Plan Review Details - Permit 20081060
Plan Review Stops For Permit 20081060
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By rmcdouga Date 2020-10-02 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2020-10-02 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-25 Cont ID  
Sent By rmcdouga Date 2020-09-25 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2020-09-25 Time 15:57 Sent To  
Notes
2020-09-25 16:10:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN A COUPLE OF PLACES ON SHEET S-1, THE ENGINEER
 SPECIFIES THAT THE DESIGN IS BASED ON ASCE 7 -16.
 CHAPTER 35 OF THE 2017 FBC REFERENCES ASCE 7-10. THE
 BUILDING CODE HAS NOT YET ADOPTED ASCE 7-16. PLEASE
 REVISE.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-25 Cont ID  
Sent By jleahy Date 2020-09-25 Time 16:11 Rev Time 0.00
Received By jleahy Date 2020-09-25 Time 15:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-25 Cont ID  
Sent By pleduc Date 2020-09-25 Time   Rev Time 0.00
Received By pleduc Date 2020-09-25 Time 15:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-02 Cont ID  
Sent By rmcdouga Date 2020-10-02 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2020-10-01 Time 16:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-01 Cont ID  
Sent By shill Date 2020-10-01 Time 16:28 Rev Time 0.00
Received By shill Date 2020-09-25 Time 10:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By rmcdouga Date 2020-10-02 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2020-10-02 Time 10:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-25 Cont ID  
Sent By rmcdouga Date 2020-09-25 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2020-09-25 Time 15:59 Sent To  
Notes
2020-09-25 16:01:00I WAS NOT ABLE TO VERIFY THAT THE DRAWINGS ARE
 DIGITALLY SIGNED BY THE ENGINEER. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-01 Cont ID  
Sent By eleveque Date 2020-10-01 Time 16:08 Rev Time 0.00
Received By elevesqu Date 2020-10-01 Time 16:08 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved