Plan Review Details - Permit 20081205
Plan Review Stops For Permit 20081205
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By jwitmer Date 2020-10-13 Time 14:05 Rev Time 0.00
Received By jwitmer Date 2020-10-13 Time 14:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-09-10 Cont ID  
Sent By jwitmer Date 2020-09-10 Time 16:43 Rev Time 0.00
Received By jwitmer Date 2020-09-10 Time 15:31 Sent To  
Notes
2020-09-10 16:37:26COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By jwitmer Date 2020-10-13 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2020-10-13 Time 14:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-10 Cont ID  
Sent By jwitmer Date 2020-09-10 Time 16:43 Rev Time 0.00
Received By jwitmer Date 2020-09-10 Time 15:31 Sent To  
Notes
2020-09-10 16:36:59WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20081205
 ADD: 1641 WORTHINGTON RD. SUITE # 410
 CONT: ANDERSON-MOORE CONSTRUCTION CO.
 TEL: 561-348-4805
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 10TH/2020
 ACTION: DENIED
  
 1) SHEETS ALS1.1 & A1.1.1 BOTH ARE MISSING THE DOOR TO
 THE 1 HOUR RATED CORRIDOR MISSING DOOR AND SWING. SHEET
 A1.1.1 DOES IDENTIFY THE MISSING DOOR AS DOOR # 121.
 SHEET A2.0 THE DOOR SCHEDULE DOES INDICATE THE DOOR TO
 BE A 45-MINUTE FIRE RATED DOOR. PLEASE SHOW COMPLIANCE
 WITH THE 2017 FBC-B SECTION 1010.1.2.1 DIRECTION OF
 SWING. PIVOT OR SIDE HINGED SWINGING DOORS SHALL SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM
 OR AREA CONTAINING AN OCCUPANT LOAD OF 50 OR MORE.
  
 2A) SHEET A-4.03 DETAIL # 1 THE BASE ACCESSIBLE CABINET
 FOR BREAK ROOM SINK. THE DETAIL IS MISSING THE
 ACCESSIBLE REQUIREMENTS FOR KNEE AND TOE CLEARANCES.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY
 CODE:
 306.2 TOE CLEARANCES
 306.3 KNEE CLEARANCES.
  
 2B) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY &
 DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-23 Cont ID  
Sent By fgiaquin Date 2020-09-23 Time 22:40 Rev Time 0.00
Received By fgiaquin Date 2020-09-23 Time 20:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-10-09 Cont ID  
Sent By pleduc Date 2020-10-09 Time   Rev Time 0.00
Received By pleduc Date 2020-10-09 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-02 Cont ID  
Sent By pleduc Date 2020-09-02 Time   Rev Time 0.00
Received By pleduc Date 2020-09-02 Time 12:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-16 Cont ID  
Sent By medwards Date 2020-10-16 Time 11:24 Rev Time 0.00
Received By medwards Date 2020-10-07 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-23 Cont ID  
Sent By fgiaquin Date 2020-09-23 Time 22:40 Rev Time 0.00
Received By fgiaquin Date 2020-08-27 Time 08:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-10-16 Cont ID  
Sent By medwards Date 2020-10-16 Time 11:22 Rev Time 0.00
Received By medwards Date 2020-10-16 Time 10:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By medwards Date 2020-09-21 Time 11:25 Rev Time 0.00
Received By medwards Date 2020-09-21 Time 10:15 Sent To  
Notes
2020-09-21 11:25:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081205
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1 INDICATES ?P.M.? THROUGHOUT THIS AREA.
 PLEASE CLARIFY WHAT A P.M. IS AND PROVIDE
 SPECIFICATIONS FOR THEM. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-10-08 Cont ID  
Sent By lcrespo Date 2020-10-08 Time 16:55 Rev Time 0.00
Received By lcrespo Date 2020-10-08 Time 16:55 Sent To  
Notes
2020-10-08 16:56:0510/05/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-15 Cont ID  
Sent By jesmith Date 2020-09-15 Time 13:26 Rev Time 0.00
Received By jesmith Date 2020-09-15 Time 12:36 Sent To  
Notes
2020-09-15 13:26:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. DOMESTIC WATER RISER DIAGRAM ON P0.1 SHOWS ? INCH
 COLD WATER ROUTED OVERHEAD TO ICEMAKER. P3.1 PLAN VIEW
 SHOWS IT GOING TO A BEVERAGE DISPENSER. PER WPB FBC
 107.2.1, CLARIFY.
  
 2. DOMESTIC WATER RISER DIAGRAM ON P0.1 SHOWS ? INCH
 COLD WATER TO RO SYSTEM BUT NO PROVISION IS MADE IN THE
 SANITARY FOR WASTE DISPOSAL. PROVIDE A TRAPPED AND
 VENTED DEDICATED WASTE RECEPTOR TO RECEIVE THE
 DISCHARGE OF THE RO SYSTEM. PROVIDE AN INDIRECT WASTE
 WITH AN AIR GAP. COMPLY WITH FBC PL 802.2, 802.2.1 AND
 802.3.
  
 3. SANITARY RISER DIAGRAM ON P0.1 SHOWS A 2 INCH WASTE
 AND VENT FOR SK-1 FIXTURE. P2.1 PLAN VIEW SHOWS A FLOOR
 DRAIN CONNECTED TO SANITARY AS WELL AS SK-1. PER WPB
 FBC 107.2.1, CLARIFY AND ADVISE AS TO THE PURPOSE OF
 THE FLOOR DRAIN. PLEASE NOTE:
 A. PER FBC PL 412.2, FLOOR DRAINS SHALL HAVE REMOVABLE
 STRAINERS. THE FLOOR DRAIN SHALL BE CONSTRUCTED SO THAT
 THE DRAIN IS CAPABLE OF BEING CLEANED. ACCESS SHALL BE
 PROVIDED TO THE DRAIN INLET. READY ACCESS SHALL BE
 PROVIDED TO FLOOR DRAINS.
 B. PER FBC PL 802.3, FOR OTHER THAN HUB DRAINS THAT
 RECEIVE ONLY CLEAR-WATER WASTE AND STANDPIPES, A
 REMOVABLE STRAINER OR BASKET SHALL COVER THE OUTLET OF
 WASTE RECEPTORS. WASTE RECEPTORS SHALL NOT BE INSTALLED
 IN CONCEALED SPACES. WASTE RECEPTORS SHALL NOT BE
 INSTALLED IN PLENUMS, CRAWL SPACES, ATTICS,
 INTERSTITIAL SPACES ABOVE CEILINGS AND BELOW FLOORS.
 READY ACCESS SHALL BE PROVIDED TO WASTE RECEPTORS
 C. PER FBC PL 802.2.1, AN AIR GAP BETWEEN THE INDIRECT
 WASTE PIPE AND THE FLOOD LEVEL RIM OF THE WASTE
 RECEPTOR SHALL BE NOT LESS THAN TWICE THE EFFECTIVE
 OPENING OF THE INDIRECT WASTE PIPE.
  
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE INSINKERATOR
 FAUCET AND THE RO SYSTEM.
 5. PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTOR
 CONFORMING TO ASSE 1010 AT THE DISHWASHER AND ICE MAKER
 LINES.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20081205 1641 WORTHINGTON RD # 410
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-16 Cont ID  
Sent By medwards Date 2020-10-16 Time 11:24 Rev Time 0.00
Received By medwards Date 2020-10-16 Time 11:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-21 Cont ID  
Sent By medwards Date 2020-09-21 Time 11:42 Rev Time 0.00
Received By medwards Date 2020-09-21 Time 11:41 Sent To  
Notes
***NONE***