| 2020-08-28 11:05:41 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20081225 |
| | 8/28/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P1 & P2: PROVIDE AN EQUIPMENT SCHEDULE ON THE |
| | PLAN LISTING THE MAKE AND MODEL OF THE NEW TANKLESS |
| | WATER HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS. |
| | THE SPECS SHALL INCLUDE A TEMPERATURE RISE CHART |
| | INDICATING GPM FLOW TO FIXTURES FOR DETERMINING |
| | ACCURATE SIZING OF THE UNIT. PLEASE NOTE THAT THE GAS |
| | PIPING TO THE HEATER SHALL BE UNDER SEPARATE PERMIT- |
| | SECTIONS M2005.1 & G2448.1 FBC RES. |
| | |
| | 2) P1 & P2: SHOW THE LOCATION OF THE MAIN SHUTOFF VALVE |
| | AT THE WATER SERVICE ENTRANCE INTO THE HOUSE- SECTION |
| | P2903.9.1 FBC RES. THE DRAWINGS INDICATE A SERVICE LINE |
| | A VALVE CONNECTING DIRECTLY TO THE WATER HEATER WHICH |
| | IS NOT IN COMPLIANCE. |
| | |
| | 3) P2: THE LOCATION OF THE EXPANSION TANK ON THE HW |
| | RECIRCULATION LINE WOULD NOT BE IN COMPLIANCE FOR A |
| | STORAGE TYPE WATER HEATER PER SECTION 607.3 FBC P, |
| | HOWEVER THE PLUMBING FOR THE TANKLESS WATER HEATER |
| | SHALL BE DONE IN ACCORDANCE WITH THE MANUFACTURER'S |
| | SPECS WHICH HAVE NOT BEEN SUBMITTED. VERIFICATION OF |
| | THE LOCATION PENDING SUBMITTAL OF SPECS- SECTIONS |
| | M2005.1 & G2448.1 FBC RES. |
| | |
| | 4) BECAUSE THERE APPEARS TO BE TWO RESIDENTIAL BUILDING |
| | ON THIS PROPERTY, A BACKFLOW PREVENTER AT THE METER MAY |
| | BE REQUIRED. PLEASE CONTACT THE CITY OF WPB UTILITIES |
| | AT 561-822-2240 FOR FURTHER DIRECTION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |