Plan Review Details - Permit 20081412
Plan Review Stops For Permit 20081412
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By rmcdouga Date 2020-12-16 Time 14:02 Rev Time 0.00
Received By rmcdouga Date 2020-12-16 Time 14:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By rmcdouga Date 2020-10-20 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2020-10-20 Time 16:25 Sent To  
Notes
2020-10-20 16:36:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FIRST PAGE OF THE POOL PLANS IS NUMBERED 1 OF 4.
 THERE WERE ONLY 3 PAGES OF PLANS. THE OTHERS ARE
 NUMBERED 2 OF 3 AND 3 OF 3. PLEASE CORRECT. FBC 107.2.1
  
 2) THE FIRST PAGE OF THE PLANS IS NOT SIGNED AND SEALED
 BY THE ENGINEER. FS 471

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-09 Cont ID  
Sent By ppetty Date 2020-12-09 Time 09:51 Rev Time 0.00
Received By ppetty Date 2020-12-09 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-05 Cont ID  
Sent By ppetty Date 2020-10-05 Time 13:08 Rev Time 0.00
Received By ppetty Date 2020-10-05 Time 12:34 Sent To  
Notes
2020-10-05 13:13:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 2.INCLUDE NEW GUEST HOUSE IN CALCULATION IF ON SAME
 SERVICE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-16 Cont ID  
Sent By rmcdouga Date 2020-12-16 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2020-12-08 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-03 Cont ID  
Sent By jleahy Date 2020-11-03 Time 07:19 Rev Time 0.00
Received By jleahy Date 2020-10-02 Time 11:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-09 Cont ID  
Sent By lcrespo Date 2020-12-09 Time 09:50 Rev Time 0.00
Received By lcrespo Date 2020-12-09 Time 09:40 Sent To  
Notes
2020-12-09 09:51:3612/09/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-05 Cont ID  
Sent By lcrespo Date 2020-10-05 Time 10:13 Rev Time 0.00
Received By lcrespo Date 2020-10-05 Time 09:57 Sent To  
Notes
2020-10-05 10:13:2610/05/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE PUMP CURVE AND SHOW ON THE POOL PUMP
 CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING
 INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM THE
 MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1.
  
 2. PLEASE SUBMIT SPECIFICATIONS FOR THE PUMP AND
 CARTRIDGE FILTER PER THE WPB AMEND. TO FBC SEC.
 107.2.1.
  
 3. THIS IS A MULTI-FAMILY DWELLING, IF THERE ARE NOT
 TWO METERS FOR WATER USERS IT WILL REQUIRE TO INSTALL A
 BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF DELIVERY.
 THE TYPE OF BACKFLOW ASSEMBLY REQUIRED WILL BE
 DEPENDENT UPON THE DEGREE OF HAZARD POSED BY THE WATER
 USER. IF ONE METER THIS PROPERTY WILL REQUIRE A REDUCED
 PRESSURE ZONE ASSEMBLY VACUUM BREAKER. A PERMIT IS
 REQUIRED BY A LICENSED CONTRACTOR AND MUST BE CERTIFIED
 BY UTILITIES BEFORE FINAL INSPECTION. PLEASE CONTACT
 THE CITY OF WPB UTILITIES AT 561-822-2240 FOR FURTHER
 DIRECTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By rmcdouga Date 2020-12-16 Time 14:03 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By rmcdouga Date 2020-10-20 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2020-10-20 Time 16:25 Sent To  
Notes
2020-10-20 16:28:29SHEET 1 OF THE POOL PLANS IS NOT SIGNED AND SEALED.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-30 Cont ID  
Sent By rthermid Date 2020-10-30 Time   Rev Time  
Received By rthermid Date 2020-10-30 Time   Sent To I
Notes
***NONE***