Plan Review Details - Permit 20081239
Plan Review Stops For Permit 20081239
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2021-01-05 Time 14:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-01-04 Cont ID  
Sent By jwitmer Date 2021-01-04 Time 14:03 Rev Time 0.00
Received By jwitmer Date 2021-01-04 Time 13:31 Sent To  
Notes
2021-01-04 14:03:422014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 20081239
 W. P. B. PERMIT: 17041276
 ADD: 1626 OKEECHOBEE RD.
 CONT: SPECTRUM RENOVATIONS LLC
 TEL: 561-291-8350
 E-MAIL:
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: MON. JAN. 04TH/ 2021
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B). WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) 3RD REQUEST. SHEET A-14 SUBMITTED 8/27/2020 HAS NOT
 EVER BEEN UPDATED FOR CODE COMPLIANCE. SHEET A-14 THE
 1ST FLOOR A/C PLAN STILL SHOWS THE AIRDUCT/ CEILING
 GRILLES PENETRATING THE RATED CEILING BUT NO NOTES
 STATING THE INSTALLATION OF RADIANT DAMPERS. IF THE
 PLAN WERE TO SHOW THE DUCTS AND GRILLES TO BE INSTALLED
 BETWEEN THE RATED CEILING AND DROPPED CEILING AREAS AND
 SOFFIT WITH THE AIR VENTS BEING SIDE WALL, BELOW THE
 RATED CEILING RADIANT DAMPERS WOULD NOT BE REQUIRED.
 THE CURRENT PROPOSED PLAN SHOWS THE AIR VENTS IN THE
 CEILING NEEDING RADIANT DAMPERS.
 NOTE BUILDING PLAN REVIEW BEFORE PERMIT ISSUANCE, ASKED
 THIS QUESTION IN THE 2ND OF 4 REVIEWS. 6B) 420.3
 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES SEPARATING
 DWELLING UNITS IN THE SAME BUILDINGS, FLOOR ASSEMBLIES
 SEPARATING SLEEPING UNITS IN THE SAME BUILDING AND
 FLOOR ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS
 FROM OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME
 BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES
 IN ACCORDANCE WITH SECTION 711.
 THE ISSUED SET OF PLANS SHEET CUT SECTION ON SHEET 19
 OF 31 SHOWS T 5/8 INCH TYPE X FIRE DRYWALL ATTACHED TO
 THE BOTTOM CHORD OF THE FLOOR ASSEMBLY MAKING A PORTION
 OF THE RATED HORIZONTAL ASSEMBLY. ISSUES SET OF PLANS
 SHEET A-14.0 SHOWS DROPPED SOFFITS FROM THE 9-FOOT-HIGH
 RATED CEILINGS.
  
 THE PROPOSED REVISION DOES NOT SHOW THE DROPPED SOFFIT
 AND PROPOSED DUCTWORK PENETRATING THE RATED FLOOR
 ASSEMBLY. FOR THIS TYPE OF CONSTRUCTION TO PASS
 COMPLIANCE WOULD REQUIRE COMPLIANCE WITH 717.6.2
 MEMBRANE PENETRATIONS 2014 FBC-B, ONE OF THREE METHODS.
 717.6.2.1 CEILING RADIATION DAMPERS. THE SAME ISSUE
 OCCURS ON THE 2ND FLOOR WITH RATED CEILING.
  
 2ND REQUEST. SEMI-COMPLIED. THE SUBMITTED 2ND FLOOR
 PLAN NOW SHOWS THE INSTALLATION OF RADIANT DAMPERS IN
 THE FIRE RATED CEILING. SHEET A-14 THE 1ST FLOOR A/C
 PLAN STILL SHOWS THE AIRDUCT/ CEILING GRILLES
 PENETRATING THE RATED CEILING BUT NO NOTES STATING THE
 INSTALLATION OF RADIANT DAMPERS. IF THE PLAN WERE TO
 SHOW THE DUCTS AND GRILLES TO BE INSTALLED BETWEEN THE
 RATED CEILING AND DROPPED CEILING AREAS AND SOFFIT WITH
 THE AIR VENTS BEING SIDE WALL, BELOW THE RATED CEILING
 RADIANT DAMPERS WOULD NOT BE REQUIRED. THE CURRENT
 PROPOSED PLAN SHOWS THE AIR VENTS IN THE CEILING
 NEEDING RADIANT DAMPERS.
  
 1ST REVIEW NOTES. NOTE BUILDING PLAN REVIEW ASKED THIS
 QUESTION IN THE 2ND OF 4 REVIEWS. 6B) 420.3 HORIZONTAL
 SEPARATION. FLOOR ASSEMBLIES SEPARATING DWELLING UNITS
 IN THE SAME BUILDINGS, FLOOR ASSEMBLIES SEPARATING
 SLEEPING UNITS IN THE SAME BUILDING AND FLOOR
 ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS FROM
 OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME
 BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES
 IN ACCORDANCE WITH SECTION 711.
  
 THE ISSUED SET OF PLANS SHEET CUT SECTION ON SHEET 19
 OF 31 SHOWS T 5/8 INCH TYPE X FIRE DRYWALL ATTACHED TO
 THE BOTTOM CHORD OF THE FLOOR ASSEMBLY MAKING A PORTION
 OF THE RATED HORIZONTAL ASSEMBLY. ISSUES SET OF PLANS
 SHEET A-14.0 SHOWS DROPPED SOFFITS FROM THE 9-FOOT-HIGH
 RATED CEILINGS.
  
 THE PROPOSED REVISION DOES NOT SHOW THE DROPPED SOFFIT
 AND PENETRATING THE RATED FLOOR ASSEMBLY. FOR THIS TYPE
 OF CONSTRUCTION TO PASS COMPLIANCE WOULD REQUIRE
 COMPLIANCE WITH 717.6.2 MEMBRANE PENETRATIONS 2014
 FBC-B, ONE OF THREE METHODS. 717.6.2.1 CEILING
 RADIATION DAMPERS. THE SAME ISSUE OCCURS ON THE 2ND
 FLOOR WITH RATED CEILING.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-04 Cont ID  
Sent By jwitmer Date 2020-11-04 Time 12:17 Rev Time 0.00
Received By jwitmer Date 2020-11-04 Time 11:26 Sent To  
Notes
2020-11-04 12:17:252014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 20081239
 W. P. B. PERMIT: 17041276
 ADD: 1626 OKEECHOBEE RD.
 CONT: SPECTRUM RENOVATIONS LLC
 TEL: 561-291-8350
 E-MAIL:
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. NOV. 04TH/ 2020
 ACTION: DENIED
  
 1) 2ND REQUEST. SEMI-COMPLIED. THE SUBMITTED 2ND FLOOR
 PLAN NOW SHOWS THE INSTALLATION OF RADIANT DAMPERS IN
 THE FIRE RATED CEILING.
 SHEET A-14 THE 1ST FLOOR A/C PLAN STILL SHOWS THE
 AIRDUCT/ CEILING GRILLES PENETRATING THE RATED CEILING
 BUT NO NOTES STATING THE INSTALLATION OF RADIANT
 DAMPERS. IF THE PLAN WERE TO SHOW THE DUCTS AND GRILLES
 TO BE INSTALLED BETWEEN THE RATED CEILING AND DROPPED
 CEILING AREAS AND SOFFIT WITH THE AIR VENTS BEING SIDE
 WALL, BELOW THE RATED CEILING RADIANT DAMPERS WOULD NOT
 BE REQUIRED. THE CURRENT PROPOSED PLAN SHOWS THE AIR
 VENTS IN THE CEILING NEEDING RADIANT DAMPERS.
  
 1ST REVIEW NOTES. NOTE BUILDING PLAN REVIEW ASKED THIS
 QUESTION IN THE 2ND OF 4 REVIEWS. 6B) 420.3 HORIZONTAL
 SEPARATION. FLOOR ASSEMBLIES SEPARATING DWELLING UNITS
 IN THE SAME BUILDINGS, FLOOR ASSEMBLIES SEPARATING
 SLEEPING UNITS IN THE SAME BUILDING AND FLOOR
 ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS FROM
 OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME
 BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES
 IN ACCORDANCE WITH SECTION 711.
  
 THE ISSUED SET OF PLANS SHEET CUT SECTION ON SHEET 19
 OF 31 SHOWS T 5/8 INCH TYPE X FIRE DRYWALL ATTACHED TO
 THE BOTTOM CHORD OF THE FLOOR ASSEMBLY MAKING A PORTION
 OF THE RATED HORIZONTAL ASSEMBLY. ISSUES SET OF PLANS
 SHEET A-14.0 SHOWS DROPPED SOFFITS FROM THE 9-FOOT-HIGH
 RATED CEILINGS.
  
 THE PROPOSED REVISION DOES NOT SHOW THE DROPPED SOFFIT
 AND PENETRATING THE RATED FLOOR ASSEMBLY. FOR THIS TYPE
 OF CONSTRUCTION TO PASS COMPLIANCE WOULD REQUIRE
 COMPLIANCE WITH 717.6.2 MEMBRANE PENETRATIONS 2014
 FBC-B, ONE OF THREE METHODS. 717.6.2.1 CEILING
 RADIATION DAMPERS. THE SAME ISSUE OCCURS ON THE 2ND
 FLOOR WITH RATED CEILING.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-14 Cont ID  
Sent By jwitmer Date 2020-09-14 Time 17:04 Rev Time 0.00
Received By jwitmer Date 2020-09-14 Time 15:58 Sent To  
Notes
2020-09-14 17:04:162014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 20081239
 W. P. B. PERMIT: 17041276
 ADD: 1626 OKEECHOBEE RD.
 CONT: SPECTRUM RENOVATIONS LLC
 TEL: 561-291-8350
 E-MAIL:
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. SEPT. 14TH/ 2020
 ACTION: DENIED
  
 1) NOTE BUILDING PLAN REVIEW ASKED THIS QUESTION IN THE
 2ND OF 4 REVIEWS. 6B) 420.3 HORIZONTAL SEPARATION.
 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH
 SECTION 711.
  
 THE ISSUED SET OF PLANS SHEET CUT SECTION ON SHEET 19
 OF 31 SHOWS T 5/8 INCH TYPE X FIRE DRYWALL ATTACHED TO
 THE BOTTOM CHORD OF THE FLOOR ASSEMBLY MAKING A PORTION
 OF THE RATED HORIZONTAL ASSEMBLY. ISSUES SET OF PLANS
 SHEET A-14.0 SHOWS DROPPED SOFFITS FROM THE 9-FOOT-HIGH
 RATED CEILINGS.
  
 THE PROPOSED REVISION DOES NOT SHOW THE DROPPED SOFFIT
 AND PENETRATING THE RATED FLOOR ASSEMBLY. FOR THIS TYPE
 OF CONSTRUCTION TO PASS COMPLIANCE WOULD REQUIRE
 COMPLIANCE WITH 717.6.2 MEMBRANE PENETRATIONS 2014
 FBC-B, ONE OF THREE METHODS. 717.6.2.1 CEILING
 RADIATION DAMPERS. THE SAME ISSUE OCCURS ON THE 2ND
 FLOOR WITH RATED CEILING.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-07 Cont ID  
Sent By medwards Date 2021-01-07 Time 09:59 Rev Time 0.00
Received By medwards Date 2021-01-05 Time 14:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-01-04 Time 14:01 Rev Time 0.00
Received By ccarvaja Date 2020-12-14 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-04 Cont ID  
Sent By medwards Date 2020-11-04 Time 13:19 Rev Time 0.00
Received By medwards Date 2020-11-03 Time 08:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-09-14 Time 17:04 Rev Time 0.00
Received By lmarchan Date 2020-08-27 Time 08:30 Sent To  
Notes
2020-09-14 17:09:462014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 20081239
 W. P. B. PERMIT: 17041276
 ADD: 1626 OKEECHOBEE RD.
 CONT: SPECTRUM RENOVATIONS LLC
 TEL: 561-291-8350
 E-MAIL:
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. SEPT. 14TH/ 2020
 ACTION: DENIED
  
 1) NOTE BUILDING PLAN REVIEW ASKED THIS QUESTION IN THE
 2ND OF 4 REVIEWS. 6B) 420.3 HORIZONTAL SEPARATION.
 FLOOR ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS
 IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH
 SECTION 711.
  
 THE ISSUED SET OF PLANS SHEET CUT SECTION ON SHEET 19
 OF 31 SHOWS T 5/8 INCH TYPE X FIRE DRYWALL ATTACHED TO
 THE BOTTOM CHORD OF THE FLOOR ASSEMBLY MAKING A PORTION
 OF THE RATED HORIZONTAL ASSEMBLY. ISSUES SET OF PLANS
 SHEET A-14.0 SHOWS DROPPED SOFFITS FROM THE 9-FOOT-HIGH
 RATED CEILINGS.
  
 THE PROPOSED REVISION DOES NOT SHOW THE DROPPED SOFFIT
 AND PENETRATING THE RATED FLOOR ASSEMBLY. FOR THIS TYPE
 OF CONSTRUCTION TO PASS COMPLIANCE WOULD REQUIRE
 COMPLIANCE WITH 717.6.2 MEMBRANE PENETRATIONS 2014
 FBC-B, ONE OF THREE METHODS. 717.6.2.1 CEILING
 RADIATION DAMPERS. THE SAME ISSUE OCCURS ON THE 2ND
 FLOOR WITH RATED CEILING.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-01-07 Cont ID  
Sent By medwards Date 2021-01-07 Time 09:36 Rev Time 0.00
Received By medwards Date 2021-01-07 Time 07:57 Sent To  
Notes
2021-01-07 09:36:48 
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-12-22 Cont ID  
Sent By medwards Date 2020-12-22 Time 07:15 Rev Time 0.00
Received By medwards Date 2020-12-22 Time 07:15 Sent To  
Notes
2020-12-22 07:15:323RD REVIEW FBC-2017 MECHANICAL
 PERMIT- 20081239
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DRAWINGS SUBMITTED UNDER THE FILE 1626
 OKEECHOBEE ? 11-6 APPEAR TO BE A FUZZY COPY OF AN
 ORIGINAL DIGITALLY SIGNED AND SEALED DRAWING. I CAN?T
 SEE THE WORDING CLEARLY ON THIS DRAWING, PLEASE SUBMIT
 THE ORIGINAL DIGITALLY SIGNED DRAWINGS SO I CAN READ
 IT. FBC 107.2
  
 2) FROM THE DRAWINGS SUBMITTED IT APPEARS THERE ARE NO
 FIRE DAMPERS ABOVE THE AHU?S WHERE THE DUCT PENETRATES
 THE FLOOR/CEILING ASSEMBLY. PLEASE EXPLAIN WHY THERE
 ARE NO FIRE DAMPERS IN THIS LOCATION. FBC M 607
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-11-04 Cont ID  
Sent By medwards Date 2020-11-04 Time 13:13 Rev Time 0.00
Received By medwards Date 2020-11-04 Time 12:05 Sent To  
Notes
2020-11-04 13:12:01PLEASE SEE MY COMMENTS FOR THE ORIGINAL REVIEW FOR THIS
 REVISION BELOW:
  
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081239
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ACCORDING TO THE ORIGINALLY APPROVED PLANS
 (17041276) THERE ARE 9? CEILINGS THROUGHOUT THE FIRST
 FLOOR WITH DROPPED 8?HIGH CEILINGS IN PART OF THE
 BEDROOM AREAS AND A 8? HIGH SOFFIT IN THE KITCHEN AREA
 ON THE 1ST FLOOR ALLOWING THE MECHANICAL DUCTWORK TO BE
 INSTALLED ABOVE THE 8? CEILINGS AND BELOW THE RATED
 FLOOR/CEILING ASSEMBLY. THIS DRAWING INDICATES THAT THE
 8? CEILINGS IN THE BEDROOM AREAS AND THE 8? SOFFIT IN
 THE KITCHEN HAS BEEN ELIMINATED AND THE DUCTWORK HAS
 BEEN INSTALLED INSIDE THE RATED ASSEMBLY WITHOUT ANY
 PENETRATION PROTECTION I.E. RATED DAMPERS. THIS IS NOT
 ALLOWED AND YOU MUST PROTECT THIS RATED ASSEMBLY AT ALL
 PENETRATIONS. FBC M 607.6.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-02 Cont ID  
Sent By medwards Date 2020-09-02 Time 08:37 Rev Time 0.00
Received By medwards Date 2020-09-01 Time 06:57 Sent To  
Notes
2020-09-02 08:37:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081239
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ACCORDING TO THE ORIGINALLY APPROVED PLANS
 (17041276) THERE ARE 9? CEILINGS THROUGHOUT THE FIRST
 FLOOR WITH DROPPED 8?HIGH CEILINGS IN PART OF THE
 BEDROOM AREAS AND A 8? HIGH SOFFIT IN THE KITCHEN AREA
 ON THE 1ST FLOOR ALLOWING THE MECHANICAL DUCTWORK TO BE
 INSTALLED ABOVE THE 8? CEILINGS AND BELOW THE RATED
 FLOOR/CEILING ASSEMBLY. THIS DRAWING INDICATES THAT THE
 8? CEILINGS IN THE BEDROOM AREAS AND THE 8? SOFFIT IN
 THE KITCHEN HAS BEEN ELIMINATED AND THE DUCTWORK HAS
 BEEN INSTALLED INSIDE THE RATED ASSEMBLY WITHOUT ANY
 PENETRATION PROTECTION I.E. RATED DAMPERS. THIS IS NOT
 ALLOWED AND YOU MUST PROTECT THIS RATED ASSEMBLY AT ALL
 PENETRATIONS. FBC M 607.6.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 15:21 Rev Time 0.00
Received By jwitmer Date 2021-01-05 Time 15:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-12-22 Cont ID  
Sent By medwards Date 2020-12-22 Time 07:15 Rev Time 0.00
Received By medwards Date 2020-12-22 Time 07:15 Sent To  
Notes
2020-12-22 07:17:28PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 OPTION
 YOU MAY ELECT TO PROVIDE A HARD COPY OF PLANS WITH
 VALID SIGNATURE OF CONTRACTOR OR DESIGNER PRIOR TO
 PERMIT. A DROP BOX HAS BEEN INSTALLED OUTSIDE CITY HALL
 FOR THIS PURPOSE. CONTACT THE OFFICE OF DEVELOPMENT
 SERVICES @ 561-805-8700 OR [email protected] TO STATE YOUR
 INTENTIONS. CITY STAFF WILL REVIEW YOUR DOCUMENTS AND
 IF APPROVED YOU WILL RECIEVE AN E-MAIL INSTRUCTING YOU
 TO DOWNLOAD AND PRINT YOUR PERMIT AND PLANS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-11-04 Cont ID  
Sent By medwards Date 2020-11-04 Time 13:15 Rev Time 0.00
Received By medwards Date 2020-11-04 Time 13:15 Sent To  
Notes
2020-11-04 13:17:25SHEET A-14 STILL NEEDS TO BE DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-02 Cont ID  
Sent By medwards Date 2020-09-02 Time 08:39 Rev Time 0.00
Received By medwards Date 2020-09-02 Time 08:38 Sent To  
Notes
2020-09-02 08:40:06PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  