Plan Review Details - Permit 20080820
Plan Review Stops For Permit 20080820
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-25 Cont ID  
Sent By lmarchan Date 2020-09-25 Time 10:58 Rev Time 0.00
Received By lmarchan Date 2020-09-24 Time 07:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-08 Cont ID  
Sent By lmarchan Date 2020-09-08 Time 10:22 Rev Time 0.00
Received By lmarchan Date 2020-09-04 Time 14:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-20 Cont ID  
Sent By ccarvaja Date 2020-08-20 Time 10:40 Rev Time 0.00
Received By ccarvaja Date 2020-08-19 Time 15:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-09-25 Cont ID  
Sent By medwards Date 2020-09-25 Time 09:53 Rev Time 0.00
Received By medwards Date 2020-09-25 Time 09:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-09-08 Cont ID  
Sent By medwards Date 2020-09-08 Time 09:44 Rev Time 0.00
Received By medwards Date 2020-09-08 Time 09:44 Sent To  
Notes
2020-09-08 09:45:102ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20080820
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MECHANICAL ENGINEER MUST PROVIDE REFRIGERANT
 INFORMATION BASED ON FBC M 1102.1
  
 2) MECHANICAL ENGINEER MUST PROVIDE REFRIGERATION
 CALCULATIONS BASED ON FBC M 1104.4 PROVIDE THE MAXIMUM
 POUNDS OF REFRIGERANT EACH SYSTEM IS DESIGNED FOR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-20 Cont ID  
Sent By medwards Date 2020-08-20 Time 08:52 Rev Time 0.00
Received By medwards Date 2020-08-20 Time 07:57 Sent To  
Notes
2020-08-20 08:53:121ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20080820
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE PRIMARY PERMIT NUMBER ON THE
 APPLICATION. FBC FS 107.2.1
  
 2) PLEASE PROVIDE INFORMATION AND SPECS ON THIS WALK IN
 COOLER AND COMPRESSOR. FBC FS 107.2.1
  
 3) SHEET AE 106: PLEASE MARK AREA OF WORK ON THE
 DRAWING. FBC FS 107.2.1
  
 4) PLEASE PROVIDE REFRIGERANT SYSTEM INFORMATION BASED
 ON FBC M 1102.1
  
 SECTION1102
 SYSTEM REQUIREMENTS
 1102.1GENERAL.
 THE SYSTEM CLASSIFICATION, ALLOWABLE REFRIGERANTS,
 MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, LOCATION
 LIMITATIONS, AND FIELD PRESSURE TEST REQUIREMENTS SHALL
 BE DETERMINED AS FOLLOWS:
 1.DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
 2.DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
 3.DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND
 OCCUPANCY.
 4.DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
 5.REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
 6.NONFACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION 1108.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-08 Cont ID  
Sent By medwards Date 2020-09-08 Time 09:50 Rev Time 0.00
Received By medwards Date 2020-09-08 Time 09:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-20 Cont ID  
Sent By medwards Date 2020-08-20 Time 08:55 Rev Time 0.00
Received By medwards Date 2020-08-20 Time 08:54 Sent To  
Notes
2020-08-20 08:55:17PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481