| 2020-08-31 14:41:16 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20081013 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE INDICATE IF THIS IS A NEW SERVICE OR EXISTING |
| | SERVICE SUPPLYING OTHER GAS APPLIANCES. FBC FS 107.2.1 |
| | |
| | 2) GAS RISER DIAGRAM SPECS 10? OF PE PIPING FOR THE NEW |
| | GENERATOR. THE OVERHEAD SURVEY MAP INDICATES THE GAS |
| | METER WILL BE ON THE OTHER SIDE OF THE HOUSE FROM WHERE |
| | THE NEW GENERATOR WILL BE LOCATED. PLEASE CORRECT THIS |
| | AND SHOW BOTH DRAWINGS TO BE CONSISTENT. FBC FS 107.2.1 |
| | |
| | 3) PLEASE PROVIDE THE GENERATOR SPECS. FBC FS 107.2.1 |
| | |
| | 4) PLEASE PROVIDE SPEC SHEET FOR THE GENERATOR PAD. FBC |
| | FS 107.2.1 |
| | |
| | 5) PROVIDE THE REGULATOR SPECS. PLEASE MARK WHICH |
| | REGULATOR AND SPRING USED FOR THIS INSTALLATION. FBC FS |
| | 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |