Plan Review Details - Permit 20081267
Plan Review Stops For Permit 20081267
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-11-23 Cont ID  
Sent By cthroop Date 2020-11-23 Time 15:57 Rev Time 0.00
Received By cthroop Date 2020-11-23 Time 15:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-11-05 Cont ID  
Sent By cthroop Date 2020-11-05 Time 14:19 Rev Time 0.00
Received By cthroop Date 2020-11-05 Time 13:23 Sent To  
Notes
2020-11-05 14:27:38PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 RE: GENERATOR SPECIFICATIONS AND PRE-CAST GENERATOR PAD
 ENGINEERING:
  
  
 1. PROVIDE THE CURRENT 2020 SPECIFICATIONS OF PROPOSED
 36KW GENERATOR. (GENERATOR SPECS SUBMITTED FOR REVIEW
 ON 9/1/2020 ARE THE SAME 2017 GENERATOR SPEC'S
 PREVIOUSLY SUBMITTED)
 SPECIFICATIONS SUBMITTED ARE FOR A 2017 GENERAC MODEL
 RG038 38KW GENERATOR.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE A PRE-CAST GENERATOR PAD DESIGN WITH CORRECT
 DATA: ( NO NEW PRE-CAST GENERATOR PAD SUBMITTED FOR
 REVIEW)
 2A. WIND DESIGN REQUIREMENTS FOR THIS SITE ARE VULT
 170MPH, VASD 132MPH, RISK CATEGORY II AND EXPOSURE
 CATEGORY C. DESIGN PRESSURE FROM TABLE IS 41.65
 2B. GENERATOR TABLE SHALL INCLUDE CORRECT MODEL OF
 PROPOSED GENERATOR, CORRECT WEIGHT OF GENERATOR FROM
 SPECIFICATIONS SUBMITTED AND CORRECT ALLOWABLE
 PRESSURE.
 CURRENT TABLE HAS MODEL QTO3624ANAX, GENERATOR WEIGHT
 OF 1271 LBS AND ALLOWABLE PRESSURE OF 40.50.
  
 NOTE 1: PRE-CAST GENERATOR PAD ENGINEERING REQUIRES
 SIGNATURE OF DESIGN PROFESSIONAL. SEE COMMENTS UNDER
 SIGNATURE REVIEW. (NOT ADDRESSED)
  
 NOTE 2: VALUE - CORRECTED
  
 NOTE 3: TWO DOC'S IN SUPPORTING DOC'S FOLDER ARE
 MISLABELED:
 1. SURVEY IS LABELED GENERATOR SPECIFICATIONS
 2. GENERATOR SPECIFICATIONS ARE LABELED SURVEY.
  
 NOTE 4: THREE DOC'S IN DRAWINGS FOLDER ARE MISLABELED:
 1. GENERATOR SPECIFICATIONS ARE LABELED GENERATOR SLAB
 SPECIFICATIONS
 2. PROPERTY DETAIL IS LABELED BENEBY CONTRACT
 3. COPY OF 1ST PERMIT APPLICATION IS LABELED BENEBY
 PROERTY APPRAISER
  
 NEW COMMENT:
  
 SEVERAL OF THE NEW DOCUMENTS SUBMITTED ARE MISLABLED.
  
 WHEN RE-SUBMITTING, USE THE REQUIRED NAMING CONVENTION
 FOR EACH DOCUMENT
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-17 Cont ID  
Sent By cthroop Date 2020-10-17 Time 06:58 Rev Time 0.00
Received By cthroop Date 2020-10-16 Time 15:51 Sent To  
Notes
2020-10-17 08:05:22PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: GENERATOR SPECIFICATIONS AND PRE-CAST GENERATOR PAD
 ENGINEERING:
  
  
 1. PROVIDE THE CURRENT 2020 SPECIFICATIONS OF PROPOSED
 36KW GENERATOR.
 SPECIFICATIONS SUBMITTED ARE FOR A 2017 GENERAC MODEL
 RG038 38KW GENERATOR.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE A PRE-CAST GENERATOR PAD DESIGN WITH CORRECT
 DATA:
 2A. WIND DESIGN REQUIREMENTS FOR THIS SITE ARE VULT
 170MPH, VASD 132MPH, RISK CATEGORY II AND EXPOSURE
 CATEGORY C. DESIGN PRESSURE FROM TABLE IS 41.65
 2B. GENERATOR TABLE SHALL INCLUDE CORRECT MODEL OF
 PROPOSED GENERATOR, CORRECT WEIGHT OF GENERATOR FROM
 SPECIFICATIONS SUBMITTED AND CORRECT ALLOWABLE
 PRESSURE.
 CURRENT TABLE HAS MODEL QTO3624ANAX, GENERATOR WEIGHT
 OF 1271 LBS AND ALLOWABLE PRESSURE OF 40.50.
  
 NOTE 1: PRE-CAST GENERATOR PAD ENGINEERING REQUIRES
 SIGNATURE OF DESIGN PROFESSIONAL. SEE COMMENTS UNDER
 SIGNATURE REVIEW.
  
 NOTE 2: VALUE HAS BEEN ADJUSTED TO $18,975.00 BASED ON
 NEW APPLICATION SUBMITTED ON 10/08/2020.
  
 NOTE 3: TWO DOC'S IN SUPPORTING DOC'S FOLDER ARE
 MISLABELED:
 1. SURVEY IS LABELED GENERATOR SPECIFICATIONS
 2. GENERATOR SPECIFICATIONS ARE LABELED SURVEY.
  
 NOTE 4: THREE DOC'S IN DRAWINGS FOLDER ARE MISLABELED:
 1. GENERATOR SPECIFICATIONS ARE LABELED GENERATOR SLAB
 SPECIFICATIONS
 2. PROPERTY DETAIL IS LABELED BENEBY CONTRACT
 3. COPY OF 1ST PERMIT APPLICATION IS LABELED BENEBY
 PROERTY APPRAISER
  
 WHEN RE-SUBMITTING, USE THE REQUIRED NAMING CONVENTION
 FOR EACH DOCUMENT
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-22 Cont ID  
Sent By cthroop Date 2020-09-22 Time 16:47 Rev Time 0.00
Received By cthroop Date 2020-09-22 Time 16:29 Sent To  
Notes
2020-09-22 16:52:31PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) VALUE
 CITY OF WPB CHPT. 1 VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR,
 MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE
 OF WORK.
 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY
 THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
 PLEASE INCREASE THE VALUATION ACCORDINGLY.
  
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
 2) PROVIDE CURRENT GENERATOR SPECIFICATIONS. SUBMITTAL
 IS FOR A 36KW GENERATOR.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4) STRUCTURAL PAD DETAIL SHALL BE SIGNED BY DESIGNER.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 5) IDENTIFY LOCATION OF GENERATOR ON SURVEY. PROVIDE
 SETBACK DIMENSIONS TO PROPERTY LINES, BUILDING AND
 BUILDING OPENINGS PER PER 107.2 CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE SITE WIND LOAD CALCULATIONS.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
  
  
2020-09-04 15:32:58VALUE APPEARS LOW. CT

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-17 Cont ID  
Sent By cthroop Date 2020-10-16 Time 16:43 Rev Time 0.00
Received By cthroop Date 2020-10-16 Time 15:51 Sent To  
Notes
2020-10-16 16:47:05NO NOTES
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-04 Cont ID  
Sent By cthroop Date 2020-09-04 Time 15:53 Rev Time 0.00
Received By cthroop Date 2020-09-04 Time 15:31 Sent To  
Notes
2020-09-04 15:54:20PLAN REVIEW GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-12-23 Cont ID  
Sent By jleahy Date 2020-12-23 Time 11:55 Rev Time 0.00
Received By jleahy Date 2020-11-19 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-11-15 Cont ID  
Sent By cpuell Date 2020-11-15 Time 18:26 Rev Time 0.00
Received By cpuell Date 2020-10-30 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-27 Cont ID  
Sent By cpuell Date 2020-10-27 Time 17:42 Rev Time 0.00
Received By cpuell Date 2020-10-09 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-30 Cont ID  
Sent By lmarchan Date 2020-09-30 Time 15:27 Rev Time 0.00
Received By lmarchan Date 2020-09-25 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-22 Cont ID  
Sent By cthroop Date 2020-09-22 Time 16:57 Rev Time 0.00
Received By cthroop Date 2020-09-01 Time 16:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-12-07 Cont ID  
Sent By jgomez Date 2020-12-07 Time 17:52 Rev Time 0.00
Received By jgomez Date 2020-12-07 Time 17:41 Sent To  
Notes
2020-12-07 17:53:22GENERATOR CONCRETE PAD WITH ENGINEER'S EMBOSSED AND
 ORIGINAL SIGNATURE MATCHES APPROVED ONE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-11-23 Cont ID  
Sent By cthroop Date 2020-11-23 Time 16:24 Rev Time 0.00
Received By cthroop Date 2020-11-23 Time 15:40 Sent To  
Notes
2020-11-23 16:25:08PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PRE-CAST GENERATOR PAD
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-11-05 Cont ID  
Sent By cthroop Date 2020-11-05 Time 14:18 Rev Time 0.00
Received By cthroop Date 2020-11-05 Time 13:23 Sent To  
Notes
2020-11-05 14:19:24PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 COMMENTS FROM PREVIOUS REVIEWS HAVE NOT BEEN ADDRESSED.
  
 RE: PRE-CAST GENERATOR PAD DESIGN
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-17 Cont ID  
Sent By cthroop Date 2020-10-17 Time 06:47 Rev Time 0.00
Received By cthroop Date 2020-10-16 Time 15:51 Sent To  
Notes
2020-10-17 06:50:58PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PRE-CAST GENERATOR PAD DESIGN
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-22 Cont ID  
Sent By cthroop Date 2020-09-22 Time 16:52 Rev Time 0.00
Received By cthroop Date 2020-09-22 Time 16:29 Sent To  
Notes
2020-09-22 16:56:32PLAN REVIEW GENERATOR / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SIGNATURE OF DESIGNER ON GENERATOR PAD
 STRUCTURAL DETAIL.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2020-12-18 Cont ID  
Sent By kalexand Date 2020-12-18 Time 14:07 Rev Time 0.00
Received By kalexand Date 2020-12-18 Time 14:07 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2020-11-13 Cont ID  
Sent By kalexand Date 2020-11-13 Time 16:00 Rev Time 0.00
Received By kalexand Date 2020-11-13 Time 15:59 Sent To I
Notes
2020-11-13 16:02:30SEE PREVIOUS COMMENTS.

Review Stop Z ZONING
Rev No 2 Status F Date 2020-10-26 Cont ID  
Sent By kalexand Date 2020-10-26 Time 08:42 Rev Time 0.00
Received By kalexand Date 2020-10-26 Time 08:40 Sent To I
Notes
2020-10-26 08:42:27ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1.GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED
 SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK. THE REQUIRED SIDE
 SETBACK IS 10 FEET, THEREFORE THE MINIMUM SETBACK FOR
 THE PROPOSED GENERATOR SHOULD BE 6 FEET.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By kalexand Date 2020-09-17 Time 16:48 Rev Time 0.00
Received By kalexand Date 2020-09-17 Time 16:47 Sent To I
Notes
2020-09-17 16:49:32ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED
 SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK. THE REQUIRED
 SETBACK IS 10 FT
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved