| 2020-09-18 16:04:09 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) BASED ON THE PHOTOS THAT WERE SUBMITTED, IT APPEARS |
| | THAT THERE IS ASBESTOS SHINGLE SIDING ON THE HOUSE. |
| | FAILED PLAN REVIEW, RESIDENTIAL: |
| | |
| | WRITTEN NOTIFICATION TO THE HEALTH DEPARTMENT IS |
| | REQUIRED FOR A RESIDENTIAL BUILDING HAVING 4 OR LESS |
| | DWELLING UNITS, IF IT HAS BEEN USED FOR COMMERCIAL |
| | PURPOSES OR IT IS BEING DEMOLISHED AS PART OF A |
| | COMMERCIAL OR PUBLIC PROJECT (WHICH INCLUDES |
| | CITY-INITIATED DEMOLITION OF A SINGLE FAMILY |
| | RESIDENCE). IF THIS PROJECT IS SUBJECT TO ASBESTOS |
| | NOTIFICATION REQUIREMENTS, PROVIDE A SIGNED |
| | ACKNOWLEDGMENT FROM THE CONTRACTOR STATING THAT THE |
| | INSTRUCTIONS ON THE WEBSITE OF THE ASBESTOS PROGRAM |
| | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH |
| | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE |
| | GIVEN TIMELY. IF THIS PROJECT IS NOT SUBJECT TO |
| | ASBESTOS NOTIFICATION REQUIREMENTS, THE CONTRACTOR IS |
| | TO PROVIDE A SIGNED STATEMENT ON LETTERHEAD EXPLAINING |
| | WHY IT IS EXEMPT (FOR EXAMPLE, ?THIS PROJECT IS EXEMPT |
| | BECAUSE IT IS A SINGLE FAMILY RESIDENCE AND IS NOT A |
| | PART OF A COMMERCIAL OR PUBLIC PROJECT, AND IS NOT A |
| | CITY-INITIATED DEMOLITION?). |
| | |
| | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS |
| | CAN BE FOUND ON THEIR WEBSITE: |
| | |
| | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| | RENOVATION.HTML |
| | |
| | 2) SUBMIT A WALL SECTION SHOWING THAT THE PROPOSED |
| | STUCCO APPLICATION COMPLIES WITH FBC-R703.7. SPECIFY |
| | THE WATERPROOFING MEMBRANE, THE BOND BREAK, THE WIRE |
| | LATH FASTENERS AND SPACING, THE WEEP SCREED AT THE BASE |
| | OF THE WOOD FRAME WALLS, THE STUCCO THICKNESS, ETC. |
| | FBC-R703.7 EXTERIOR PLASTER. INSTALLATION OF THESE |
| | MATERIALS SHALL BE IN COMPLIANCE WITH ASTM C926, ASTM |
| | C1063 AND THE PROVISIONS OF THIS CODE. |
| | |
| | |