Plan Review Details - Permit 20081327
Plan Review Stops For Permit 20081327
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-16 Cont ID  
Sent By rmcphers Date 2020-11-16 Time 13:04 Rev Time 0.00
Received By rmcphers Date 2020-11-16 Time 13:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-13 Cont ID  
Sent By rmcphers Date 2020-10-13 Time 08:35 Rev Time 0.00
Received By rmcphers Date 2020-10-13 Time 08:35 Sent To  
Notes
2020-10-13 08:36:26SOLAR PANELS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
 2ND REVIEW
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ON DRAWING S-2 - ON THE "ATTACHMENT DIAGRAM" PLEASE
 DESCRIBE WHAT THE "POLYSET AH 160" IS ATTACHED TO
 (PLYWOOD, CONCRETE, EXISTING ROOFING SYSTEM ETC.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By rmcphers Date 2020-09-23 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2020-09-23 Time 15:00 Sent To  
Notes
2020-09-23 15:30:13SOLAR PANELS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ON DRAWING S-2 - ON THE "ATTACHMENT DIAGRAM" PLEASE
 DESCRIBE WHAT THE "POLYSET AH 160" IS ATTACHED TO
 (PLYWOOD, CONCRETE, EXISTING ROOFING SYSTEM ETC.)

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-11-13 Cont ID  
Sent By equinone Date 2020-11-13 Time 16:04 Rev Time 0.00
Received By equinone Date 2020-11-13 Time 16:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By jleahy Date 2020-10-13 Time 10:07 Rev Time 0.00
Received By jleahy Date 2020-10-13 Time 10:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-14 Cont ID  
Sent By jleahy Date 2020-09-14 Time 11:29 Rev Time 0.00
Received By jleahy Date 2020-09-14 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-16 Cont ID  
Sent By rmcphers Date 2020-11-16 Time 13:05 Rev Time 0.00
Received By rmcphers Date 2020-11-03 Time 16:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-13 Cont ID  
Sent By jleahy Date 2020-10-13 Time 10:07 Rev Time 0.00
Received By jleahy Date 2020-09-29 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-23 Cont ID  
Sent By rmcphers Date 2020-09-23 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2020-08-28 Time 11:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-03 Cont ID  
Sent By jgomez Date 2020-11-03 Time 16:21 Rev Time 0.00
Received By jgomez Date 2020-11-03 Time 15:15 Sent To  
Notes
2020-11-03 16:22:28DRAWINGS C1, E1, S1 AND S2 HAVE ENGINEER'S ORIGINAL
 SEAL/SIGNATURE. JG.
  
 NOTE:
 ALL THESE DRAWINGS WERE UPLOADED TO PROJECTDOX TO AVOID
 CONFLICTS/DELAYS BECAUSE THE ENGINEER WHO SIGNED AND
 SEALED THE HARDCOPY DRAWINGS WAS A DIFFERENT ENGINEER.
 JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-13 Cont ID  
Sent By rmcphers Date 2020-10-13 Time 08:38 Rev Time 0.00
Received By rmcphers Date 2020-10-13 Time 08:38 Sent To  
Notes
2020-10-13 08:39:112ND REVIEW - - WHEN DRAWINGS ARE OPENED IN THE "ADOBE
 READER" IT STATES THAT THE SIGNATURES ARE "INVALID" - -
 - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By rmcphers Date 2020-09-23 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2020-09-23 Time 15:30 Sent To  
Notes
2020-09-23 15:31:59WHEN DRAWINGS ARE OPENED IN THE "ADOBE READER" IT
 STATES THAT THE SIGNATURES ARE "INVALID" - - - SIGNED
 AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-11-12 Cont ID  
Sent By rthermid Date 2020-11-12 Time   Rev Time 0.00
Received By rthermid Date 2020-11-12 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-10-06 Cont ID  
Sent By rthermid Date 2020-10-06 Time   Rev Time 0.00
Received By rthermid Date 2020-10-06 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-09 Cont ID  
Sent By rthermid Date 2020-09-09 Time   Rev Time  
Received By rthermid Date 2020-09-09 Time   Sent To I
Notes
***NONE***