Plan Review Details - Permit 20081298
Plan Review Stops For Permit 20081298
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2020-11-20 Time 13:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-08 Cont ID  
Sent By rmcdouga Date 2020-10-08 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2020-10-08 Time 08:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By rmcdouga Date 2020-09-23 Time 12:30 Rev Time 0.00
Received By rmcdouga Date 2020-09-23 Time 12:30 Sent To  
Notes
2020-09-23 12:43:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRE-FAB GENERATOR PAD DRAWING THAT WERE
 SUBMITTED IS THE CORRECT ONE. HOWEVER, IT IS A COPY AND
 AN ORIGINAL IS REQUIRED WHEN SUBMITTING FOR PUBLIC
 RECORD. FS 471 & FAC 61G-15 SEE SIGNATURE COMMENTS.
2020-09-05 06:43:02VALUE APPEARS LOW. ESTIMATE IS FOR AN UNDERGROUND FUEL
 TANK AND RELATED WORK. PROVIDE VALUE OF ALL LABOR AND
 MATERIALS FOR THE GENERATOR / STRUCTURAL PAD AND
 ELECTRICAL EQUIPMENT. CT

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-06 Cont ID  
Sent By jleahy Date 2020-10-06 Time 07:56 Rev Time 0.00
Received By jleahy Date 2020-10-06 Time 07:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-05 Cont ID  
Sent By cthroop Date 2020-09-05 Time 06:52 Rev Time 0.00
Received By cthroop Date 2020-09-05 Time 06:38 Sent To  
Notes
2020-09-05 07:03:03PLAN REVIEW / GENERATOR / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ESTIMATE IS FOR AN UNDERGROUND FUEL TANK AND RELATED
 WORK. PROVIDE VALUE OF ALL LABOR AND MATERIALS FOR THE
 GENERATOR / STRUCTURAL PAD AND ELECTRICAL EQUIPMENT.
  
 1. CITY OF WPB CHPT. 1 VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR,
 MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE
 OF WORK.
 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY
 THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
 PLEASE INCREASE THE VALUATION ACCORDINGLY.
  
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2020-11-17 Cont ID  
Sent By ccole Date 2020-11-17 Time 15:29 Rev Time 0.00
Received By ccole Date 2020-11-17 Time 15:29 Sent To  
Notes
2020-11-17 15:30:17LP GAS TANK AND GAS PIPING APPROVED UNDER PERMIT-
 20090131.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-09-28 Cont ID  
Sent By ccole Date 2020-09-28 Time 15:03 Rev Time 0.00
Received By ccole Date 2020-09-28 Time 08:53 Sent To  
Notes
2020-09-28 15:06:012ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20081298
 9/28/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST.
 NO NEW PLANS, SPECIFICATIONS ETC. OR COMMENT RESPONSES
 WERE PROVIDED- PLEASE COMPLY.
  
 1) PROVIDE AN LP GAS RISER DRAWING SHOWING THE TYPES
 AND SIZES OF PIPING; TOTAL DEVELOPED LENGTH OF THE
 SYSTEM AND LENGTHS OF BRANCHES TO ALL NEW AND EXISTING
 LP APPLIANCES OR EQUIPMENT; TOTAL BTUH LOAD OF THE
 SYSTEM AND INDIVIDUAL LOADS OF APPLIANCES OR EQUIPMENT;
 LOCATIONS AND TYPES OF SHUTOFF VALVES, LOCATIONS AND
 MAKES AND MODELS OF REGULATORS INCLUDING INLET AND
 OUTLET PRESSURES, LOCATIONS OF UNION, RISERS AND FLEX
 CONNECTORS; AND A LIST OF GAS PIPE SIZING TABLES-
 SECTION 107.2.1 WPB. PLEASE NOTE THE UPDATED GENERAC
 SPECIFICATIONS INDICATE THE A 306,000 FULL BTUH LOAD
 FOR THE 22 KW GENERATOR. PROVIDE UPDATED SPECS AND
 MARKED UP SPECS FOR THE REGULATORS SHOWING THE SELECTED
 MODELS TO BE INSTALLED.
  
 2) SUBMIT A SUB-PERMIT FOR THE INSTALLATION OF THE TANK
 AND THE PIPING- SECTION 105.1 WPB. THE SUBMITTED
 APPLICATIONS BEAR EC LICENCES WHICH ARE NOT VALID FOR
 THE LP TANK INSTALLATION. THE SUB-PERMIT APPLICATION
 SHALL BEAR THE CONTRACTOR'S FDACS LP GAS LICENSE
 NUMBER.
  
 3) PLEASE MARK UP THE SUBMITTED SURVEY TO SHOW THE
 REQUIRED 10 FT. CLEARANCES DISTANCES FROM THE TANK TO
 THE BUILDING, AND ADJACENT PROPERTY LINES- TABLE
 6.3.1.1 NFPA 58. PLEASE SHOW THE PIPING RUN ON THE
 SURVEY FROM THE TANK TO THE GENERATOR.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 5) PROVIDE LP TANK INSTALLATION DETAILS AS OUTLINED IN
 THE SUBMITTED CONTRACT, AND AS REQUIRED BY NFPA 58:
 A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT
 FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION
 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW
 THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL,
 AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS
 B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 &
 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND
 HOW IT WILL BE TESTED- SECTION 6.17.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 08:15 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 07:17 Sent To  
Notes
2020-09-24 08:16:521ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20081298
 9/24/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN LP GAS RISER DRAWING SHOWING THE TYPES
 AND SIZES OF PIPING; TOTAL DEVELOPED LENGTH OF THE
 SYSTEM AND LENGTHS OF BRANCHES TO ALL NEW AND EXISTING
 LP APPLIANCES OR EQUIPMENT; TOTAL BTUH LOAD OF THE
 SYSTEM AND INDIVIDUAL LOADS OF APPLIANCES OR EQUIPMENT;
 LOCATIONS AND TYPES OF SHUTOFF VALVES, LOCATIONS AND
 MAKES AND MODELS OF REGULATORS INCLUDING INLET AND
 OUTLET PRESSURES, LOCATIONS OF UNION, RISERS AND FLEX
 CONNECTORS; AND A LIST OF GAS PIPE SIZING TABLES-
 SECTION 107.2.1 WPB. PLEASE NOTE THE UPDATED GENERAC
 SPECIFICATIONS INDICATE THE A 306,000 FULL BTUH LOAD
 FOR THE 22 KW GENERATOR. PROVIDE UPDATED SPECS AND
 MARKED UP SPECS FOR THE REGULATORS SHOWING THE SELECTED
 MODELS TO BE INSTALLED.
  
 2) SUBMIT A SUB-PERMIT FOR THE INSTALLATION OF THE TANK
 AND THE PIPING- SECTION 105.1 WPB. THE SUBMITTED
 APPLICATIONS BEAR EC LICENCES WHICH ARE NOT VALID FOR
 THE LP TANK INSTALLATION. THE SUB-PERMIT APPLICATION
 SHALL BEAR THE CONTRACTOR'S FDACS LP GAS LICENSE
 NUMBER.
  
 3) PLEASE MARK UP THE SUBMITTED SURVEY TO SHOW THE
 REQUIRED 10 FT. CLEARANCES DISTANCES FROM THE TANK TO
 THE BUILDING, AND ADJACENT PROPERTY LINES- TABLE
 6.3.1.1 NFPA 58. PLEASE SHOW THE PIPING RUN ON THE
 SURVEY FROM THE TANK TO THE GENERATOR.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 5) PROVIDE LP TANK INSTALLATION DETAILS AS OUTLINED IN
 THE SUBMITTED CONTRACT, AND AS REQUIRED BY NFPA 58:
 A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT
 FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION
 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW
 THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL,
 AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS
 B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 &
 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND
 HOW IT WILL BE TESTED- SECTION 6.17.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2020-11-18 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-11-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-11-16 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-27 Cont ID  
Sent By cpuell Date 2020-10-27 Time 17:44 Rev Time 0.00
Received By cpuell Date 2020-09-25 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-09-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-01 Time 16:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-11-17 Cont ID  
Sent By ccole Date 2020-11-17 Time 15:30 Rev Time 0.00
Received By ccole Date 2020-11-17 Time 15:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-09-28 Cont ID  
Sent By ccole Date 2020-09-28 Time 15:03 Rev Time 0.00
Received By ccole Date 2020-09-28 Time 08:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-24 Cont ID  
Sent By ccole Date 2020-09-24 Time 07:17 Rev Time 0.00
Received By ccole Date 2020-09-24 Time 07:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-11-24 Cont ID  
Sent By jgomez Date 2020-11-24 Time 09:17 Rev Time 0.00
Received By jgomez Date 2020-11-24 Time 09:15 Sent To  
Notes
2020-11-24 09:19:08GENERATOR CONCRETE PAD DWG WITH ENGINEER'S EMBOSSED
 SEAL AND ORIGINAL SIGNATURE MATCHES APPROVED ONE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-11-20 Cont ID  
Sent By rmcdouga Date 2020-11-20 Time 13:38 Rev Time 0.00
Received By rmcdouga Date 2020-11-20 Time 13:30 Sent To  
Notes
2020-11-20 13:39:09THE PREFABRICATED GENERATOR PAD DRAWINGS ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ENGINEER. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
 CONTRACTOR SIGNATURE VERIFIED ON LOAD CALC'S AND
 ELECTRICAL RISER. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-11-17 Cont ID  
Sent By ccole Date 2020-11-17 Time 15:33 Rev Time 0.00
Received By ccole Date 2020-11-17 Time 15:33 Sent To  
Notes
2020-11-17 15:35:00SIGNATURE REVIEW
 11/17/2020
  
 THE PREFABRICATED GENERATOR PAD DRAWINGS ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ENGINEER. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & SECTION 61G15-23.005
 FAC.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-08 Cont ID  
Sent By rmcdouga Date 2020-10-08 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2020-10-08 Time 08:26 Sent To  
Notes
2020-10-08 08:27:12THE PREFABRICATED GENERATOR PAD DRAWINGS ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ENGINEER. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By rmcdouga Date 2020-09-23 Time 12:30 Rev Time 0.00
Received By rmcdouga Date 2020-09-23 Time 12:30 Sent To  
Notes
2020-09-23 12:35:18THE PREFABRICATED GENERATOR PAD DRAWINGS ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ENGINEER. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
2020-09-05 06:51:23CONTRACTOR SIGNATURE VERIFIED ON LOAD CALC'S AND
 ELECTRICAL RISER. CT

Review Stop Z ZONING
Rev No 2 Status P Date 2020-10-26 Cont ID  
Sent By kalexand Date 2020-10-26 Time 11:59 Rev Time 0.00
Received By kalexand Date 2020-10-26 Time 11:59 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By kalexand Date 2020-09-17 Time 16:55 Rev Time 0.00
Received By kalexand Date 2020-09-17 Time 16:55 Sent To I
Notes
2020-09-17 16:58:58ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED
 SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR
 EQUIPMENT TO REAR PROPERTY LINE
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved