| 2020-08-27 16:05:52 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20080881 |
| | 8/27/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS CVR, A1, & E1: REFER TO TABLE 403.3 AND |
| | PROVIDE PLUMBING FIXTURES CALCULATIONS FOR THE BUSINESS |
| | OCCUPANCY. PROVIDE A SCHEDULE THAT INDICATES THE |
| | REQUIRED AND PROVIDED FIXTURES. CONCERNING THE REQUIRED |
| | DRINKING FOUNTAIN FOR BUSINESS OCCUPANCIES, PLEASE |
| | CORRECT THE NOTE UNDER CODE ANALYSIS ON SHEET CVR. IN |
| | RESTAURANTS ONLY WHERE DRINKING WATER IS PROVIDED TO |
| | CUSTOMERS IN A CONTAINER FREE OF CHARGE, DRINKING |
| | FOUNTAINS SHALL NOT BE REQUIRED- SECTION 410.4. PLEASE |
| | NOTE DRINKING FOUNTAINS SHALL NOT BE REQUIRED FOR AN |
| | OCCUPANT LOAD OF 15 OR FEWER- SECTION 410.2. |
| | |
| | 2) SHEETS CVR, A1, & E1: VERIFY COMPLIANCE WITH SECTION |
| | 403.3 EXCEPTION 2: SEPARATE PLUMBING FIXTURES ARE NOT |
| | REQUIRED FOR AN OCCUPANT LOAD INCLUDING BOTH EMPLOYEES |
| | AND CUSTOMERS OF 15 OR FEWER. |
| | |
| | 3) SHEETS CVR, A1, & E1: SECTION 403.3 REQUIRES THAT |
| | PUBLIC TOILET FACILITIES SHALL BE PROVIDED FOR |
| | CUSTOMERS, PATRONS AND VISITORS TO THE NEW TENANT SPACE |
| | UNLESS EXCEPTION 2 UNDER 403.3 IS APPLICABLE. PLEASE |
| | VERIFY COMPLIANCE WITH EXCEPTION 2 UNDER 403.3, OR |
| | PROVIDE A PUBLIC TOILET ROOM. PLEASE NOTE THAT PUBLIC |
| | ACCESS THROUGH THE KITCHEN AREA TO THE TOILET ROOM AT |
| | BOH IS NOT ALLOWED PER SECTION 403.3.1. |
| | SECTION 403.3 EXCEPTION 2: PUBLIC TOILET FACILITIES |
| | SHALL NOT BE REQUIRED IN STRUCTURES AND TENANT SPACES |
| | INTENDED FOR QUICK TRANSACTIONS, INCLUDING TAKEOUT, |
| | PICKUP AND DROP-OFF, HAVING A PUBLIC ACCESS AREA LESS |
| | THAN OR EQUAL TO 300 SQUARE FEET. |
| | |
| | 4) A1 & E1: THE NEW TOILET ROOM SHALL BE DESIGNED IN |
| | ACCORDANCE WITH THE FLORIDA ACCESSIBILITY CODE- 2017 |
| | SIXTH EDITION. REFER TO SECTION 213 AND PROVIDE |
| | ENLARGED, DIMENSIONED TOILET ROOM DRAWINGS SHOWING: |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- SECTION 606.2. |
| | C) TURNING SPACE DIAMETER- SECTION 304.3. |
| | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| | SECTION 604.2. |
| | E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| | FLOOR- SECTION 604.4. |
| | F) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE |
| | FINISHED FLOOR- SECTION 606.3 |
| | G) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| | 306. |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 & 609.4 |
| | I) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION |
| | 604.6. |
| | J) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE |
| | TOILET PAPER DISPENSER- SECTION 604.7. |
| | L) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE |
| | BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3. |
| | |
| | 5) A1: PROVIDE AN INTERIOR FINISH MATERIAL SCHEDULE FOR |
| | THE NEW TOILET ROOM- SECTION 310.3 FBC P. |
| | |
| | 6) E1: IT APPEARS THAT THE SANITARY RISER DOES NOT |
| | REPRESENT THE NEW TOILET ROOM DRAIN AND VENT SYSTEM AND |
| | IS SHOWING THE GREASE WASTE SYSTEM. PLEASE CORRECT PER |
| | SECTION 107.2.1 AND 107.3.5.1 WPB. |
| | |
| | 7) E1: CORRECT THE 3-COMPARTMENT SINK/GREASE TRAP |
| | DETAIL AND THE GREASE TRAP RISER IN ACCORDANCE WITH |
| | SECTIONS 802.1.8 & 802.2 FBC P. EACH WELL OF A |
| | MULTIPLE-COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLY |
| | TO A WASTE RECEPTOR, |
| | 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. |
| | SINKS, IN OTHER THAN DWELLING UNITS, USED FOR THE |
| | WASHING, RINSING OR SANITIZING OF UTENSILS, DISHES, |
| | POTS, PANS OR SERVICE WARE USED IN THE PREPARATION, |
| | SERVING OR EATING OF FOOD SHALL DISCHARGE INDIRECTLY |
| | THROUGH AN AIR GAP OR AN AIR BREAK TO THE DRAINAGE |
| | SYSTEM. |
| | 802.2 INSTALLATION. |
| | INDIRECT WASTE PIPING SHALL DISCHARGE THROUGH AN AIR |
| | GAP OR AIR BREAK INTO A WASTE RECEPTOR. WASTE RECEPTORS |
| | SHALL BE TRAPPED AND VENTED AND SHALL CONNECT TO THE |
| | BUILDING DRAINAGE SYSTEM. INDIRECT WASTE PIPING THAT |
| | EXCEEDS 30 INCHES (762 MM) IN DEVELOPED LENGTH MEASURED |
| | HORIZONTALLY, OR 54 INCHES (1372 MM) IN TOTAL DEVELOPED |
| | LENGTH, SHALL BE TRAPPED. |
| | |
| | 8) E-1: IT APPEARS THAT THE FLOOR SINK FOR THE |
| | 3-COMPARTMENT SINK IS MISLABELED AS A FLOOR DRAIN, AND |
| | THE ROOM FLOOR DRAIN IS MISSING FROM THE RISER- SEE |
| | SECTION 802.3.1. |
| | |
| | 9) E-1: TRAP SEAL PROTECTION IS REQUIRED FOR THE FLOOR |
| | DRAIN- SECTION 1002.4.1 & 1002.4.1.1. PLEASE NOTE THAT |
| | TRAP SEAL PRIMER VALVES SHALL CONFORM TO ASSE 1018. |
| | |
| | 10) E-1 GREASE TRAP RISER: THE MOP SINK AND |
| | 3-COMPARTMENT SINK TRAPS REQUIRE VENTING PER SECTIONS |
| | 901.2.1 AND 802.2. |
| | |
| | 11) E-1 GREASE TRAP RISER: WITHIN EACH PLUMBING SYSTEM, |
| | NOT LESS THAN ONE STACK VENT OR VENT STACK SHALL EXTEND |
| | OUTDOORS TO THE OPEN AIR- SECTION 918.7. |
| | |
| | 12) E-1 GREASE INTERCEPTOR: A) PROVIDE AN EQUIPMENT |
| | SCHEDULE FOR THE NEW INTERCEPTOR INDICATING THE MAKE, |
| | MODEL AND GALLON SIZE- SECTION 1003.3.4 B) PROVIDE |
| | GREASE WASTE CALCULATIONS IN ACCORDANCE WITH SECTION |
| | AND TABLE 1003.3.4.1. C) PROVIDE A PLUMBING PIPING |
| | DETAIL IN THE PLAN CONSISTENT WITH THE MANUFACTURER'S |
| | GUIDELINES FOR INSTALLATION- SECTION 1003.3.4.1. |
| | |
| | 13) E-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW |
| | TANKLESS WATER HEATER. PLEASE CLARIFY WHY THERE ARE TWO |
| | WATER HEATERS SHOWN ON THE PLANS- SECTION 107.2.1 WPB. |
| | |
| | 14) E-1: PROVIDE A WATER DISTRIBUTION RISER SHOWING THE |
| | SUPPLY PIPING RUNS TO THE PLUMBING FIXTURES, AND |
| | LOCATIONS OF SHUT OFF VALVES, AND OTHER DEVICES SUCH AS |
| | WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS, AND MIXING |
| | VALVES- SECTION 107.3.5.1 WPB. |
| | |
| | 15) E-1: INDICATE HOW REQUIRED TEMPERED WATER WILL BE |
| | PROVIDE TO THE LAVATORY SINK- SECTION 416.5 FBC P. |
| | PLEASE NOTE THAT TEMPERATURE LIMITING DEVICES SUCH AS |
| | MIXING VALVES SHALL CONFORM TO ASSE 1070 OR CSA B125.3. |
| | |
| | 16) E-1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE |
| | ON THE PLAN- SECTION 401.1 FBC P 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |