Plan Review Details - Permit 20081014
Plan Review Stops For Permit 20081014
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By shill Date 2020-09-21 Time 07:00 Rev Time 0.00
Received By shill Date 2020-09-21 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 13:06 Rev Time 0.00
Received By shill Date 2020-09-12 Time 13:03 Sent To  
Notes
2020-09-12 13:10:29****CORRECTIONS****
 REVISED 9/20/20
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. INDICATE PROPOSED ELEVATION OF THE GENERATOR AS THIS
 IS LOCATED IN A SPECIAL FLOOD HAZARD AREA. IT APPEARS
 THE MINIMUM DFE IS 9'.
  
 2. IT DOES NOT APPEAR THAT THE "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE WAS SUBMITTED AS
 REQUIRED. SUBMIT AS A "SUBMITTAL"; EMAIL A PLAN REVIEW
 REQUEST FORM TO [email protected]. YOU WILL BE
 GIVEN A LINK TO UPLOAD THE ELEVATION CERTIFICATE AS
 WELL AS A SUBMITTAL NUMBER. (THIS COMMENT IS FOR THE
 HOUSE UNDER CONSTRUCTION)
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-29 Cont ID  
Sent By cthroop Date 2020-08-29 Time 10:06 Rev Time 0.00
Received By cthroop Date 2020-08-29 Time 09:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-11-04 Cont ID  
Sent By abelisle Date 2020-11-04 Time 16:27 Rev Time 0.00
Received By abelisle Date 2020-11-04 Time 10:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-05 Cont ID  
Sent By medwards Date 2020-10-05 Time 10:14 Rev Time 0.00
Received By medwards Date 2020-10-05 Time 09:54 Sent To  
Notes
2020-10-05 10:17:02PLEASE SEE ORIGINAL REVIEWERS NOTE 7. PLEASE PROVIDE
 WHICH GAS TABLE WAS USED TO DESIGN THIS GAS SYSTEM. FBC
 FG 402.4
 HOW ARE YOU SECURING THIS GENERATOR? FBC RES M1307.2
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-01 Cont ID  
Sent By abelisle Date 2020-09-01 Time 14:28 Rev Time 0.00
Received By abelisle Date 2020-09-01 Time 14:09 Sent To  
Notes
2020-09-01 14:28:071ST REVIEW FBC-2017 PLUMBING
 PERMIT-20081014
 9/1/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.4.1.
  
 6.. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 OR 2017
 FBC FUEL GAS RES. SEC. G2413.2.
  
 7.. SUBMIT A COPY OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL
 GAS RES. SEC. G2413.3
  
 8. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
  
 9. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. 2017 FBC FUEL GAS SEC. 401.4, 401.8,
 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS SECS.G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-23 Cont ID  
Sent By lmarchan Date 2020-10-23 Time 16:54 Rev Time 0.00
Received By lmarchan Date 2020-10-08 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-05 Cont ID  
Sent By medwards Date 2020-10-05 Time 10:23 Rev Time 0.00
Received By medwards Date 2020-09-25 Time 14:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 13:11 Rev Time 0.00
Received By shill Date 2020-08-24 Time 13:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-10-23 Cont ID  
Sent By abelisle Date 2020-10-23 Time 16:11 Rev Time 0.00
Received By abelisle Date 2020-10-23 Time 16:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-05 Cont ID  
Sent By medwards Date 2020-10-05 Time 10:17 Rev Time 0.00
Received By medwards Date 2020-10-05 Time 10:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-01 Cont ID  
Sent By abelisle Date 2020-09-01 Time 14:19 Rev Time 0.00
Received By abelisle Date 2020-09-01 Time 14:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-12-07 Cont ID  
Sent By medwards Date 2020-10-05 Time 10:22 Rev Time 0.00
Received By medwards Date 2020-10-05 Time 10:22 Sent To  
Notes
2020-10-05 10:22:44 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 13:10 Rev Time 0.00
Received By shill Date 2020-09-12 Time 13:10 Sent To  
Notes
2020-09-12 13:11:12NO ENGINEERING SUBMITTED, BUT MAY BE REQUIRED IF A
 PREFAB CONCRETE PAD IS USED.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-01 Cont ID  
Sent By kalexand Date 2020-09-01 Time 22:57 Rev Time 0.00
Received By kalexand Date 2020-09-01 Time 22:57 Sent To I
Notes
***NONE***