| Plan Review Stops For Permit 20081311 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2020-11-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-11-16 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-11-16 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2020-11-16 16:33:56 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | 4TH BUILDING REVIEW APPROVED WITH PROVISOS: | | | | | | 1) THE ACCESSIBLE STAIR, RAMP, LANDINGS AND HANDRAILS | | | MUST BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH | | | THE FLORIDA ACCESSIBILITY CODE INCLUDING SLOPES, | | | CLEARANCES, MANEUVERABILITY AND ALL OTHER REQUIREMENTS | | | OF THE FLORIDA ACCESSIBILITY CODE. THESE REQUIREMENTS | | | WILL BE CONFIRMED AT TIME OF INSPECTION. | | | | | | NOTES: PLEASE SEE NFIP AND SIGNATURE REVIEWS. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-11-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-11-02 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-11-02 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2020-11-12 12:51:38 | CHANGED REVIEW PASS TO FAIL; GENERATOR WILL BE REMOVED | | | | | | | | 2020-11-02 07:50:51 | PROVISO - MECHANICAL EQUIPMENT TO BE RAISED TO 15.9' | | | NAVD88 | | | | | | BUILDING HEIGHT AND AREA COMPLIES WITH TYPE 5 | | | CONSTRUCTION, SO CAN BE CONSIDERED AS ONE BUILDING, | | | THEREFORE DISTANCE TO PROPERTY LINE CAN BE DISREGARDED | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-10-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-10-04 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-10-04 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2020-10-04 14:53:26 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20081311 | | | ADD: 2277 PALM BEACH LAKES BLVD. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: 281-960-9605 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: SUN. OCT. 04TH/2020 | | | ACTION: DENIED | | | | | | NOTICE: FOR BUILDING REVIEW NO TRANSMITTAL LETTER WAS | | | SUBMITTED. PLANS DO NOT RELECT A VERSION 2. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) | | | | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | SECOND REQUEST FOR ALL COMMENTS: | | | 1) UNDER FLORIDA LICENSING LAWS A LICENSED COMPANY/ | | | INDIVIDUAL (QUALIFIER) MUST APPLY FOR A PERMIT TO | | | INSTALL A MANUFACTURED BUILDING. WE COULD NOT SEE WHERE | | | SATELLITE STRUCTURES HAS ANY FLORIDA LICENSING. | | | | | | 2) PLEASE NOTE THE SUBMITTED SURVEY DOES NOT SHOW THIS | | | PROPERTY IS IN AN AE FLOOD ZONE. PLEASE SUBMIT A | | | CURRENT SURVEY SHOWING THE LOCATION OF THE AE FLOOD | | | ZONE AND THE PROPOSED LOCATION OF THE NEW MANUFACTURED | | | BUILDING. IF THE MANUFACTURED BUILDING IS IN AN AE | | | FLOOD ZONE, THEN THE BOTTOM OF THE FLOOR FRAMING MUST | | | BE ABOVE THE BASE FLOOD WITH THE ADDITIONAL 2 FEET | | | FREEBOARD BY WEST PALM BEACH FLOOD ORDINANCES. | | | | | | FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF | | | AGRICULTURE | | | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & | | | CONTROL | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION | | | 94-546. STRUCTURE IS IN AN "A" FLOOD ZONE. A FLOOD | | | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW | | | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN | | | ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF PERMIT | | | APPLICATION AFTER SEPT. 12/2016, | | | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE | | | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. | | | AFTER OCT. 11/ 2017 THE BUILDING DEPARTMENT WILL HAVE | | | ADOPTED THE NEW FLOOD MAPS IN NAVD 88 ELEVATIONS. YOU | | | CAN GO TO THE WEBSITE: | | | WWW.NGS.NOAA.GOV/TOOLS/VERTCON/VERTCON.HTML FOR | | | CONVERSIONS. | | | | | | 3) THE SUBMITTED SURVEY SHOWS THE LOCATION OF THE | | | MANUFACTURED BUILDING AND EXISTING BUILDING BUT DOES | | | NOT PROVIDE AN ASSUMED PROPERTY LINE BETWEEN THE 2 | | | STRUCTURES NOR SHOW WALL AND WINDOW RATINGS BECAUSE OF | | | THE CLOSENESS OF THE 2 STRUCTURES. SEE 2017 FBC-B | | | SECTIONS: | | | TABLE 602 FIRE RESISTANCE RATINGS FOR EXTERIOR WALLS | | | BASED ON FIRE SEPARATION DISTANCE | | | TABLE 705.8 FIRE SEPARATION DISTANCE AND DEGREE OF | | | OPENING PROTECTIVES. | | | | | | 4) STAIR & RAMP SHEETS 11-19ALL SHOW THEY ARE APPROVED | | | IN TEXAS, THEY DO NOT SHOW A FLORIDA REGISTERED | | | ENGINEER. FLORIDA STATUTE 471. | | | | | | 5) SHEET 10 THE ACCESSIBLE RAMP SHEET INDICATES THE TOP | | | LANDING IS 5 FEET 4 INCHES BY 5 FEET 4 INCHES. THE PLAN | | | IS NOT CLEAR IF THIS IS A OUTSIDE MEASUREMENT OR INSIDE | | | MEASUREMENT OF THE GUARDRAIL? THE TOP LANDING MUST BE A | | | CLEAR LANDING OF 60 INCHES BY 60 INCHES CLEAR. 2017 | | | FBC-ACCESSIBILITY CODE 405.7.4. | | | | | | 6) SHEET 10 THERE IS NO DIMENSION FROM THE LATCH SIDE | | | OF THE DOOR TO THE GUARDRAIL TO THE RIGHT SIDE OF THE | | | DOOR. WHEN CALIBRATING THE PLAN AND MEASURING THE | | | DISTANCE FROM THE EDGE OF DOOR TO THE GUARDRAIL THERE | | | APPEARS TO BE ONLY 18 INCHES. THE 2017 | | | FBC-ACCESSIBILITY CODE REQUIRES 2-0 FEET MANEUVERING | | | CLEARANCE SEE FIGURE 404.2.4.1(H). | | | | | | 7) SHEET 2 SHOWS THE MANUFACTURES BUILDING FLOOR PLAN | | | AND NO LAYOUT OF THE STAIRS AND LANDING NOR THE RAMP | | | AND TOP LANDING. THE SHEET 10 FOR THE RAMP INDICATES | | | THE RAMP AND TOP LANDING ARE 35 FEET 4 INCHES LONG THE | | | DISTANCE BETWEEN THE 2 DOORS IS ONLY 31.20 FEET. PLEASE | | | PROVIDE THE FLOOR PLAN WITH BOTH LANDINGS FOR DOOR AND | | | RAMP PLUS THE STAIR AND RAMP. 107.2.1.2 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 8) PLEASE PROVIDE HOW LONG THIS UNIT IS INTENDED TO BE | | | AT THIS SITE, MAY REQUIRE IMPACT FEES. | | | | | | 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-09-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-09-10 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-09-10 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2020-09-10 12:03:21 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20081311 | | | ADD: 2277 PALM BEACH LAKES BLVD. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: 281-960-9605 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. SEPT.10TH/2020 | | | ACTION: DENIED | | | | | | 1) UNDER FLORIDA LICENSING LAWS A LICENSED COMPANY/ | | | INDIVIDUAL (QUALIFIER) MUST APPLY FOR A PERMIT TO | | | INSTALL A MANUFACTURED BUILDING. WE COULD NOT SEE WHERE | | | SATELLITE STRUCTURES HAS ANY FLORIDA LICENSING. | | | | | | 2) PLEASE NOTE THE SUBMITTED SURVEY DOES NOT SHOW THIS | | | PROPERTY IS IN AN AE FLOOD ZONE. PLEASE SUBMIT A | | | CURRENT SURVEY SOWING THE LOCATION OF THE AE FLOOD ZONE | | | AND THE PROPOSED LOCATION OF THE NEW MANUFACTURED | | | BUILDING. IF THE MANUFACTURED BUILDING IS IN AN AE | | | FLOOD ZONE, THEN THE BOTTOM OF THE FLOOR FRAMING MUST | | | BE ABOVE THE BASE FLOOD WITH THE ADDITIONAL 2 FEET | | | FREEBOARD BY WEST PALM BEACH FLOOD ORDINANCES. | | | | | | FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF | | | AGRICULTURE | | | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & | | | CONTROL | | | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION | | | 94-546. STRUCTURE IS IN AN "A" FLOOD ZONE. A FLOOD | | | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW | | | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN | | | ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF PERMIT | | | APPLICATION AFTER SEPT. 12/2016, | | | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE | | | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. | | | AFTER OCT. 11/ 2017 THE BUILDING DEPARTMENT WILL HAVE | | | ADOPTED THE NEW FLOOD MAPS IN NAVD 88 ELEVATIONS. YOU | | | CAN GO TO THE WEBSITE: | | | WWW.NGS.NOAA.GOV/TOOLS/VERTCON/VERTCON.HTML FOR | | | CONVERSIONS. | | | | | | 3) THE SUBMITTED SURVEY SHOWS THE LOCATION OF THE | | | MANUFACTURED BUILDING AND EXISTING BUILDING BUT DOES | | | NOT PROVIDE AN ASSUMED PROPERTY LINE BETWEEN THE 2 | | | STRUCTURES NOR SHOW WALL AND WINDOW RATINGS BECAUSE OF | | | THE CLOSENESS OF THE 2 STRUCTURES. SEE 2017 FBC-B | | | SECTIONS: | | | TABLE 602 FIRE RESISTANCE RATINGS FOR EXTERIOR WALLS | | | BASED ON FIRE SEPARATION DISTANCE | | | TABLE 705.8 FIRE SEPARATION DISTANCE AND DEGREE OF | | | OPENING PROTECTIVES. | | | | | | 4) STAIR & RAMP SHEETS 11-19ALL SHOW THEY ARE APPROVED | | | IN TEXAS, THEY DO NOT SHOW A FLORIDA REGISTERED | | | ENGINEER. FLORIDA STATUTE 471. | | | | | | 5) SHEET 10 THE ACCESSIBLE RAMP SHEET INDICATES THE TOP | | | LANDING IS 5 FEET 4 INCHES BY 5 FEET 4 INCHES. THE PLAN | | | IS NOT CLEAR IF THIS IS A OUTSIDE MEASUREMENT OR INSIDE | | | MEASUREMENT OF THE GUARDRAIL? THE TOP LANDING MUST BE A | | | CLEAR LANDING OF 60 INCHES BY 60 INCHES CLEAR. 2017 | | | FBC-ACCESSIBILITY CODE 405.7.4. | | | | | | 6) SHEET 10 THERE IS NO DIMENSION FROM THE LATCH SIDE | | | OF THE DOOR TO THE GUARDRAIL TO THE RIGHT SIDE OF THE | | | DOOR. WHEN CALIBRATING THE PLAN AND MEASURING THE | | | DISTANCE FROM THE EDGE OF DOOR TO THE GUARDRAIL THERE | | | APPEARS TO BE ONLY 18 INCHES. THE 2017 | | | FBC-ACCESSIBILITY CODE REQUIRES 2-0 FEET MANEUVERING | | | CLEARANCE SEE FIGURE 404.2.4.1(H). | | | | | | 7) SHEET 2 SHOWS THE MANUFACTURES BUILDING FLOOR PLAN | | | AND NO LAYOUT OF THE STAIRS AND LANDING NOR THE RAMP | | | AND TOP LANDING. THE SHEET 10 FOR THE RAMP INDICATES | | | THE RAMP AND TOP LANDING ARE 35 FEET 4 INCHES LONG THE | | | DISTANCE BETWEEN THE 2 DOORS IS ONLY 31.20 FEET. PLEASE | | | PROVIDE THE FLOOR PLAN WITH BOTH LANDINGS FOR DOOR AND | | | RAMP PLUS THE STAIR AND RAMP. 107.2.1.2 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | 8) PLEASE PROVIDE HOW LONG THIS UNIT IS INTENDED TO BE | | | AT THIS SITE, MAY REQUIRE IMPACT FEES. | | | | | | 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-11-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-11-16 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-11-16 |
Time |
09:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-10-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-13 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-13 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2020-10-13 14:09:09 | SEE ORIGINAL COMMENTS JLEAHY | | | | | | HOW DOES POWER GET TO THE TRAILER???? |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-09-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-09-14 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-09-11 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2020-09-14 06:52:29 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED TO SHOW SERVICE AND LOCATION OF TE SERVICE, PLEASE | | | INCLUDE WIRE SIZES AND PANEL AND DISCONNECT SIZES ALSO. | | | 215.5 | | | | | | PROVIDE AIC RATING CALCULATION IN ACCORDANCE WITH | | | 110.9, 110.10 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2020-10-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-10-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-10-02 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2020-09-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-09-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-09-10 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2020-09-10 09:53:22 | PREVIOUS FIRE COMMENTS NOT ADDRESSED. | | | | | | PERVIOUS COMMENTS RE-POSTED BELOW: | | | | | | HIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | CONSTRUCTION TRAILERS | | | | | | | | | 1) THE SITE PLAN INDICATED THE LOCATION OF THE TRAILER | | | TOO CLOSE TO THE PROPOSED BUILDING. | | | | | | PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE | | | 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE | | | REQUIRED IN EACH TRAILER. | | | | | | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER | | | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH | | | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER | | | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS | | | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE | | | IN ACCORDANCE WITH TABLE 4.2.1. | | | | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | NOTES: | | | (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY | | | STRUCTURES IS LESS THAN THE MINIMUM SEPARATION | | | DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE | | | CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING | | | WALL LENGTHS OF THE TEMPORARY STRUCTURES. | | | (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES | | | SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL | | | STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO | | | MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE | | | APPLYING THIS TABLE, IS 3600 MM (144 IN.). | | | | | | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | | | | PLEASE PROVIDE THE LOCATION AND APPLICABLE CODE | | | REQUIRED SEPARATION DISTANCE FROM THE PROPOSED OR | | | EXISTING BUILDING OR PROVIDE FIRE SPRINKLERS FOR A 75% | | | REDUCTION OF THE REQUIRED SEPARARTION. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2020-09-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-09-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-09-02 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2020-09-02 16:18:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | CONSTRUCTION TRAILERS | | | | | | | | | 1) THE SITE PALN INDICATED THE LOCATION OF THE TRAILER | | | TOO CLOSE TO THE PROPOSED BUILDING. | | | | | | PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE | | | 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE | | | REQUIRED IN EACH TRAILER. | | | | | | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER | | | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH | | | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER | | | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS | | | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE | | | IN ACCORDANCE WITH TABLE 4.2.1. | | | | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | NOTES: | | | (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY | | | STRUCTURES IS LESS THAN THE MINIMUM SEPARATION | | | DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE | | | CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING | | | WALL LENGTHS OF THE TEMPORARY STRUCTURES. | | | (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES | | | SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL | | | STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO | | | MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE | | | APPLYING THIS TABLE, IS 3600 MM (144 IN.). | | | | | | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, | | | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND | | | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION. | | | | | | PLEASE PROVIDE THE LOCATION AND APPLICABLE CODE | | | REQUIRED SEPARATION DISTANCE FROM THE PROPOSED OR | | | EXISTING BUILDING OR PROVIDE FIRE SPRINKLERS FOR A 75% | | | REDUCTION OF THE REQUIRED SEPARARTION. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2020-08-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-08-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-08-28 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2020-08-28 15:44:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS NO SITE PLAN SHOWING THE EXACT LOCATION OF | | | THE TRAILER INCLUDING PROPERETY LINE, BUILDINGS AND | | | OTHER IMPORTANT OBJECTS. | | | | | | PLEASE PROVIDE A DETAILED SITE PLAN INCLUDING | | | DIMENSIONS. | | | | | | | | | 2) PLEASE PROIVDE A BIEF SCOPE OF WORK NARRATIVE FOR | | | THE PROJECT INCLUDING HOW LONG THE TRAILER IS PROPOSED | | | TO BE THERE. | | | | | | PLEASE PROVIDE. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-11-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-11-16 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-11-16 |
Time |
07:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-10-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-10-13 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-09-30 |
Time |
14:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-09-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-09-22 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-08-28 |
Time |
15:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2020-10-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-10-19 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-10-09 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2020-10-19 17:06:00 | SEE EMAIL FROM WILLIE SWOOPE DATED 10/13 (ADDED TO | | | SUPPORTING DOCS) | | | | | 2020-10-09 14:39:45 | 10/9/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-10-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-10-08 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-10-08 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2020-10-08 10:31:00 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | | | | IMPACT FEES - PAPER SUBMITTALS | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2020-10-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-10-01 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-10-01 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2020-10-01 12:11:46 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT-20081311 | | | | | | CODES IN EFFECT: | | | | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE DETAILS OF HOW THE TEMPORARY FUEL | | | STORAGE TANKS WILL MEET NFPA 30A-2015 SECTION 4.3.10 | | | DOCUMENTATION PROVIDED IN THIS SUBMITTAL. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-09-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-09-09 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-09-09 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2020-09-10 09:30:01 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20081311 | | | | | | CODES IN EFFECT: | | | | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE DETAILS AND SPEC SHEETS OF THE | | | GENERATORS AND THE FUEL TANKS. IT MENTIONS PORTABLE | | | GENERATORS, IS THERE GOING TO BE ANY PIPING FROM TANK | | | TO GENERATORS? WHAT KIND OF TANKS ARE GOING TO BE USED? | | | HOW ARE YOU GOING TO SECURE THE TANKS? HOW ARE YOU | | | GOING TO PROTECT THE TANKS AND THE GENERATORS FROM | | | VEHICULAR TRAFFIC? THE GENERATOR AND FUEL SUPPLY SHOULD | | | BE SUBMITTED AS A SEPARATE SUBMITTAL. FBC FS 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
P |
Date |
2020-11-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-11-16 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-11-16 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2020-11-16 16:58:54 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | 3RD NFIP REVIEW APPROVED WITH PROVISOS: | | | | | | 1) PLEASE REMOVE THE MECHANICAL EQUIPMENT FROM THE | | | SURVEY AND RESUBMIT. | | | | | | 2) PLEASE PROVIDE AN ELEVATION CERTIFICATE DUE TO FLOOD | | | ZONE LOCATION. THE ELEVATION CERTIFICATE MUST BE | | | COMPLETED AS PER THE "FEMA NATIONAL FLOOD INSURANCE | | | PROGRAM ELEVATION CERTIFICATE INSTRUCTIONS" AND THE | | | CITY OF WEST PALM BEACH REQUIREMENTS, ALL EQUIPMENT PAD | | | ELEVATIONS MUST BE INCLUDED. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-11-02 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-11-02 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2020-11-02 08:08:25 | CHANGED TO FAIL; NEW REVIEW REQUIRED (GENERATOR TO BE | | | REMOVED) | | | | | | PROVISO: | | | | | | MECHANICAL EQUIPMENT TO BE RAISED TO 15.9' NAVD88, THEN | | | SUBMIT A NEW ELEVATION CERTIFICATE FOR REVIEW AS A | | | SUBMITTAL | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2020-10-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-10-13 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-10-13 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2020-10-13 16:28:57 | SEE BUILDING |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2020-09-24 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-09-24 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-09-24 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2020-09-24 15:31:28 | 20081311 2277 PALM BEACH LAKES BLVD | | | | | | PLUMBING COMMENTS: APPROVED | | | | | | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | | INSPECTOR'S APPROVAL | | | | | | PROVISO: SEE PLAN PAGE 5 OF 7 (P5); PER FBC PL 608.8.1, | | | PROVIDE AT ALL NON-POTABLE WATER OUTLETS, SIGNAGE | | | STATING ?NON POTABLE WATER IS UTILIZED FOR HANDWASHING | | | AND FLUSHING OF TOILETS; CAUTION: NONPOTABLE WATER-DO | | | NOT DRINK? WITH PICTOGRAPH-DO NOT DRINK INDICATED AS | | | FIGURE 608.8.1. | | | | | | PROVISO: SEE PLAN PAGE 5 OF 7 (P5); PROVIDE FROM | | | PROVIDER OF SANITARY AND NON-POTABLE HOLDING TANKS | | | SERVICE/MAINTENANCE/PUMP-OUT SCHEDULES AS APPLICABLE. | | | SCHEDULE(S) SHALL BE ON SITE PRIOR TO FINAL INSPECTION. | | | | | | SEE PLAN PAGE 5 OF 7 (P5); SEE EMAIL DATED 9/24/2020 | | | FROM BILL SCHAEFER | PROJECT MANAGER/SATELLITE | | | SHELTERS, INC. CONFIRMING OPTIONAL PLUMBING PLAN | | | WITHOUT THE DRINKING / WATER FOUNTAIN IS APPLICABLE. | | | | | | SEE PLAN PAGE SITE REVISED PLAN;SEE EMAIL DATED | | | 9/24/2020 FROM BILL SCHAEFER | PROJECT | | | MANAGER/SATELLITE SHELTERS, INC. CLARIFYING SITE PLAN | | | SHOWING WATER TANK: THE NON-POTABLE WATER TANK AND 275 | | | GALLON SANITARY TANK ARE DIRECTLY ADJACENT TO EACH | | | OTHER. 9/24/2020 | | | | | | PROVISO: ACCESSIBILITY; REVISED SEE PLAN PAGE 1 OF 7 | | | (P1) | | | A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 | | | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC | | | ACC 604.2 | | | B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND | | | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | | WALL PER FBC ACC 604.3.1 | | | C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG | | | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE | | | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR | | | WALL PER FBC ACC 604.5.1 | | | D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG | | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES | | | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 | | | E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. | | | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. | | | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE | | | WATER CLOSET PER FBC ACC 604.6 | | | F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC | | | ACC 604.8. | | | G. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES | | | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS | | | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER | | | FBC ACC 604.4. | | | H. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A | | | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT | | | THE CENTER) OF THE GRIPPING SURFACE, | | | I. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE | | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS | | | REQUIRED BY FBC ACC 306.2 AND 306.3 | | | J. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS | | | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE | | | REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE | | | THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE | | | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE | | | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 | | | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 603.3. | | | | | | | | | | | | | | | | | | 20081311 2277 PALM BEACH LAKES BLVD |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-09-15 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-09-15 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-09-10 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2020-09-15 09:38:20 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 20081311 2277 PALM BEACH LAKES BLVD | | | | | | | | | 2ND REVIEW | | | PLUMBING COMMENTS: DENIED; SEE ITEM 2 COMMENT BELOW | | | | | | 1. PER WPB FBC 107.2.1, CLEARLY INDICATE ON PLAN SHEET | | | 5 OF 7 WHETHER THE PLUMBING PLAN OR THE OPTIONAL | | | PLUMBING PLAN IS APPLICABLE; SANITARY AND WATER RISERS | | | SHALL REFLECT THE APPLICATION. | | | COMMENT | | | SEE PLAN SHEET 5 OF 7 PLUMBING PROVISO: PER PERMIT | | | APPLICANT?S RESPONSE LETTER DATED 9/4/2020, THE | | | PLUMBING PLAN IS APPLICABLE. | | | | | | 2. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE SURVEY | | | THE METER AND BACKFLOW PREVENTER DESIGNATED TO PROVIDE | | | POTABLE WATER TO THE UNIT. PROVIDE ROUTING AND SIZING | | | OF WATER SERVICE TO THE POINT OF CONNECTION AT THE | | | TRAILER. PROVIDE SPEC/DETAIL FOR LEAD FREE RPZ BFP. | | | COMMENT | | | SEE PLAN SHEET SURVEY DENIED REGARDING THE PERMIT | | | APPLICANT?S RESPONSE LETTER DATED 9/4/2020, PER FBC PL | | | 602.3, THE USE OF FRESH WATER SUPPLY TANK CONNECTED TO | | | THE INTERNAL SYSTEM IS NOT PERMITTED AS THERE IS | | | POTABLE CITY UTILITIES WATER AVAILABLE; PROVIDE ROUTING | | | AND SIZING OF WATER SERVICE TO THE POINT OF CONNECTION | | | TO THE TRAILER. PER WPB FBC 107.2.1, PROVIDE | | | SPEC/DETAIL OF LEAD FREE RPZ AND COMPLY WITH THE | | | REQUIREMENTS OF FBC PL SECTION 608. | | | | | | 3. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE SURVEY | | | ONE OF THE FOLLOWING; | | | A. THE CAPACITY AND LOCATION OF A PORTABLE SANITARY | | | HOLDING TANK | | | B. PROVIDE A BUILDING SEWER AND CONNECTION TO THE CITY | | | SEWAGE SYSTEM | | | COMMENT | | | SEE PLAN SHEET SURVEY AND PLAN SHEET 5 OF 7 PLUMBING | | | PROVISO: PER PERMIT APPLICANT?S RESPONSE LETTER DATED | | | 9/4/2020, A 275 GALLON SANITARY HOLDING TANK IS TO BE | | | LOCATED AT THE HITCH END OF THE TRAILER. | | | | | | 4. PER WPB FBC 107.2.1, CLEARLY INDICATE THE FUEL | | | SOURCE AND TYPE FOR THE PORTABLE GENERATORS NOTED ON | | | THE SURVEY. | | | COMMENT | | | SEE PLAN SHEET SURVEY PER PERMIT APPLICANT?S RESPONSE | | | LETTER DATED 9/4/2020, EACH USE TYPE 2 DIESEL, EQUIPPED | | | WITH 90 GALLON FUEL TANK. EXTRA TANK SIZE 500 GALLON. | | | THIS RESPONSE HAS BEEN REFERRED TO MECHANICAL PLANS | | | EXAMINER FOR REVIEW. | | | | | | | | | | | | PROVISO: ACCESSIBILITY; SEE PLAN PAGE 1 OF 7 | | | A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 | | | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC | | | ACC 604.2 | | | B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND | | | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | | WALL PER FBC ACC 604.3.1 | | | C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG | | | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE | | | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR | | | WALL PER FBC ACC 604.5.1 | | | D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG | | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES | | | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 | | | E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. | | | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. | | | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE | | | WATER CLOSET PER FBC ACC 604.6 | | | F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC | | | ACC 604.8. | | | G. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES | | | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS | | | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER | | | FBC ACC 604.4. | | | H. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A | | | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT | | | THE CENTER) OF THE GRIPPING SURFACE, | | | I. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE | | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS | | | REQUIRED BY FBC ACC 306.2 AND 306.3 | | | J. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2 | | | K. DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER | | | FBC ACC 602.1. | | | L. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. | | | M. OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC | | | 602.3. | | | N. SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM | | | ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 602.4. | | | O. THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) | | | MINIMUM FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) | | | MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING | | | BUMPERS PER FBC ACC 602.5. | | | P. THE SPOUT SHALL PROVIDE A FLOW OF WATER 4 INCHES | | | (100 MM) HIGH MINIMUM AND SHALL BE LOCATED 5 INCHES | | | (125 MM) MAXIMUM FROM THE FRONT OF THE UNIT. THE ANGLE | | | OF THE WATER STREAM SHALL BE MEASURED HORIZONTALLY | | | RELATIVE TO THE FRONT FACE OF THE UNIT. WHERE SPOUTS | | | ARE LOCATED LESS THAN 3 INCHES (75 MM) OF THE FRONT OF | | | THE UNIT, THE ANGLE OF THE WATER STREAM SHALL BE 30 | | | DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED BETWEEN 3 | | | INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM FROM THE | | | FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM SHALL | | | BE 15 DEGREES MAXIMUM PER FBC ACC 602.6. | | | Q. SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING | | | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 | | | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND PER FBC ACC 607.2. | | | R. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS | | | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE | | | REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE | | | THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE | | | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE | | | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 | | | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 603.3. | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE | | | DESIGNER IN ACCORDANCE WITH FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20081311 2277 PALM BEACH LAKES BLVD | | | | | | | | 2020-09-10 08:19:17 | FOR JERRY SMITH |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-09-01 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-09-01 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-09-01 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2020-09-01 14:04:04 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 20081311 2277 PALM BEACH LAKES BLVD | | | | | | | | | 1ST REVIEW | | | PLUMBING COMMENTS: DENIED | | | | | | 1. PER WPB FBC 107.2.1, CLEARLY INDICATE ON PLAN SHEET | | | 5 OF 7 WHETHER THE PLUMBING PLAN OR THE OPTIONAL | | | PLUMBING PLAN IS APPLICABLE; SANITARY AND WATER RISERS | | | SHALL REFLECT THE APPLICATION. | | | 2. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE SURVEY | | | THE METER AND BACKFLOW PREVENTER DESIGNATED TO PROVIDE | | | POTABLE WATER TO THE UNIT. PROVIDE ROUTING AND SIZING | | | OF WATER SERVICE TO THE POINT OF CONNECTION AT THE | | | TRAILER. PROVIDE SPEC/DETAIL FOR LEAD FREE RPZ BFP. | | | 3. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE SURVEY | | | ONE OF THE FOLLOWING; | | | A. THE CAPACITY AND LOCATION OF A PORTABLE SANITARY | | | HOLDING TANK | | | B. PROVIDE A BUILDING SEWER AND CONNECTION TO THE CITY | | | SEWAGE SYSTEM | | | 4. PER WPB FBC 107.2.1, CLEARLY INDICATE THE FUEL | | | SOURCE AND TYPE FOR THE PORTABLE GENERATORS NOTED ON | | | THE SURVEY. | | | | | | | | | PROVISO: ACCESSIBILITY; SEE PLAN PAGE 1 OF 7 | | | A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 | | | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC | | | ACC 604.2 | | | B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND | | | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR | | | WALL PER FBC ACC 604.3.1 | | | C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG | | | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE | | | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR | | | WALL PER FBC ACC 604.5.1 | | | D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG | | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES | | | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 | | | E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. | | | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. | | | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE | | | WATER CLOSET PER FBC ACC 604.6 | | | F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC | | | ACC 604.8. | | | G. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES | | | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS | | | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER | | | FBC ACC 604.4. | | | H. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A | | | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT | | | THE CENTER) OF THE GRIPPING SURFACE, | | | I. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE | | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS | | | REQUIRED BY FBC ACC 306.2 AND 306.3 | | | J. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2 | | | K. DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER | | | FBC ACC 602.1. | | | L. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE | | | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH | | | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. | | | M. OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC | | | 602.3. | | | N. SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM | | | ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 602.4. | | | O. THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) | | | MINIMUM FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) | | | MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING | | | BUMPERS PER FBC ACC 602.5. | | | P. THE SPOUT SHALL PROVIDE A FLOW OF WATER 4 INCHES | | | (100 MM) HIGH MINIMUM AND SHALL BE LOCATED 5 INCHES | | | (125 MM) MAXIMUM FROM THE FRONT OF THE UNIT. THE ANGLE | | | OF THE WATER STREAM SHALL BE MEASURED HORIZONTALLY | | | RELATIVE TO THE FRONT FACE OF THE UNIT. WHERE SPOUTS | | | ARE LOCATED LESS THAN 3 INCHES (75 MM) OF THE FRONT OF | | | THE UNIT, THE ANGLE OF THE WATER STREAM SHALL BE 30 | | | DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED BETWEEN 3 | | | INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM FROM THE | | | FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM SHALL | | | BE 15 DEGREES MAXIMUM PER FBC ACC 602.6. | | | Q. SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING | | | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 | | | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND PER FBC ACC 607.2. | | | R. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS | | | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE | | | REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE | | | THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE | | | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE | | | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 | | | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC | | | ACC 603.3. | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE | | | DESIGNER IN ACCORDANCE WITH FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20081311 2277 PALM BEACH LAKES BLVD | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2020-12-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-12-17 |
Time |
05:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-12-17 |
Time |
05:38 |
Sent To |
|
|
| Notes |
| 2020-12-17 05:39:30 | PLANS ARE FOR A STATE APPROVED MANUFACTURED BUILDING | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-11-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-11-16 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-11-16 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2020-11-16 16:41:06 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | 3RD SIGNATURE REVIEW APPROVED WITH PROVISO: | | | | | | PLEASE UPLOAD DOCUMENTS/PLANS WITH 3RD PARTY VERIFIED | | | DIGITAL SIGNATURES TO PROJECT DOX. | | | | | | FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN | | | ORIGINAL. | | | | | | EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO ME, OR YOU CAN MAIL ONE ORIGINAL SIGNED AND SEALED | | | PAPER ORIGINAL WITH A WET SIGNATURE TO: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | | 561-805-6673. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-10-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-10-04 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-10-04 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2020-10-04 14:55:18 | STAIR & RAMP SHEETS 11-19 ALL SHOW THEY ARE APPROVED IN | | | TEXAS, THEY DO NOT SHOW A FLORIDA REGISTERED ENGINEER. | | | FLORIDA STATUTE 471. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-09-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-09-10 |
Time |
12:05 |
Rev Time |
|
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-09-10 12:05:06 | STAIR & RAMP SHEETS 11-19ALL SHOW THEY ARE APPROVED IN | | | TEXAS, THEY DO NOT SHOW A FLORIDA REGISTERED ENGINEER. | | | FLORIDA STATUTE 471. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-10-06 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-10-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2020-10-06 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2020-09-22 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-09-22 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2020-09-22 |
Time |
|
Sent To |
I |
|
| Notes |
|
|