Plan Review Details - Permit 20081431
Plan Review Stops For Permit 20081431
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-10-14 Cont ID  
Sent By cpuell Date 2020-10-14 Time 15:38 Rev Time 0.00
Received By cpuell Date 2020-10-14 Time 15:38 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-09-10 Cont ID  
Sent By cpuell Date 2020-09-10 Time 08:43 Rev Time 0.00
Received By cpuell Date 2020-09-10 Time 08:43 Sent To  
Notes
2020-09-10 08:43:50PLEASE CONTACT [email protected] TO ESTABLISH AN ADDRESS
 FOR THE PROPERTY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-28 Cont ID  
Sent By jgomez Date 2020-10-28 Time 17:04 Rev Time 0.00
Received By jgomez Date 2020-10-28 Time 16:26 Sent To  
Notes
2020-10-28 17:05:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-TRUSS PACKAGE:
 NEED THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF
 RECORD AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER
 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NOTE: TRUSS PACKAGE WITH ENGINEER'S ORIGINAL
 SEAL/SIGNATURE MAY BE: (1)DELIVERED TO BUILDING
 INSPECTOR AT TIME OF FRAMING INSPECTION. (2)DROPPED OFF
 AT CITY HALL OR (3)SUBMITTED ELECTRONICALLY WITH
 DIGITAL SIGNATURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By jgomez Date 2020-09-30 Time 15:37 Rev Time 0.00
Received By jgomez Date 2020-09-30 Time 13:11 Sent To  
Notes
2020-09-30 15:38:00NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS
 UPDATED TO $203,056. THE PERMIT FEE BALANCE IS $369.05.
  
  
  
 PROVISO:
 1-TRUSS PACKAGE:
 A)NEEDS TO BE REVIEWED/APPROVED IN WRITING BY THE
 ARCHITECT OF RECORD.
 B)NEEDS THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER
 OF RECORD AS REQUIRED BY SEC. 61G15-23.003 FAC AND
 CHAPTER 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS.
 NOTE: TRUSS PACKAGE WITH ENGINEER'S ORIGINAL
 SEAL/SIGNATURE MAY BE: (1)DELIVERED TO BUILDING
 INSPECTOR AT TIME OF FRAMING INSPECTION. (2)DROPPED OFF
 AT CITY HALL OR (3)SUBMITTED ELECTRONICALLY WITH
 DIGITAL SIGNATURE.
  
 2- SOIL TEST REPORT NEEDS THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: REPORT WITH ENGINEER'S ORIGINAL SEAL/SIGNATURE
 MAY BE: (1)DROPPED OFF AT CITY HALL OR (2)SUBMITTED
 ELECTRONICALLY WITH DIGITAL SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-29 Cont ID  
Sent By jleahy Date 2020-09-29 Time 11:41 Rev Time 0.00
Received By jleahy Date 2020-09-29 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-29 Cont ID  
Sent By medwards Date 2020-10-29 Time 06:50 Rev Time 0.00
Received By medwards Date 2020-10-13 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-30 Cont ID  
Sent By jgomez Date 2020-09-30 Time 15:43 Rev Time 0.00
Received By jgomez Date 2020-09-14 Time 15:23 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-01-14 Cont ID  
Sent By lmarchan Date 2021-01-14 Time 09:38 Rev Time 0.00
Received By lmarchan Date 2020-11-12 Time 14:57 Sent To  
Notes
2021-01-05 09:59:12RECEIPT - MU-2020-46256 - $4133.44 - PAID
2020-11-12 14:57:5211/12/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-09-30 Cont ID  
Sent By jgomez Date 2020-09-30 Time 15:40 Rev Time 0.00
Received By jgomez Date 2020-09-30 Time 15:39 Sent To  
Notes
2020-09-30 15:40:47IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-10-29 Cont ID  
Sent By medwards Date 2020-10-29 Time 06:50 Rev Time 0.00
Received By medwards Date 2020-10-29 Time 06:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-09-21 Cont ID  
Sent By medwards Date 2020-09-21 Time 15:31 Rev Time 0.00
Received By medwards Date 2020-09-21 Time 15:30 Sent To  
Notes
2020-09-21 15:44:12PROVISO: FBC EC R4.3.3.6 AIR HANDLING UNITS
 AIR HANDLER MAY BE INSTALLED IN THE ATTIC ONLY IF THE
 FOLLOWING CONDITIONS ARE MET.
 1) THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET OF AN ATTIC ACCESS.
 2) A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT
 DOWN THE UNIT WHEN THE CONDENSATION DRAIN IS NOT
 WORKING PROPERLY.
 3) THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4) A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOME OWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
 NOTICE TO HOMEOWNER
  
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIR CONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR CONDITIONING SYSTEM IS EQUIPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By lcrespo Date 2020-09-15 Time 17:41 Rev Time 0.00
Received By lcrespo Date 2020-09-15 Time 17:41 Sent To  
Notes
2020-09-15 17:42:3009/15/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-09-30 Cont ID  
Sent By jgomez Date 2020-09-30 Time 15:41 Rev Time 0.00
Received By jgomez Date 2020-09-30 Time 15:41 Sent To  
Notes
2020-09-30 15:42:16SHINGLES FL10124-R26.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 13:37 Rev Time 0.00
Received By equinone Date 2020-10-20 Time 13:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By medwards Date 2020-09-21 Time 15:18 Rev Time 0.00
Received By medwards Date 2020-09-21 Time 15:18 Sent To  
Notes
2020-09-21 15:19:23PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-18 Cont ID  
Sent By rthermid Date 2020-09-18 Time   Rev Time  
Received By rthermid Date 2020-09-18 Time   Sent To I
Notes
***NONE***