Plan Review Details - Permit 20080995
Plan Review Stops For Permit 20080995
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-10-08 Cont ID  
Sent By jwitmer Date 2020-10-08 Time 12:44 Rev Time 0.00
Received By jwitmer Date 2020-10-08 Time 12:43 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-10-04 Cont ID  
Sent By jwitmer Date 2020-10-04 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2020-10-04 Time 13:43 Sent To  
Notes
2020-10-04 14:28:47COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-09-15 Cont ID  
Sent By jwitmer Date 2020-09-15 Time 18:45 Rev Time 0.00
Received By jwitmer Date 2020-09-15 Time 13:07 Sent To  
Notes
2020-09-15 18:42:41COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:44
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-18 Cont ID  
Sent By jwitmer Date 2020-10-18 Time 13:28 Rev Time 0.00
Received By jwitmer Date 2020-10-18 Time 12:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2020-10-04 Time   Rev Time 0.00
Received By jwitmer Date 2020-10-04 Time 13:44 Sent To  
Notes
2020-10-04 14:25:05WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW/ UNIVERSITY PREPARATORY
 ACADEMY
 W. P. B. PERMIT: 20080995
 ADD: 2101 AUSTRALIAN AVE.
 CONT: P & T CONSTRUCTION
 TEL: 561-324-8050
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SUN. OCT. 04TH/ 2020
 ACTION: DENIED
  
 1) SHEET A-1:
 1A) THE RESPONSE SHEET INDICATES THE INTERIOR
 DEMOLITION SHEET WILL BE INCLUDED IN THE SET OF PLANS
 AS INDICATED BY THE PLAN INDEX. NOT IN THE 2ND REVIEW
 CYCLE.
 1ST ROUND COMMENTS. THE INDEX OF DRAWINGS INDICATES
 THERE IS A DEMO SHEET WHICH IS NOT IN THIS SET OF
 PLANS. PART OF THE PLAN REVIEW EXERCISE IS TO SEE WHAT
 IS EXISTING AND WHAT IS TO BE DEMOLISHED. 107.2.1.2
 ADDITIONAL INFORMATION REQUIRED. THERE IS A DISCREPANCY
 IN THE SUBMITTED PLAN SET AND INDEX.
  
 1B) 2ND ROUND OF COMMENTS, NOT ADDRESSED. THERE IS NO
 EXISTING BUILDING CODE FOR STATE LICENSED FACILITIES
 (CHARTER SCHOOLS, PRIVATE SCHOOLS), SEE CHAPTER 4,
 SPECIAL OCCUPANCIES, OF THE FLORIDA BUILDING CODE,
 BUILDING.
 SECTION 468.1 IS FOR FLORIDA?S PUBLIC AND PRIVATE
 SCHOOLS, COLLEGES AND UNIVERSITIES. THERE IS NO
 EXISTING BUILDING CODE TO GO BY UNDER SPECIAL
 OCCUPANCIES FOUND IN CHAPTER 4. IN THE 2017FBC-B
 SECTION 468.1 SCOPING DEALS WITH FLORIDA?S PUBLIC,
 PRIVATE SCHOOLS, COLLEGES AND UNIVERSITIES.
  
 1ST ROUND OF COMMENTS. UNDER THE HEADING OF BUILDING
 BASICS THE PLANS STATE ALTERATION LEVEL L11-
 PRESCRIPTIVE COMPLIANCE METHOD (301.1.1). I?M NOT SURE
 WHAT METHOD IS BEING CONVEYED?
 PLEASE NOTE THIS IS A PARTIAL CHANGE OF OCCUPANCY FROM
 AN A-4 INDOOR SPORTING EVENTS WITH SPECTATOR SEATING TO
 E, EDUCATIONAL. PLEASE REVIEW THE SCOPING REQUIREMENTS
 IN THE 2017 EXISTING BUILDING CODE 101.2 THE EXCEPTION.
 PLEASE BE AWARE OF THE 2017 FBC-EXISTING BUILDING CODE
 SCOPING REQUIREMENTS AND THE EXCEPTION FOUND UNDER
 SECTION 101.2. EXCEPTION: 2.
 EXCEPTION 2 DOES NOT ALLOW THE USE OF THE EXISTING
 BUILDING CODE; IT REFERS YOU BACK TO THE BUILDING CODE
 FOR NEW CONSTRUCTION. FOR THE PURPOSE OF PUBLIC
 EDUCATIONAL FACILITIES AND STATE LICENSED FACILITIES
 (CHARTER SCHOOLS, PRIVATE SCHOOLS), SEE CHAPTER 4,
 SPECIAL OCCUPANCIES, OF THE FLORIDA BUILDING CODE,
 BUILDING.
 SECTION 468.1 IS FOR FLORIDA?S PUBLIC AND PRIVATE
 SCHOOLS, COLLEGES AND UNIVERSITIES. THERE IS NO
 EXISTING BUILDING CODE TO GO BY UNDER SPECIAL
 OCCUPANCIES FOUND IN CHAPTER 4. IN THE 2017FBC-B
 SECTION 468.1 SCOPING DEALS WITH FLORIDA?S PUBLIC,
 PRIVATE SCHOOLS, COLLEGES AND UNIVERSITIES.
  
 1C-D) THE RESPONSE INDICATES TO SEE THE TABLE 2902.1 ON
 SHEET A-3 INDICATES THE BREAK DOWN OF TOILETS BUT THERE
 IS ONLY ONE RESTROOM DESIGNATED FOR TEACHERS THAT IS IN
 THE TEACHER PLANNING ROOM. THERE ARE 26 CLASSROOMS, 26
 TEACHERS + 8 KITCHEN STAFF AND PROBABLY AT LEAST 8
 ADMINISTRATIVE STAFF (NOT INCLUDED IN TABLE 2902.1)
 BRINGING THE ADULT STAFF UP TO 42 OCCUPANTS REQUIRING 2
 ADULT TOILETS. 2017 FBC-B SECTION 468.5.2 TEACHERS
 TOILETS
 1ST ROUND OF COMMENTS. THERE IS NOT ENOUGH INFORMATION
 ON THE PLAN TO DETERMINE CODE COMPLIANCE FOR CODE
 COMPLIANCE FOR THE REQUIRED NUMBER OF FIXTURES REQUIRED
 UNDER THE 2017 FBC-B TABLE 2902.1 FOR EDUCATION.
  
 1D) PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION
 468.5.2 TEACHERS TOILETS. FACILITIES AND STAFF TOILETS
 SHALL BE SEPARATE FROM STUDENT TOILETS.
  
 1E-H) COMPLIED.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-15 Cont ID  
Sent By jwitmer Date 2020-09-15 Time 18:45 Rev Time 0.00
Received By jwitmer Date 2020-09-15 Time 13:02 Sent To  
Notes
2020-09-15 13:07:51WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW/ UNIVERSITY PREPARATORY
 ACADEMY
 W. P. B. PERMIT: 20080995
 ADD: 2101 AUSTRALIAN AVE.
 CONT: P & T CONSTRUCTION
 TEL: 561-324-8050
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 15TH/ 2020
 ACTION: DENIED
  
 1) SHEET A-1:
 1A) THE INDEX OF DRAWINGS INDICATES THERE IS A DEMO
 SHEET WHICH IS NOT IN THIS SET OF PLANS. PART OF THE
 PLAN REVIEW EXERCISE IS TO SEE WHAT IS EXISTING AND
 WHAT IS TO BE DEMOLISHED. 107.2.1.2 ADDITIONAL
 INFORMATION REQUIRED. THERE IS A DISCREPANCY IN THE
 SUBMITTED PLAN SET AND INDEX.
  
 1B) UNDER THE HEADING OF BUILDING BASICS THE PLANS
 STATE ALTERATION LEVEL L11- PRESCRIPTIVE COMPLIANCE
 METHOD (301.1.1). I?M NOT SURE WHAT METHOD IS BEING
 CONVEYED?
 PLEASE NOTE THIS IS A PARTIAL CHANGE OF OCCUPANCY FROM
 AN A-4 INDOOR SPORTING EVENTS WITH SPECTATOR SEATING TO
 E, EDUCATIONAL. PLEASE REVIEW THE SCOPING REQUIREMENTS
 IN THE 2017 EXISTING BUILDING CODE 101.2 THE EXCEPTION.
 PLEASE BE AWARE OF THE 2017 FBC-EXISTING BUILDING CODE
 SCOPING REQUIREMENTS AND THE EXCEPTION FOUND UNDER
 SECTION 101.2. EXCEPTION: 2.
 EXCEPTION 2 DOES NOT ALLOW THE USE OF THE EXISTING
 BUILDING CODE; IT REFERS YOU BACK TO THE BUILDING CODE
 FOR NEW CONSTRUCTION. FOR THE PURPOSE OF PUBLIC
 EDUCATIONAL FACILITIES AND STATE LICENSED FACILITIES
 (CHARTER SCHOOLS, PRIVATE SCHOOLS), SEE CHAPTER 4,
 SPECIAL OCCUPANCIES, OF THE FLORIDA BUILDING CODE,
 BUILDING.
 SECTION 468.1 IS FOR FLORIDA?S PUBLIC AND PRIVATE
 SCHOOLS, COLLEGES AND UNIVERSITIES. THERE IS NO
 EXISTING BUILDING CODE TO GO BY UNDER SPECIAL
 OCCUPANCIES FOUND IN CHAPTER 4. IN THE 2017FBC-B
 SECTION 468.1 SCOPING DEALS WITH FLORIDA?S PUBLIC,
 PRIVATE SCHOOLS, COLLEGES AND UNIVERSITIES.
  
 1C) THERE IS NOT ENOUGH INFORMATION ON THE PLAN TO
 DETERMINE CODE COMPLIANCE FOR CODE COMPLIANCE FOR THE
 REQUIRED NUMBER OF FIXTURES REQUIRED UNDER THE 2017
 FBC-B TABLE 2902.1 FOR EDUCATION.
  
 1D) PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION
 468.5.2 TEACHERS TOILETS. FACILITIES AND STAFF TOILETS
 SHALL BE SEPARATE FROM STUDENT TOILETS.
  
 1E) THE PLANS DO NOT INDICATE WHAT AGE GROUP OF
 CHILDREN ARE GOING TO OCCUPY THE NEW ROOMS? ARE ANY OF
 THE NEW ROOMS ALSO GOING TO BE USED FOR AFTER SCHOOL
 CARE AND WHAT AGE OF THE CHILDREN IN THE AFTER-SCHOOL
 PROGRAM? WILL THERE BE ANY DAYCARE, PRE-KINDERGARTEN OR
 KINDERGARTEN IN THE PROPOSE NEW CLASSROOMS? ADDITIONAL
 INFORMATION IS REQUIRED TO BE ABLE TO DO A THOROUGH
 REVIEW OF THESE PLANS. 107.2.1.2.
  
 1F) SHEET A-1 SHOWS STORAGE CLOSETS FOR CHAIRS PLEASE
 PROVIDE THE TOTAL STORAGE CLOSET AREAS TO SEE IF THEY
 ARE OVER 10% OF THE FLOOR PLAN FOR THE BUILDING, THEN
 THEY WOULD BE A SEPARATE STORAGE OCCUPANCY. IF NOT THEN
 THE WALLS OF THE STORAGE CLOSETS MUST SHOW COMPLIANCE
 WITH 509.4.2 AND DEMONSTRATE CONSTRUCTION CAPABLE OF
 RESISTING SMOKE. WALLS SHALL EXTEND FROM FLOOR LEVEL TO
 THE UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB
 ABOVE. IT APPEARS THE DETAILS ON SHEET A-4 DO NOT SHOW
 COMPLIANCE.
  
 1G) SHEET A-1 THE 4 NEW CHAIR STORAGE ROOMS AND DOORS
 7, 8, 9 & 10. THE DOOR SCHEDULE FOR HARDWARE LIST A
 LOCKSET AND ASTRAGAL. PLEASE REFER TO THE 2017 FBC-B
 SECTION 509.4.2 PROTECTION. DOORS SHALL BE SELF-CLOSING
 OR AUTOMATIC CLOSING UPON DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3.
  
 1H) SHEET A-1 AS WELL AS M-1 SHOW A RAISED PLATFORM.
 SHEET A-1 STATES FUTURE RAISED PLATFORM. EITHER REMOVE
 THE RAISED PLATFORM OR PROVIDE THE DETAILS AS TO OW THE
 RAISED PLATFORM WILL BE BUILT. WE WILL ALSO NEED
 DETAILS OF THE ACCESSIBLE RAMP, STAIRS, LOADING FOR
 BOTH THE STAIRS, RAMP AND PLATFORM, HANDRAIL/ GUARDRAIL
 SYSTEMS. 107.2.1.2. MISSING INFORMATION, ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-06 Cont ID  
Sent By fgiaquin Date 2020-10-06 Time 23:33 Rev Time 0.00
Received By fgiaquin Date 2020-10-06 Time 22:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-07 Cont ID  
Sent By fgiaquin Date 2020-09-07 Time 22:24 Rev Time 0.00
Received By fgiaquin Date 2020-09-07 Time 21:07 Sent To  
Notes
2020-09-07 22:24:09ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLEASE REMOVE FIRE ALARM FROM DRAWINGS. FIRE ALARM
 IS TO BE SUBMITTED AS ITS OWN SEPARATE STAND ALONE
 PERMIT WITH SEPARATE DRAWINGS. FBC 105.1 107.2.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2020-10-16 Time   Rev Time 0.00
Received By pleduc Date 2020-10-16 Time 16:50 Sent To  
Notes
2020-10-16 16:51:30THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By pleduc Date 2020-10-02 Time   Rev Time 0.00
Received By pleduc Date 2020-10-02 Time 14:14 Sent To  
Notes
2020-10-02 14:35:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-08-26 Cont ID  
Sent By pleduc Date 2020-08-26 Time   Rev Time 0.00
Received By pleduc Date 2020-08-26 Time 14:54 Sent To  
Notes
2020-08-26 15:02:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-10-23 Time   Rev Time 0.00
Received By lmarchan Date 2020-10-23 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-19 Cont ID  
Sent By lmarchan Date 2020-10-19 Time 11:10 Rev Time 0.00
Received By lmarchan Date 2020-10-15 Time 13:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-06 Cont ID  
Sent By fgiaquin Date 2020-10-06 Time 23:33 Rev Time 0.00
Received By fgiaquin Date 2020-09-30 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-15 Cont ID  
Sent By jwitmer Date 2020-09-15 Time 18:45 Rev Time 0.00
Received By jwitmer Date 2020-08-21 Time 11:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-10-01 Cont ID  
Sent By medwards Date 2020-10-01 Time 10:31 Rev Time 0.00
Received By medwards Date 2020-10-01 Time 08:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-01 Cont ID  
Sent By medwards Date 2020-09-01 Time 11:52 Rev Time 0.00
Received By medwards Date 2020-09-01 Time 09:27 Sent To  
Notes
2020-09-01 11:52:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20080995
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A DETAIL OF THE RETURN AIR PATH. WHAT
 IS THE HEIGHT OF THE ORIGINAL RETURN AIR INTAKES? FBC
 FS 107.2.1
  
 2) PLEASE SHOW CFM?S OF THE SUPPLY REGISTERS IN THE
 CLASSROOMS. FBC FS 107.2.1
  
 3) PLEASE SHOW THE CFM?S OF THE RETURN AIR TRANSFER
 GRILLES IN EACH CLASSROOM. FBC FS 107.2.1
  
 4) IT APPEARS THE EXISTING RETURN AIR GRILLES ARE IN
 THE MIDDLE OF THE DOORWAYS. WILL THESE NEW CLASSROOMS
 BE SHARING RETURN AIR FROM THE CORRIDORS? FBC FS
 107.2.1
  
 5) PLEASE PROVIDE THE AGE GROUPS OF EACH CLASSROOM. THE
 VENTILATION FOR THE CLASSROOMS IS BASED ON THE AGE OF
 THE CHILDREN. FBC M TABLE 403.3.1.1
  
 6) PLEASE PROVIDE A BREAKDOWN OF EACH CLASSROOM FOR
 THE VENTILATION CALCULATIONS BASED ON; FBC M TABLE
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-10-23 Cont ID  
Sent By ccole Date 2020-10-23 Time 16:20 Rev Time 0.00
Received By ccole Date 2020-10-23 Time 15:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-10-19 Cont ID  
Sent By ccole Date 2020-10-19 Time 10:48 Rev Time 0.00
Received By ccole Date 2020-10-19 Time 07:13 Sent To  
Notes
2020-10-19 10:49:112ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20080995
 10/19/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE REQUIRED PLUMBING FIXTURE CALCULATIONS
 INDICATE 10 DRINKING FOUNTAINS REQUIRED AND PROVIDED,
 HOWEVER IT APPEARS THAT ONLY 9 ARE SHOWN ON THE FLOOR
 PLAN- TABLE 403.3 FBC P AND SECTION 211.2 FBC ACC.
  
 2) P1: REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, SPOUT LOCATIONS, AND THE ADA BARRIERS IF
 INSTALLED.
  
 3) P1: SHOW THE NEW DRINKING FOUNTAIN INSTALLATIONS ARE
 IN COMPLIANCE WITH COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES ABOVE THE FINISH FLOOR OR
 GROUND SHALL PROTRUDE 4 INCHES MAXIMUM HORIZONTALLY
 INTO THE CIRCULATION PATH.
  
 4) P1: WATER AND SANITARY RISER DRAWINGS HAVE BEEN
 PROVIDED TO SHOW THE PLUMBING FOR THE 3 NEW DRINKING
 FOUNTAINS. IT APPEARS THAT ONLY TWO NEW (P3) DRINKING
 FOUNTAINS ARE SHOWN IN THE WATER RISER.
  
 A) PROVIDE A CORRELATING SYMBOL LEGEND FOR THE P
 FIXTURES SHOWN IN THE RISER- SECTION 107.2.1 WPB
  
 B) SHOW THE LOCATIONS OF THE SHUT OFF VALVES FOR THE
 NEW FOUNTAINS- SECTION 606.2
  
 C) SHOW THE LOCATIONS OF THE REQUIRED WATER HAMMER
 ARRESTORS ON WATER PIPES SUPPLYING THE DRINKING
 FOUNTAINS- SECTION 604.9 FBC P.
  
 5) P1: THE LOCATION OF THE EXISTING WATER HEATER IS NOT
 SHOWN ON THE PLUMBING FLOOR PLAN, HOWEVER IT SHOULD BE
 NOTED THAT THE RISER DRAWING DOES NOT SHOW A
 RECIRCULATION LINE FOR THE SYSTEM. IT APPEARS THAT THE
 DEVELOPED LENGTH OF THE SYSTEM MAY EXCEED 50 FT. FROM
 THE WATER HEATER TO THE MOST REMOTE OUTLET REQUIRING
 HOT OR TEMPERED WATER. PLEASE VERIFY COMPLIANCE WITH
 SECTION 607.2 FBC P.
  
 6) REFER TO SECTION 468.3.5.6 FBC B- FLOOR DRAINS AND
 HOSE BIBBS. PLEASE VERIFY ALL GROUP TOILET ROOMS ARE
 PROVIDED WITH AT LEAST ONE FLOOR DRAIN AND ONE EASILY
 ACCESSIBLE HOSE BIBB. THE FLOOR SHALL BE SLOPED DOWN TO
 THE DRAIN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-10-01 Cont ID  
Sent By ccole Date 2020-10-01 Time 16:54 Rev Time 0.00
Received By ccole Date 2020-10-01 Time 16:54 Sent To  
Notes
2020-10-01 16:54:292ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20080995
 10/1//2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENT #1 FROM THE IST REVEW HAS NOT BEEN COMPLETELY
 ADDRESSED. I HAVE ADDED NOTES TO THE COMMENT BASED ON
 REVIEW OF THE CORRECTED PLANS.
  
 1) SHEETS A-1: THE NOTES UNDER BUILDING BASICS APPEAR
 TO INDICATE EITHER A LEVEL II OR III ALTERATION AS SET
 FORTH IN THE FLORIDA EXISTING BUILDING CODE- 2017 SIXTH
 EDITION. PLEASE REFER TO SECTION 810.1 MINIMUM
 FIXTURES. WHERE THE OCCUPANT LOAD OF THE STORY IS
 INCREASED BY MORE THAN 20 PERCENT, PLUMBING FIXTURES
 FOR THE STORY SHALL BE PROVIDED IN QUANTITIES SPECIFIED
 IN THE FLORIDA BUILDING CODE PLUMBING BASED ON THE
 INCREASED OCCUPANT LOAD. BECAUSE AN EXISTING FLOOR OR
 LIFE SAFETY PLAN WAS NOT PROVIDED IT IS NOT POSSIBLE TO
 TELL IF THERE HAS BEEN AN INCREASE BEYOND THE ALLOWABLE
 20 PERCENT. PLEASE PROVIDE AN EXISTING FLOOR PLAN
 DRAWING AND OCCUPANT LOAD CALCULATIONS FOR THE EXISTING
 AND NEW FLOOR PLANS. REFER TO TABLE 403.3 FBC P AND
 PROVIDE A PLUMBING FIXTURE CALCULATION SCHEDULE THAT
 SHOWS THE REQUIRED AND PROVIDED NUMBER OF PLUMBING
 FIXTURES.
 THE PLUMBING FIXTURE COUNT TABLE DOES NOT INCLUDE THE
 REQUIRED DRINKING FOUNTAINS AND SERVICE SINK- TABLE
 403.3 FBC P. PLEASE NOTE THE PLAN APPEARS TO SHOW
 DEFICIENCY IN THE NUMBER OF DRINKING FOUNTAINS
 PROVIDED. THE FIXTURE COUNT ALSO DOES NOT PROVIDE A
 BREAKDOWN OF MALE, FEMALE, OR UNISEX BATHROOMS, OR
 BREAKDOWN COUNTS FOR BUSINESS AND ASSEMBLY AREAS.
 PLEASE NOTE THE TOTAL OCCUPANCY OF 890 ON SHEET A-3
 DOES NOT INCLUDE THE OCCUPANCY LOADS FOR THE
 MULTI-ASSEMBLY AREAS- SECTION 403.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-27 Cont ID  
Sent By ccole Date 2020-08-27 Time 17:01 Rev Time 0.00
Received By ccole Date 2020-08-27 Time 16:19 Sent To  
Notes
2020-08-27 17:02:101ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20080995
 8/27/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: THE NOTES UNDER BUILDING BASICS APPEAR TO
 INDICATE EITHER A LEVEL II OR III ALTERATION AS SET
 FORTH IN THE FLORIDA EXISTING BUILDING CODE- 2017 SIXTH
 EDITION. PLEASE REFER TO SECTION 810.1 MINIMUM
 FIXTURES. WHERE THE OCCUPANT LOAD OF THE STORY IS
 INCREASED BY MORE THAN 20 PERCENT, PLUMBING FIXTURES
 FOR THE STORY SHALL BE PROVIDED IN QUANTITIES SPECIFIED
 IN THE FLORIDA BUILDING CODE PLUMBING BASED ON THE
 INCREASED OCCUPANT LOAD. BECAUSE AN EXISTING FLOOR OR
 LIFE SAFETY PLAN WAS NOT PROVIDED IT IS NOT POSSIBLE TO
 TELL IF THERE HAS BEEN AN INCREASE BEYOND THE ALLOWABLE
 20 PERCENT. PLEASE PROVIDE AN EXISTING FLOOR PLAN
 DRAWING AND OCCUPANT LOAD CALCULATIONS FOR THE EXISTING
 AND NEW FLOOR PLANS. REFER TO TABLE 403.3 FBC P AND
 PROVIDE A PLUMBING FIXTURE CALCULATION SCHEDULE THAT
 SHOWS THE REQUIRED AND PROVIDED NUMBER OF PLUMBING
 FIXTURES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-10-23 Cont ID  
Sent By ccole Date 2020-10-23 Time 16:20 Rev Time 0.00
Received By ccole Date 2020-10-23 Time 16:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-18 Cont ID  
Sent By jwitmer Date 2020-10-18 Time 13:28 Rev Time 0.00
Received By jwitmer Date 2020-10-18 Time 12:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-04 Cont ID  
Sent By jwitmer Date 2020-10-04 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2020-10-04 Time 13:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By jwitmer Date 2020-09-15 Time 18:44 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy