Plan Review Details - Permit 20080980
Plan Review Stops For Permit 20080980
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2020-09-18 Cont ID  
Sent By jwitmer Date 2020-09-18 Time 09:22 Rev Time 0.00
Received By jwitmer Date 2020-09-18 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-18 Cont ID  
Sent By jwitmer Date 2020-09-18 Time 10:31 Rev Time 0.00
Received By jwitmer Date 2020-09-18 Time 09:13 Sent To  
Notes
2020-09-18 11:44:40WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20081068
 ADD: 901 45TH ST. KAPLAN BLDG. ADULT & PEDIATRIC
 OUTPATIENT CLINIC
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. SEPT. 18TH/2020
 ACTION: DENIED
  
 1) SHEET G001 CODE ANALYSIS HEADING VIII OCCUPANT LOAD.
 IN ALL 3 CASES BUSINESS, ASSEMBLY &STORAGE THE DESIGNER
 OF RECORD ROUNDED DOWN THE OCCUPANT LOAD COUNT.
 BUSINESS 11,085/100= 110.85 / 111
 ASSEMBLY 1120/15= 74.66 / 75
 STORAGE 805/300= 2.68 / 03
 TOTAL OCCUPANTS 189
 IN BOTH THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA
 INFORMAL INTERPRETATION & 2015 IBC CODE COMMENTARY BOTH
 HAVE YOU ROUND UP TO THE NEXT WHOLE OCCUPANT SINCE
 THERE ARE NO PARTS OF OCCUPANTS.
  
 2) SHEET G301 ADA TYPICAL STANDARDS
 2A) THE UPPER LEFT CORNER OF SHEET. THE MIRROR IS SHOWN
 OVER THE LAV AND NO HEIGHT DIMENSION IS GIVEN.
 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MINIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 2B) THE UPPER LEFT CORNER OF THE SHEET. THE WATER
 CLOSET GRAB BARS ARE SHOWN TO BE MEASURED CENTERLINE TO
 THE FINISH FLOOR, NOT THE TOP OF THE GRIPPING SURFACE.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 2C) THE BOTTOM ABOUT CENTER OF THE SHEET THE ELECTRIC
 DRINKING FOUNTAIN SHOWS A OUTDATED SINGLE HEIGHT
 DRINKING FOUNTAIN, THE UPPER LEFT PORTION OF THE PAGE
 DOES SHOW A CODE COMPLIANT HIGH-LOW DRINKING FOUNTAIN,
 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 2D) DRINKING FOUNTAINS ALSO NEED TO SHOW COMPLIANCE
 WITH PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH. IF NOT INSTALLED IN AN ALCOVE.
  
 2E) SHOWS FIGURE 10 TYPICAL TOILET LAYOUT WITH A IN
 SWING DOOR CROSSING BOTH CLEAR FLOOR SPACE FOR THE
 WATER CLOSET AND LAV. IF YOU USE THE 2017
 FBC-ACCESSIBILITY CODE FIGURE 604.8.1.6 SHOWS AN
 OUTSWING DOOR. PLEASE ALSO REVIEW SECTION 603.2.3 DOOR
 SWING AND EXCEPTION 2. I BELIEVE THIS IS HOW YOU ARE
 STRIVING TO SHOW CODE COMPLIANCE. WHAT IS MISSING IS
 THE REQUIRED CLEAR FLOOR SPACE BEYOND THE ARC OF THE
 DOOR. IT IS USUALLY SHOWN AT A 45-DEGREE ANGLE TO THE
 ENTRY DOOR.
  
 3) SHEET A-151 SHOWS AREA WHERE WORK IS TO TAKE PLACE.
 PLEASE ALSO NOTE THE ON-CALL ROOM IS SHOWN AS AREA
 OUTSIDE OF THE SCOPE. THE DOOR LEADING INTO THIS ROOM
 (DOOR # 133) DOES NOT HAVE 18 INCHES ON THE LATCH SIDE
 OF THE DOOR, IN ACCORDANCE WITH ACCESS. CODE 404.2.4
 MANEUVERING CLEARANCES. DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS AND GATES SHALL COMPLY WITH
 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL
 WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE FOR
 SIDE CLEARANCE. SEE FIGURE 404.2.4.1(A) FRONT APPROACH
 PULL SIDE.
  
 3A) THE PLANS SHOW TO A LARGE EXTENT OF THE REMODELING,
 THE UPGRADE TO RESTROOMS. PLEASE SHOW HOW
 DISPROPORTIONATE COST ARE TO BE COMPLETED.
  
 2017 FBC-ACCESSIBILITY CODE, DISPROPORTIONATE COST
 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET
 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW
 THEY ARE GOING TO SPEND UP TO THE 20% DISPROPORTIONATE
 FUNDS ($283,536.00) LISTED FOR EACH ELEMENT WHERE THE
 FUNDS ARE BEING SPENT AND IN THE ORDER LISTED IN
 SECTION 202.4.1 DISPROPORTIONATE COST OF THE 2017
 ACCESSIBILITY CODE.
  
 3B) THIS SAME DOOR (133) SHEET A-101 THERE IS NO
 DIMENSION OF THE HALLWAY INSURING CODE COMPLIANCE WITH
 404.2.4. MANEUVERING CLEARANCES & FIGURE 404.2.4.1( J
 AND OR K). THE RESTROOMS ON BOTH SIDES SHOW THEY ARE
 GOING UNDER ACCESSIBLE UPGRADES.
  
 4) SHEET A201 ALL RESTROOM DETAILS EITHER SHOW THE
 60-INCH CIRCLE OR THE T TURNING AREA, BOTH SWING INTO
 THE CLEAR FLOOR SPACE OF THE DOOR. PLEASE ALSO REVIEW
 SECTION 603.2.3 DOOR SWING AND EXCEPTION 2. I BELIEVE
 THIS IS HOW YOU ARE STRIVING TO SHOW CODE COMPLIANCE.
 WHAT IS MISSING IS THE REQUIRED CLEAR FLOOR SPACE
 BEYOND THE ARC OF THE DOOR. IT IS USUALLY SHOWN AT A
 45-DEGREE ANGLE TO THE ENTRY DOOR.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-05 Cont ID  
Sent By jleahy Date 2020-09-05 Time 15:39 Rev Time 0.00
Received By jleahy Date 2020-09-05 Time 15:39 Sent To  
Notes
2020-09-05 15:42:22FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ALL NEW CIRCUIT NUMBERS DETERMINED IN THE FIELD SHALL
 BE SUBMITTED FOR REVIEW WHEN ADDED TO PLANS AND PANEL
 SCHEDULES , PRIOR TO THE FINAL ELECTRICAL INSPECTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-08-27 Cont ID  
Sent By pleduc Date 2020-08-27 Time   Rev Time 0.00
Received By pleduc Date 2020-08-27 Time 10:04 Sent To  
Notes
2020-08-27 10:04:35THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-09-18 Time 10:32 Rev Time 0.00
Received By lmarchan Date 2020-08-24 Time 09:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-07 Cont ID  
Sent By medwards Date 2020-09-07 Time 11:21 Rev Time 0.00
Received By medwards Date 2020-09-07 Time 10:19 Sent To  
Notes
2020-09-07 11:22:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20080980
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CODE ANALYSIS INDICATES THIS PROJECT OCCUPATION
 CLASSIFICATION GOING FROM AN INSTITUTIONAL TO BUSINESS.
 PLEASE PROVIDE VENTILATION CALCULATIONS FOR THIS NEW
 CLASSIFICATION FOR THE ENTIRE BUILDING.
  
 2) SHEET M0.01: EF-2 DOES NOT SHOW ANY CFM RATES.
 PLEASE INDICATE CFM?S EXHAUSTED WITH EF-2. FBC FS
 107.2.1
  
 3) THE EXHAUST DUCTS IN THE RETURN AIR PLENUM MUST
 COMPLY WITH: FBC M 601.4
  
 4) PLEASE PROVIDE A MECHANICAL DEMO SHEET AND A NEW
 MECHANICAL WORK SHEET. FBC FS 107.2.1
  
 5) SHEET M1.01: PLEASE PROVIDE A SCHEDULE IDENTIFYING
 EXISTING, NEW AND THE HASH LINES THROUGH DUCTS. FBC FS
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-09-08 Cont ID  
Sent By jesmith Date 2020-09-08 Time 16:24 Rev Time 0.00
Received By jesmith Date 2020-09-08 Time 08:33 Sent To  
Notes
2020-09-08 16:24:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20080980 901 45TH ST
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PER WPB FBC 107.2.1, PROVIDE CLEAR FLOOR SPACE FOR
 ALL ACCESSIBLE SINKS; COMPLY WITH FBC ACC 305.3.
  
 2. DETAIL FOR GRAB BARS SHOW 33 INCHES FROM FLOOR TO
 CENTERLINE. PER FBC ACC 609.4, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
  
 3. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
  
 4. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2.
  
 5. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
  
 6. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 SANITARY AND WATER RISER DIAGRAMS. SHOW EXISTING
 INFRASTRUCTURE AND NEW PIPING WITH POINTS OF
 CONNECTION. IDENTIFY ALL FIXTURES AND EQUIPMENT
 EXISTING AND NEW.
  
 7. PROVIDE TRAP PRIMER AND DETAIL FOR FLOOR DRAIN(S) TO
 COMPLY WITH FBC PL 1002.4.
  
 8. PER FBC 1212.2.2 AND FBC PL 310.3, WALLS AND
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS
 SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE PER
 FBC-BUILDING SEC. 1210.2.2. SECTION 1210.2.2 STIPULATES
 THAT THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION
 IS THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A
 TYPE THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL
 COULD BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE
 AND SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 9. SUBMIT A SLAB REPAIR DETAIL FOR REVIEW AND ONCE
 APPROVED HAVE TWO COPIES AT THE JOB SITE. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, THE ANCHORING
 MATERIAL FOR THE DOWELS AND THE SPACING OF THE DOWELS
 ON CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE
 TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER
 OVER WELL-COMPACTED SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
  
 10. PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE
 SHOWING COMPLIANCE WITH FBC PL TABLE 403.1, OCCUPANCY
 BUSINESS. INDICATE WHAT IS REQUIRED AND THEN WHAT IS
 SUPPLIED. THIS IS TO INCLUDE WATER CLOSETS, LAVATORIES,
 DRINKING FOUNTAINS AND SERVICE SINK(S). SEE THE
 FOLLOWING COMMENTS CONCERNING DRINKING FOUNTAINS AND
 SERVICE SINK(S).
  
  
 11. PER WPB FBC 107.2.1, PROVIDE TWO (2) DRINKING
 FOUNTAINS TO COMPLY WITH FBC PL TABLE 403.1, OCCUPANCY
 BUSINESS OR PROVIDE DRAWING WITH LOCATION OF EXISTING
 DRINKING FOUNTAINS IN ADJOINING AREA WITHIN A DISTANCE
 OF TRAVEL OF 500 FEET OF THE MOST REMOTE LOCATION IN
 THE TENANT SPACE AND NOT MORE THAN ONE STORY ABOVE OR
 BELOW THE TENANT SPACE; DRINKING FOUNTAINS SHALL BE
 LOCATED ON AN ACCESSIBLE ROUTE PER FBC PL 403.5.
 TWO (2) DRINKING FOUNTAINS ARE REQUIRED; AN ACCESSIBLE
 BI-LEVEL DRINKING FOUNTAIN CONSTITUTES TWO (2) DRINKING
 FOUNTAINS.
  
 12. PER WPB FBC 107.2.1, PROVIDE ONE (1) SERVICE SINK
 TO COMPLY WITH FBC PL TABLE 403.1, OCCUPANCY BUSINESS
 OR PROVIDE DRAWING WITH LOCATION OF THE SAME IN
 ADJOINING AREA WHICH WILL SERVICE THE FACILITY. THERE
 APPEARS TO BE A SERVICE SINK IN THE JANITOR RM 102, BUT
 THERE IS NO SANITARY PIPING SHOWN. CLARIFY.
  
  
 13. PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING
 SCHEDULE THE APPLICATION OF FIXTURE P-6, OATEY 38808
 AND PROVIDE NOTE IF A WATER HAMMER ARRESTOR IS INCLUDED
 AND IF LEAD FREE.
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20080980 901 45TH ST
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-07 Cont ID  
Sent By medwards Date 2020-09-07 Time 11:33 Rev Time 0.00
Received By medwards Date 2020-09-07 Time 11:33 Sent To  
Notes
2020-09-07 11:34:36SHEET G101: MISSING DIGITAL SEAL AND SIGNATURE OF
 DESIGNER.
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  