN YOUR COMMENTS. PLEASE PROVIDE A
 WALL DETAIL OF THE AREA SHOWING THE SUPPLY AND RETURN
 GRILLES LOCATION. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By medwards Date 2020-10-02 Time 09:18 Rev Time 0.00
Received By medwards Date 2020-10-01 Time 14:49 Sent To  
Notes
2020-10-02 09:19:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090083
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECIFICATIONS FOR THE NEW RTU-1 AND
 RTU-2. FBC 107.2.1
  
 2) PLEASE PROVIDE SPECIFICATIONS ON ALL COOKING
 EQUIPMENT, SHOW HOW THE COOKING EQUIPMENT MEETS FBC M
 507.1
  
 3) SHEET M1.0- THE OCCUPANT COUNT SHOWN IN THE OSA
 CALCULATIONS IS 26 BUT SHEET A0.1 INDICATES 126 TOTAL
 OCCUPANT COUNT. PLEASE PROVIDE AN OUTSIDE AIR
 CALCULATION BASED ON TOTAL OCCUPANT COUNT PER USE OF
 SPACE LISTED UNDER THE OCCUPANT LOAD TABLE. FBC M TABLE
 403.3.1.1
  
 4) PLEASE SHOW RETURN AIR PATH FROM DINING AREA BACK TO
 RTU-2. FBC M 601.5; 601.6
  
 5) PLEASE PROVIDE DETAILS AS TO ACCESS TO THE EQUIPMENT
 LOCATED ON THE ROOF. FBC M 306.5
  
 6) PLEASE SHOW THAT THE EQUIPMENT LOCATED ON THE ROOF
 MEETS FBC M 304.11 FOR GUARD REQUIREMENTS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By lcrespo Date 2020-12-04 Time 18:48 Rev Time 0.00
Received By lcrespo Date 2020-12-04 Time 11:57 Sent To  
Notes
2020-12-04 18:48:3412/04/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By jesmith Date 2020-09-17 Time 14:08 Rev Time 0.00
Received By jesmith Date 2020-09-15 Time 16:41 Sent To  
Notes
2020-09-17 14:08:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, IDENTIFY EXISTING EMERGENCY
 OVERFLOW SCUPPERS OR PROVIDE NEW TO COMPLY WITH FBC PL
 1108.1. PROVIDE DETAIL OF SAME.
  
 2. RE: S-1 HAND SINK; FIXTURE SHALL BE SEPARATELY
 TRAPPED BY A LIQUID SEAL TRAP AND DIRECTLY CONNECTED TO
 THE DRAINAGE SYSTEM IN ACCORDANCE WITH FBC PL CHAPTER 7
 PER FBC PL 802.1 AND 1002.1. FIXTURE TRAP SHALL BE
 VENTED IN ACCORDANCE WITH FBC PL CHAPTER 9, WHICH
 INCLUDES THE USE OF AIR ADMITTANCE VALVES AS NOTED IN
 SECTION 918.
  
 3. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TRAP PRIMER,
 SHOW ON WATER RISER DIAGRAM, WATER CONNECTION TO SIOUX
 CHIEF #695 TRAP PRIMER VALVE(S) AND ON SANITARY RISER
 DIAGRAM TRAP PRIMER CONNECTIONS TO REQUIRED TRAPS.
  
 4. RE: EF1.1; PER WPB FBC 107.2.1, SHOW LOCATION AND
 PROVIDE DETAIL ON PLUMBING PLAN FOR ITEM 22, MCCANN
 WATER BOOSTER AND A MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL. IS THIS FOR A
 CARBONATED BEVERAGE DISPENSER. I CANNOT FIND ANY SUCH
 DISPENSER ON THE PLANS OR SCHEDULE. PLEASE CLARIFY.
 WATER SUPPLY SYSTEM SHALL BE PROTECTED BY A BACKFLOW
 PREVENTION DEVICE COMPLYING WITH FBC PL 608.16.1.
  
 5. PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING PLAN
 THE FIXTURES THAT ARE TO BE PROVIDED WITH THE TMV NOTED
 ON P1.0, SPECIALTY FIXTURE SCHEDULE AND PROVIDE NOTE
 STATING TMV IS ASSE 1070 COMPLIANT.
  
 6. PER WPB FBC 107.2.1, PROVIDE UP TO DATE
 CERTIFICATION OF THE EXISTING BACKFLOW PREVENTER NOTED
 ON P1.1.
  
 7. RE: P1.1 AND P2.0: PER WPB FBC 107.2.1, TO BE CLEAR,
 PROVIDE SIZE OF EXPANSION TANK TO BE INSTALLED WITH THE
 SPECIFIED WATER HEATER.
  
 8. RE: P1.1 AND P2.0: PER WPB FBC 107.2.1, PROVIDE
 DETAIL FOR WATER HEATER SHELF SPECIFYING MEANS, METHOD,
 MATERIALS, ANCHORS AND IF APPLICABLE, WATER HEATER
 RESTRAINTS.
  
 9. PER FBC PL 606.1(5), FULL OPEN VALVES SHALL BE
 INSTALLED AT TOP OF EVERY WATER DOWN FEED PIPE.
  
 10. PER FBC PL 606.1(8), THE BALL VALVE IN WATER SUPPLY
 TO THE WATER HEATER SHALL BE FULL PORT.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090083 301 SOUTHERN BLVD
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2020-12-04 Cont ID  
Sent By lcrespo Date 2020-12-04 Time 18:46 Rev Time 0.00
Received By lcrespo Date 2020-12-04 Time 18:46 Sent To  
Notes
2020-12-04 18:47:09A SEPERATE SUB PERMIT REQUIRED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-02-18 Cont ID  
Sent By jwitmer Date 2021-02-18 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2021-02-18 Time 15:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-22 Cont ID  
Sent By medwards Date 2020-12-22 Time 17:01 Rev Time 0.00
Received By medwards Date 2020-12-22 Time 17:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-24 Cont ID  
Sent By medwards Date 2020-11-24 Time 12:26 Rev Time 0.00
Received By medwards Date 2020-11-24 Time 12:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-02 Cont ID  
Sent By medwards Date 2020-10-02 Time 09:43 Rev Time 0.00
Received By medwards Date 2020-10-02 Time 09:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-01-14 Cont ID  
Sent By fmittner Date 2021-01-14 Time 10:49 Rev Time 0.00
Received By fmittner Date 2021-01-14 Time 10:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-09 Cont ID  
Sent By fmittner Date 2020-12-09 Time 13:19 Rev Time 0.00
Received By fmittner Date 2020-12-09 Time 13:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-25 Cont ID  
Sent By fmittner Date 2020-09-25 Time 10:36 Rev Time 0.00
Received By fmittner Date 2020-09-25 Time 10:36 Sent To  
Notes
***NONE***