Plan Review Details - Permit 20081107
Plan Review Stops For Permit 20081107
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-28 Cont ID  
Sent By rmcdouga Date 2020-09-28 Time 07:19 Rev Time 0.00
Received By rmcdouga Date 2020-09-28 Time 07:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-11 Cont ID  
Sent By cthroop Date 2020-09-11 Time 16:10 Rev Time 0.00
Received By cthroop Date 2020-09-11 Time 15:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By ccole Date 2020-09-17 Time 09:35 Rev Time 0.00
Received By ccole Date 2020-09-16 Time 16:23 Sent To  
Notes
2020-09-17 09:35:551ST REVIEW FBC-2017 RES.
 PERMIT- 20081107
 9/17/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $18,500 TOTAL VALUE ON THE APPLICATION AND ON
 THE CONTRACT DOES NOT APPEAR TO INCLUDE THE $4500.00
 COST OF THE GAS PIPING INSTALLATION AS SHOWN ON THE
 SUB-PERMIT APPLICATION. THE TOTAL VALUE MAY HAVE TO
 INCREASE TO $23,000.00- SECTION 109.3 WPB.
  
 2) THE LP TANK TIE DOWN DETAIL DESIGNED BY ATCHLEY P.E
 HAS AN OUTDATED STANDARD SEAL AND SIGNATURE, AND ALSO
 APPEARS TO BEAR A COPIED ELECTRONIC SEAL. THIS DOCUMENT
 AND DETAILS SHALL BEAR AN ORIGINAL ELECTRONIC SEAL AND
 SIGNATURE TO BE VALID FOR PERMITTING- FL. STATUTES
 471.02=03, 471.025, AND FAC 61G15-23.005. IN LIEU OF
 UPLOADING A VERIFIABLE ELECTRONICALLY SIGNED AND SEALED
 DETAIL, AN ORIGINAL PAPER COPY MAY BE PHYSICALLY
 DELIVERED TO THE WPB BUILDING DEPARTMENT. PLEASE
 CONTACT ME IF YOU HAVE QUESTIONS ABOUT THE SUBMITTAL.
  
 3) CATHODIC PROTECTION SYSTEM- SECTIONS 5.2.1.11 &
 6.6.6.1(I) NFPA 58. SHOW ON THE RISER DRAWING THE TYPE
 OF CATHODIC PROTECTION TO BE PROVIDED. IF USING A
 CLOTH-BAGGED ANODE, INDICATE THE SIZE OF THE ANODE AND
 SHOW WHERE IT WILL BE LOCATED. SPECS FOR THE ANODE CAN
 BE SUBMITTED WITH CORRECTED PLANS OR BE ONSITE FOR
 INSPECTION.
  
 3) GAS RISER:
 A) ACCORDING TO THE SUBMITTED SPECS THE GENERATOR HAS A
 340,000 BTUH LOAD- (136 X 2500= 340,000) AND A 7-11
 IN.WC. INPUT PRESSURE RATING. PLEASE CORRECT THE RISER.
  
 B) INDICATE THE PE AND SCHEDULE 40 METALLIC PIPE SIZING
 TABLES ON THE DRAWING- SEE TABLES G2413.4(1)-
 G2413.4(8) FBC RES. SHOW THE THE SIZE OF THE METALLIC
 PIPE.
  
 C) INDICATE THE MAKE AND MODEL OF THE REGULATOR ON THE
 DRAWING AND SUBMIT MANUFACTURER'S SPECIFICATIONS MARKED
 UP TO SHOW THE INLET AND OUTLET SIZES AND PRESSURES,
 AND ORIFICE SIZES- SECTION G2421.1 & G2421.2 FBC RES.
 SHOW THE LOCATIONS OF THE REQUIRED PIPE UNIONS WITHIN 1
 FT. ON EACH SIDE OF THE REGULATORS- SECTION G2421.2
 (7).
  
 D) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
  
 E) INDICATE THE BURIAL DEPTH OF THE PE PIPING- SECTION
 G2415.12 AND SHOW A TRACER WIRE WILL BE INSTALLED
 ADJACENT TO THE PIPE- SECTION G2415.17.3.
  
 F) SHOW HOW THE PE PIPING RISER WILL CONNECT TO THE
 METALLIC PIPE PER SECTIONS G2415.17.1 & G2415.17.2.
 PLEASE NOTE THAT SPECS FOR ANODELESS RISERS AND
 PE/METALLIC PIPE CONNECTORS SHALL BE LISTED AND
 LABELED.
  
 4) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM
 OF 5 FT. FROM COMBUSTIBLE WALLS. THE 18 IN. CLEARANCE
 DISTANCE SHALL BE PERMITTED IF THE HOUSE WALL HAS A
 1-HR. FIRE RESISTANCE RATING, OR THE GENERATOR HAS A
 WEATHERPROOF ENCLOSURE CONSTRUCTED OF NON-COMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE OF THE ENCLOSURE- SECTION 4.1.4 NFPA
 37. PLEASE SUBMIT THE GENERATOR INSTALLATION GUIDELINES
 FROM THE MANUFACTURER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-28 Cont ID  
Sent By rmcdouga Date 2020-09-28 Time 07:21 Rev Time 0.00
Received By rmcdouga Date 2020-09-09 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-17 Cont ID  
Sent By ccole Date 2020-09-17 Time 09:39 Rev Time 0.00
Received By ccole Date 2020-09-16 Time 16:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-28 Cont ID  
Sent By rmcdouga Date 2020-09-28 Time 07:19 Rev Time 0.00
Received By rmcdouga Date 2020-09-28 Time 07:19 Sent To  
Notes
2020-09-28 07:21:07THE GENERATOR PAD ENGINEERING IS NOT DIGITALLY SIGNED.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  
2020-09-11 16:11:36VERIFIED CONTRACTORS SIGNATURE ON LOAD CALC'S AND
 ELECTRIC RISER. CT

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-21 Cont ID  
Sent By kalexand Date 2020-09-21 Time 10:29 Rev Time 0.00
Received By kalexand Date 2020-09-21 Time 10:29 Sent To I
Notes
***NONE***