| 2020-09-10 14:20:55 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20080982 |
| | 9/10/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS ISOMETRIC DRAWING: |
| | A) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE INTERIOR |
| | PIPING RUN- SECTION G2413.4.1 & G2413.4.2 FBC RES, AND |
| | THE TOTAL BTUH LOAD OF THE ENTIRE SYSTEM- SECTION |
| | G2413.2 FBC RES. |
| | |
| | B) THE SPECS SUBMITTED FOR THE GENERATOR UNDER |
| | PERMIT-20070263 INDICATE 327,000 BTUH AT FULL LOAD- |
| | PLEASE CORRECT- SECTION 107.2.1 WPB. |
| | |
| | C) INDICATE THE PIPE SIZING TABLE ON THE DRAWING- SEE |
| | TABLES G2413.4(1)- G2413.4(8) FBC RES. |
| | |
| | D) SHOW THE LOCATIONS OF THE FLEX CONNECTOR, SHUTOFF |
| | VALVE FOR THE GAS SUPPLY TO THE GENERATOR, AND THE |
| | REQUIRED PIPE UNION AT THE REGULATOR- SECTIONS G2420.4, |
| | G2420.5, AND G2421.2(7). |
| | |
| | E) SUBMIT MANUFACTURER'S SPECS FOR THE B42 SERIES |
| | REGULATOR WITH MARKUPS ON THE COPY TO INDICATE THE |
| | MODEL NUMBER, INLET PRESSURE, ORIFICE AND SPRING SIZE |
| | OF THE SELECTED REGULATOR- SECTION G2421.1 & G2421.2. |
| | |
| | F) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX |
| | CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING |
| | STANDARDS, AND INSTALLATION GUIDELINES- SECTION |
| | G2415.1. |
| | |
| | G) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO |
| | THE UG PE PIPING- SECTION G2415.17.3. |
| | |
| | H) INDICATE HOW THE PE PIPING RISERS WILL CONNECT TO |
| | THE METALLIC PIPING PER SECTIONS G2415.17.1 & |
| | G2415.17.2. PLEASE NOTE THAT SPECS FOR ANODELESS RISERS |
| | AND PE/METALLIC PIPE CONNECTORS SHALL BE LISTED AND |
| | LABELED. |
| | |
| | 2) SUBMIT INSTALLATION GUIDELINES FROM GENERAC TO |
| | VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS |
| | SHOWN ON THE SURVEY. PLEASE PROVIDE A CLEARER COPY OF |
| | THE MARKED-UP SURVEY SHOWING THE GENERATOR DISTANCES TO |
| | THE BUILDING, OPERABLE OPENINGS INTO THE BUILDING, AND |
| | THE ADJACENT PROPERTY LINES- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |