Plan Review Details - Permit 20081055
Plan Review Stops For Permit 20081055
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-11-05 Cont ID  
Sent By jgomez Date 2020-11-05 Time 13:33 Rev Time 0.00
Received By jgomez Date 2020-11-05 Time 13:33 Sent To  
Notes
2020-11-05 13:34:22CONTRACTOR SIGNED THE AKNOWLEDGEMENT LETTER. CAMERON H
 FOCKLER

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-11-03 Cont ID  
Sent By jgomez Date 2020-11-03 Time 13:36 Rev Time 0.00
Received By jgomez Date 2020-11-03 Time 13:36 Sent To  
Notes
2020-11-03 13:38:53THE ACKNOWLEDGMENT LETTER NEEDS TO BE ON THE
 CONTRACTOR'S LETTERHEAD NOT ON THE ARCHITECT'S
 LETTERHEAD. REVISE AS REQUIRED. SEE BELOW.
  
  
 ASBESTOS REVIEW
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 NOTE:
 THE CONTRACTOR ACKNOWLEDGMENT TO BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ASBESTOS IN THE
 SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jgomez Date 2020-09-23 Time 17:24 Rev Time 0.00
Received By jgomez Date 2020-09-23 Time 17:24 Sent To  
Notes
2020-09-23 17:24:37ASBESTOS REVIEW
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 NOTE:
 THE CONTRACTOR ACKNOWLEDGEMENT TO BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ASBESTOS IN THE
 SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-05 Cont ID  
Sent By jgomez Date 2020-11-05 Time 14:33 Rev Time 0.00
Received By jgomez Date 2020-11-05 Time 13:34 Sent To  
Notes
2020-11-05 14:09:37BUILDING REVIEW APPROVED WITH PROVISO:
 (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSPECTIONS):
 1- REVISE ENERGY CALCULATIONS: WINDOWS AND DOORS
 INFORMATION DON'T MATCH PLANS. SEE PLANS AND REVISE AS
 REQUIRED.
 2- REVISE THE CODE DATA INFORMATION SHOWN ON THE
 INDEX-COVER PAGE:
 A)THERE IS NOT OCCUPANCY CLASSIFICATION 5B.
 B)PROPOSED FLOOR PLAN SHOWS WAREHOUSE/OFFICE. REVISE
 CODE DATA OCCUPANCY CLASSIFICATION TO STORAGE AND
 BUSINESS (MIXED USE. AND CLEARLY SPECIFY IF STORAGE S-1
 OR S-2.)
 C) CHANGE OF USE. A NEW CERTIFICATE OF OCCUPANCY WILL
 BE REQUIRED AS REQUIRED BY SEC. 1001.3 FBC-EXISTING
 BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-03 Cont ID  
Sent By jgomez Date 2020-11-03 Time 14:24 Rev Time 0.00
Received By jgomez Date 2020-11-03 Time 10:27 Sent To  
Notes
2020-11-03 14:25:26SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR
 OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH
 THE CODE, AS PER SECTION 553.907, FLORIDA STATUTES,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 ENERGY FORM SUBMITTED DOESN'T HAVE ANY BODY SIGNING
 UNDER THE OWNER OR AGENT LINE.
  
 B) PARTIALLY COMPLIED. ARCHITECT SUBMITTED LETTER
 STATING COMPLIANCE. SEC. C103.1.1.2 FBC-ENERGY
 CONSERVATION REQUIRES CERTIFICATION ON THE ENERGY CODE
 FORM. SEE SEC. C103.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) WINDOWS AND DOORS INFORMATION DON'T MATCH PLANS.
 THERE ARE WINDOWS ON THREE SIDES OF THE BUILDING NOT
 JUST ON THE NORTH SIDE. THERE ARE MORE DOORS ON THE
 SOUTH SIDE. HOW ARE THE WINDOWS SHADED? SEE PLANS,
 ELEVATIONS AND REVISE AS REQUIRED. SEC. C103.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 2- REVISE THE CODE DATA INFORMATION SHOWN ON THE
 INDEX-COVER PAGE:
 A THE OCCUPANCY CLASSIFICATION IS NOT R2, UNIT 711.
 SEC. 302.1 FBC-BUILDING.
  
 RESPONSE:
 OCCUPANCY CLASSIFICATION WAS CHANGED TO 5B. WHAT IS
 OCCUPANCY CLASSIFICATION 5B?. INFORMATION IS NOT CLEAR.
 5B IS A CONSTRUCTION TYPE NOT OCCUPANCY TYPE. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 B)THIS IS NOT A LEVEL 2 ALTERATION. SEE ITEM #3 BELOW
 AND REVISE AS REQUIRED. SEC. 506 FBC-EXISTING BUILDING.
 SEC. 505 FBC-EXISTING BUILDING.
  
 RESPONSE:
 NOT ADDRESSED.
 NOTE:
 NEED TO COORDINATE THE CODE DATA WITH ITEM #3. NEED TO
 CLARIFY IF THIS IS BUSINESS OCCUPANCY OR MIXED
 OCCUPANCY: WAREHOUSE AND OFFICE AS SHOWN ON REVISED
 SHEET A1.0.
 CLARIFICATION IS REQUIRED FOR PROPER PLAN REVIEW.
  
 3- SHEET A1.0:
 ACCORDING TO CITY RECORDS AND PBC PROPERTY APPRAISER
 THE EXISTING BUILDING IS A WAREHOUSE. THE PROPOSED
 FLOOR PLAN SHOWS AN STUDIO AS THE PROPOSED USE. THIS IS
 A CHANGE OF OCCUPANCY (SEC. 506 FBC-EXISTING BUILDING)
 AND ALTERATION LEVEL 3 (SEC. 505 FBC-EXISTING
 BUILDING). PLAN SHOWS AN OPEN STUDIO AND NEW ADA
 RESTROOM. PLAN DOESN'T SHOW IF THE ACCESS TO THE NEW
 STUDIO IS ACCESSIBLE. IT ONLY SHOWS EXISTING ENTRY
 DOOR. PLEASE SHOW HOW THE STUDIO IS ACCESSIBLE FROM THE
 STREET. SEC. 206.2.1 FBC-ACCESSIBILITY.
  
 RESPONSE:
 INFORMATION ON THE PROPOSED FLOOR PLAN AND THE CODE
 DATA ON THE INDEX-COVER PAGE IS NOT CLEAR. IS THIS A
 BUSINESS USE OR MIXED USE WAREHOUSE AND BUSINESS.
 CLARIFICATION IS REQUIRED FOR PROPER PLAN REVIEW.
 ALSO, CLARIFY IF ENTRY IS ACCESSIBLE. NOTE STATING
 "EXISTING THRESHOLD" DOESN'T CLARIFY IF THE THRESHOLD
 IS ACCESSIBLE OR NOT.
  
 4- OK
  
 5- OK
  
 6- OK
  
 7- OK
  
 8- A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED AS
 REQUIRED BY SEC. 1001.3 FBC-EXISTING BUILDING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By jgomez Date 2020-09-24 Time 17:54 Rev Time 0.00
Received By jgomez Date 2020-09-23 Time 14:56 Sent To  
Notes
2020-09-24 17:57:28BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR
 OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH
 THE CODE, AS PER SECTION 553.907, FLORIDA STATUTES,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SEC. C103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B)ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND LICENSE
 NUMBER) ON ENERGY FORM AS REQUIRED BY SEC. C103.1.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C) WINDOWS AND DOORS INFORMATION DON'T MATCH PLANS.
 THERE ARE WINDOWS ON THREE SIDES OF THE BUILDING NOT
 JUST ON THE NORTH SIDE. THERE ARE MORE DOORS ON THE
 SOUTH SIDE. HOW ARE THE WINDOWS SHADED? SEE PLANS,
 ELEVATIONS AND REVISE AS REQUIRED. SEC. C103.2
 FBC-ENERGY CONSERVATION.
  
 D) ROOFING INFORMATION DOESN'T MATCH PLANS. WHERE IS
 THE CLAY TILE AND PAVERS?. SEC. C103.2 FBC-ENERGY
 CONSERVATION.
  
  
 2- REVISE THE CODE DATA INFORMATION SHOWN ON THE
 INDEX-COVER PAGE:
 A)THE OCCUPANCY CLASSIFICATION IS NOT R2, UNIT 711.
 SEC. 302.1 FBC-BUILDING.
  
 B)THIS IS NOT A LEVEL 2 ALTERATION. SEE ITEM #3 BELOW
 AND REVISE AS REQUIRED. SEC. 506 FBC-EXISTING BUILDING.
 SEC. 505 FBC-EXISTING BUILDING.
  
 3- SHEET A1.0:
 ACCORDING TO CITY RECORDS AND PBC PROPERTY APPRAISER
 THE EXISTING BUILDING IS A WAREHOUSE. THE PROPOSED
 FLOOR PLAN SHOWS AN STUDIO AS THE PROPOSED USE. THIS IS
 A CHANGE OF OCCUPANCY (SEC. 506 FBC-EXISTING BUILDING)
 AND ALTERATION LEVEL 3 (SEC. 505 FBC-EXISTING
 BUILDING). PLAN SHOWS AN OPEN STUDIO AND NEW ADA
 RESTROOM. PLAN DOESN'T SHOW IF THE ACCESS TO THE NEW
 STUDIO IS ACCESSIBLE. IT ONLY SHOWS EXISTING ENTRY
 DOOR. PLEASE SHOW HOW THE STUDIO IS ACCESSIBLE FROM THE
 STREET. SEC. 206.2.1 FBC-ACCESSIBILITY.
  
 4-SHEET A3.0:
 A)WINDOW REPLACEMENT IS NOT CLEAR. ELEVATIONS SHOW
 SINGLE HUNG WINDOWS, BUT NOA SUBMITTED IS FOR FIXED
 WINDOWS. ON THE OTHER HAND THE WINDOW SCHEDULE DOESN'T
 SPECIFY TYPE OF WINDOW. ALSO, NOA LISTED IN THE WINDOW
 SCHEDULE DOESN'T MATCH NOA SUBMITTED. REVISE/CLARIFY AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 B)NOA LISTED ON THE DOOR SCHEDULE DOESN'T MATCH NOA
 SUBMITTED. DOOR SCHEDULE LISTS D2 DOOR, WHILE DOOR
 ELEVATION ON SAME DRAWING LISTS D1. THE DOOR SCHEDULE
 DOESN'T SPECIFY TYPE OF DOOR. REVISE/CLARIFY AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 5-SHEET LS1: LIFE SAFETY PLAN:
 A) CLARIFY HOW THE EXIT CAPACITY WAS DETERMINED.
 SPECIFY THE SIZE OF EXISTING EXIT DOORS. SEC. 1005
 FBC-EXISTING BUILDING.
 ALSO, PLEASE ROUND UP THE NUMBER OF PEOPLE.
  
 B)CLARIFY WHY THE DISTANCE BETWEEN THE TWO EXITS IS
 65'-9" IF THE TOTAL LENGTH OF THE BUILDING IS 70'-6"
 AND THE TWO EXIT DOORS ARE IN STRAIGHT LINE?. SEE SEC.
 1007.1.1.1 FBC-BUILDING TO SEE HOW DISTANCE IS MEASURED
 AND REVISE AS REQUIRED.
  
 6- SHEET S1.1, S1.2 AND S1.3:
 PLEASE PROVIDE COMPLETE WIND DESIGN DATA AS REQUIRED BY
 SEC. 1603.1.4 FBC-BUILDING.
  
 7-GARAGE DOOR NOA 17-1108.30 EXPIRED ON FEB. 22,2020.
 NEED TO PROVIDE CURRENT PRODUCT APPROVAL. FAC
 61G20.3.001
  
 8- A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED AS
 REQUIRED BY SEC. 1001.3 FBC-EXISTING BUILDING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By jleahy Date 2020-09-15 Time 10:45 Rev Time 0.00
Received By jleahy Date 2020-09-15 Time 10:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-04 Cont ID  
Sent By pleduc Date 2020-11-04 Time   Rev Time 0.00
Received By pleduc Date 2020-11-04 Time 15:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-09-03 Cont ID  
Sent By pleduc Date 2020-09-03 Time   Rev Time 0.00
Received By pleduc Date 2020-09-02 Time 16:32 Sent To  
Notes
2020-09-03 11:39:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 3 - THERE ARE NO INDICATIONS OF THE HARDWARE
 FOR THE EXIT DOORS.
  
 LOCKS AND HARDWARE ON EXITS DOORS SHALL COMPLY WITH
 NFPA 101, CH 7 MEANS OF EGRESS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL
 BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF
 OPERATION AND THAT IS READILY OPERATED UNDER ALL
 LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE
 LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR
 OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF
 WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS
 OTHERWISE
 SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR
 7.2.1.5.10.6.
  
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-05 Cont ID  
Sent By jgomez Date 2020-11-05 Time 14:56 Rev Time 0.00
Received By jgomez Date 2020-11-05 Time 13:12 Sent To I
Notes
2020-11-05 13:12:57ARCHITECT EMAILED SIGNED ENERGY CALCULATIONS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-04 Cont ID  
Sent By ccarvaja Date 2020-11-04 Time 17:13 Rev Time 0.00
Received By ccarvaja Date 2020-10-29 Time 16:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-26 Cont ID  
Sent By cpuell Date 2020-10-26 Time 13:10 Rev Time 0.00
Received By cpuell Date 2020-08-24 Time 13:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2020-11-18 Cont ID  
Sent By lmarchan Date 2020-11-18 Time 14:48 Rev Time 0.00
Received By lmarchan Date 2020-11-06 Time 14:56 Sent To  
Notes
2020-11-18 14:48:2811/18/20 NO IMPACT FEES DUE PER COUNTY. LEM
2020-11-06 14:57:3811/06/2020 EMAILED PBC IMPACT FEE OFFICE. IMPACT FEE
 QUESTIONNAIRE IS UPLAODED IN PROJECDOX AND READY TO BE
 REVIEWED. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-11-03 Cont ID  
Sent By jgomez Date 2020-11-03 Time 14:27 Rev Time 0.00
Received By jgomez Date 2020-11-03 Time 14:27 Sent To  
Notes
2020-11-03 14:28:45IMPACT FEES - DIGITAL SUBMITTALS
 ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISER THE
 BUILDING USE IS FOR WAREHOUSE/STORAGE. NEW USE PROPOSED
 WAREHOUSE/OFFICE.
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jgomez Date 2020-09-23 Time 17:46 Rev Time 0.00
Received By jgomez Date 2020-09-23 Time 17:45 Sent To  
Notes
2020-09-23 17:46:14IMPACT FEES - DIGITAL SUBMITTALS
 ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISER THE
 BUILDING USE IS FOR WAREHOUSE/STORAGE. NEW USE
 PROPOSED.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-11-02 Cont ID  
Sent By medwards Date 2020-11-02 Time 15:00 Rev Time 0.00
Received By medwards Date 2020-11-02 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-14 Cont ID  
Sent By medwards Date 2020-09-14 Time 08:39 Rev Time 0.00
Received By medwards Date 2020-09-14 Time 07:02 Sent To  
Notes
2020-09-14 08:53:51THE ENERGY CALCULATIONS SUBMITTED ARE FOR A 1436 SQ.
 FT. RETAIL SPACE. THE PROJECT SUBMITTED SHOWS SEVERAL
 OCCUPANCY USES AND SHOWS THE SQUARE FOOTAGE TO BE 1551.
 PLEASE BE CONSISTANT WITH SHEET LS1.0
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-09-14 08:39:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081055
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CALCULATIONS OF THE HEATING AND
 COOLING LOADS. FBC EC C403.2
  
 2) PLEASE SHOW THE O.A. DUCT WORK TO RETURN AIR DUCT.
 FBC FS 107.2.1
  
 3) PLEASE SHOW RETURN AIR DUCTWORK. FBC FS 107.2.1
  
 4) PLEASE PROVIDE A VENTILATION CALCULATION BASED ON
 THE OCCUPANCIES LISTED ON LS1.0. FBC M 403
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-11-03 Cont ID  
Sent By lcrespo Date 2020-11-03 Time 09:03 Rev Time 0.00
Received By lcrespo Date 2020-11-03 Time 09:02 Sent To  
Notes
2020-11-03 09:03:1411/03/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-03 Cont ID  
Sent By lcrespo Date 2020-09-03 Time 11:59 Rev Time 0.00
Received By lcrespo Date 2020-09-03 Time 07:26 Sent To  
Notes
2020-09-03 12:02:2009/03/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLEASE SUBMIT A SLAB REPAIR DETAIL, SHOW THE WIDTH
 OF THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO
 BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBODIMENT DEPTH
 INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE
 DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE
 REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL
 AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
 3. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE A ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
  
 4. PLEASE IDENTIFY THE USE OF THE SECOND SINK AND ITS
 USE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. WATER HEATER IS NOT IN A LOCATION THAT PROVIDES
 ACCESS FOR OBSERVATION, MAINTENANCE, SERVICING AND
 REPLACEMENT AS THE AC UNIT IS NEXT TO IT BLOCKING IT
 PER THE 2017 FBC SEC. P 501.4 LOCATION.
  
 6. SHEET A1-0;
 A. PLEASE PROVIDE A DETAIL CLEAR FLOOR SPACE FOR LAV
 AND TOILET, WHICH SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE REAR WALL PER 2017 FBC
 ACC. SEC. 604.3.1.
  
 B. PLEASE SHOW THE DISTANCE FROM TOILET FOR THE PAPER
 HOLDER PER THE 2017 FBC ACC SEC. 604.7.
  
 C. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5.
  
 D. ON THE LABORATORY DETAIL FOR THE MIRROR PLEASE AD
 NOTE ON 40" MAX TO THE REFLECTIVE SIDE PER THE 2017 FBC
 ACC SEC. 603.3.
  
 E. THE FIRST WATER CLOSET DETAIL IS NOT NECESSARY THAT
 THE 24" GRAB BAR BE SHOWN AS IT MAY CAUSE CONFUSION FOR
 INSTALLERS IN FIELD INSTEAD PLEASE GIVE THE DIMENSIONS
 FOR TOILET FROM WALL PER THE 2017 FBC ACC SEC. 604.2
 (A) 16"-18".
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-05 Cont ID  
Sent By jgomez Date 2020-11-05 Time 14:55 Rev Time 0.00
Received By jgomez Date 2020-11-05 Time 13:13 Sent To  
Notes
2020-11-05 14:56:31PROVISO:
 ARCHITECT TO UPLOAD ARCHITECTURAL DRAWINGS WITH THE
 DIGITAL SIGNATURE TO THE SIGNATURE FOLDER. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-11-03 Cont ID  
Sent By jgomez Date 2020-11-03 Time 14:29 Rev Time 0.00
Received By jgomez Date 2020-11-03 Time 14:28 Sent To  
Notes
2020-11-03 14:29:21ARCHITECTURAL AND STRUCTURAL DRAWINGS SUBMITTED DON'T
 HAVE A DIGITAL SIGNATURE. PLANS SUBMITTED HAVE A COPY
 OF THE ARCHITECT'S SEAL AND SIGNATURE. PLANS NEED TO
 HAVE ARCHITECT'S ORIGINAL SEAL AND SIGNATURE WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS AS REQUIRED BY
 61G1-16.003 FAC. PLANS WERE SUBMITTED ELECTRONICALLY.
 ARCHITECT TO PROVIDE PLANS WITH DIGITAL SIGNATURE OR
 PROVIDE HARD COPY PLANS WITH THE ORIGINAL SEAL AND
 SIGNATURE.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By medwards Date 2020-09-14 Time 08:57 Rev Time 0.00
Received By jgomez Date 2020-09-14 Time 08:57 Sent To  
Notes
2020-09-23 17:29:10ARCHITECTURAL AND STRUCTURAL DRAWINGS SUBMITTED DON'T
 HAVE A DIGITAL SIGNATURE. PLANS SUBMITTED HAVE A COPY
 OF THE ARCHITECT'S SEAL AND SIGNATURE. PLANS NEED TO
 HAVE ARCHITECT'S ORIGINAL SEAL AND SIGNATURE WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS AS REQUIRED BY
 61G1-16.003 FAC. PLANS WERE SUBMITTED ELECTRONICALLY.
 ARCHITECT TO PROVIDE PLANS WITH DIGITAL SIGNATURE OR
 PROVIDE HARD COPY PLANS WITH THE ORIGINAL SEAL AND
 SIGNATURE.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-22 Cont ID  
Sent By kalexand Date 2020-10-22 Time 11:06 Rev Time 0.00
Received By kalexand Date 2020-10-22 Time 11:06 Sent To I
Notes
***NONE***