Plan Review Details - Permit 20080762
Plan Review Stops For Permit 20080762
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2020-09-01 Cont ID  
Sent By jwitmer Date 2020-09-01 Time 07:58 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-09-01 07:58:33 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-09 Cont ID  
Sent By jwitmer Date 2020-09-09 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2020-09-09 Time 13:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-01 Cont ID  
Sent By jwitmer Date 2020-09-01 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2020-09-01 Time 07:57 Sent To  
Notes
2020-09-01 09:15:57WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20080762
 ADD: 603 VILLAGE BLVD. # 208
 CONT: VERTEX CONSTRUCTION
 TEL: 561-619-7722
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 01/2020
 ACTION: DENIED
  
 1) THE FLOOR PLAN SHEET A-1.00 SHOWS THE RESTROOM DOOR
 IDENTIFIED AS DOOR # 2 A OUTSWING DOOR. SHEET A-2.00
 HAS THE DOOR SCHEDULE AND DOOR # 2 THE RESTROOM DOOR
 HAVING A CLOSER & LATCH. PLEASE NOTE ON THE FLOOR PLAN
 SHEET A-1.00 IN THE RESTROOM ON THE LATCH SIDE OF THE
 DOOR THERE IS NOT 1 FOOT MANEUVERING CLEARANCES.
 2017 FBC-ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND
 GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES
 SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE
 REQUIRED LATCH SIDE FOR SIDE CLEARANCE. SEE FIGURE
 404.2.4.1( C ),FRONT APPROACH, PUSH SIDE, DOOR PROVIDES
 WITH BOTH CLOSER AND LATCH.
  
 2A) SHEET P-1 SHOWS THE WATER CLOSET BEING MOVED,
 ASSUMED 3 INCHES FROM 15 INCHES CENTER LINE OFF SIDE
 WALL TO 18 INCHES CENTER LINE OF THE SIDEWALL. THE
 PLANS ARCHITECTURAL NOR PLUMBING SHOW HOW OR HAT THE
 FLOOR INFILL WILL BE. WHILE IT IS TRUE THAT THE TYPE
 II-B BUILDING DOES NOT REQUIRE THE FLOORS TO BE FIRE
 RATED AND THE UNKNOWN IS FOUND IN THE 2017 FBC-B
 SECTION 711.2.4.2. SEPARATING FIRE AREAS. WHERE THE
 HORIZONTAL ASSEMBLY IS SEPARATES A SINGLE OCCUPANCY
 INTO DIFFERENT FIRE AREAS, THE ASSEMBLY SHALL AFIRE
 RESISTANCE RATING OF NOT LESS THAN THAT REQUIRED BY
 SECTION/TABLE 707.3.10.
  
 2B) IF REQUIRED THEN SHOW COMPLIANCE WITH SECTION
 714.4.1.2 THROUGH-PENETRATION FIRESTOP SYSTEMS. THE F
 RATING/ T RATING OF NOT LESS THAN 1 HOUR BUT LESS THAN
 THE REQUIRED RATING OF THE FLOOR PENETRATED.
  
 3) SHEET A-000 THE ACCESSIBILITY DETAIL SHEET. THIS
 SHEET HAS A DETAIL FOR LAVATORY CLEARANCES. IN THIS
 SAME DETAIL THERE IS A NOTE THAT (FOR MEDICINE
 CABINETS) THE LOWEST SHELF IS TO BE NO HIGHER THAN 44
 INCHES FROM THE FINISH FLOOR. PLEASE ALSO NOT FOR
 MEDICINE CABINETS WITH MIRROR FRONTS MUST MEET THE SAME
 REQUIREMENT AS FOR MIRRORS.
 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. 2017
 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-22 Cont ID  
Sent By jleahy Date 2020-08-22 Time 14:23 Rev Time 0.00
Received By jleahy Date 2020-08-22 Time 14:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-08-19 Cont ID  
Sent By pleduc Date 2020-08-19 Time   Rev Time 0.00
Received By pleduc Date 2020-08-19 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-09-09 Time 14:00 Rev Time 0.00
Received By lmarchan Date 2020-09-02 Time 16:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-01 Cont ID  
Sent By jwitmer Date 2020-09-01 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2020-08-18 Time 08:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-09-07 Cont ID  
Sent By medwards Date 2020-09-07 Time 08:33 Rev Time 0.00
Received By medwards Date 2020-09-07 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-08-19 Cont ID  
Sent By hmoser Date 2020-08-19 Time 14:55 Rev Time 0.00
Received By hmoser Date 2020-08-19 Time 13:34 Sent To  
Notes
2020-08-19 14:54:56REFER TO SECTION 606.2.1 IF AIR HANDLERS PRODUCE OVER
 2000 CFM DUCT DETECTOR IS REQUIRED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-03 Cont ID  
Sent By lcrespo Date 2020-09-03 Time 12:33 Rev Time 0.00
Received By lcrespo Date 2020-09-03 Time 12:04 Sent To  
Notes
2020-09-03 12:34:0509/03/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-20 Cont ID  
Sent By lcrespo Date 2020-08-20 Time 16:24 Rev Time 0.00
Received By lcrespo Date 2020-08-20 Time 15:03 Sent To  
Notes
2020-08-20 16:28:3208/20/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. SHEET A000 ACCESSIBILITY;
  
 A. UNDER FAC NOTES LETTER H TOILET PAPER DISPENSER
 VERBIAGE SHALL BE PER THE 2017 ACC 604.7.
  
 B. UNDER FAC NOTES LETTER N THE MIRROR SHALL BE 40" TO
 THE REFLECTIVE PART PER THE 2017 FBC ACC SEC. 603.3.
  
 C. IN DETAIL OF THE SECTION 606.3 THE MIRROR NEEDS TO
 BE NOTED TO THE REFLECTIVE PART OF IT PER THE 2017 FBC
 ACC SEC. 603.3.
  
 D. IN THAT SAME DETAIL THE NOTE FOR HOT WATER PIPING
 WRAP SHOULD BE REEFING 2017 FBC ACC SEC. 606.5.
  
 E. PLEASE DELETE ANY VERBIAGE OR DRAWINGS THAT DOES NOT
 REFLECT OF COINCIDE WITH THIS PROJECT ON ALL PLUMBING
 PAGES, I.E., DRINKING FOUNTAIN, KITCHEN SINK, URINAL,
 ETC., PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. SHEET A100 ACCESSIBILITY;
  
 A. IN CONSTRUCTION PLANS PLEASE SHOW ALL DIMENSIONS FOR
 ALL DETAIL OF CLEAR FLOOR SPACE LAV AND TOILET PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. PLEASE DELETE ANY VERBIAGE OR DRAWINGS THAT DOES NOT
 REFLECT OF COINCIDE WITH THIS PROJECT ON ALL PLUMBING
 PAGES PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. SHEET P-2 PLUMBING;
  
 A. PLEASE PROVIDE SPECIFICATIONS FOR INSTA-HOT FROM
 MANUFACTURE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. STOPS ON THE SINK DETAIL SHOWS ONLY ONE ANGLE STOP
 NOTED AS THREE WAY PLEASE SHOW INDIVIDUAL STOP FOR EACH
 FIXTURE PER THE 2017 FBC P 606.3.
  
 C. PLEASE DELETE ANY VERBIAGE OR DRAWINGS THAT DOES NOT
 REFLECT OF COINCIDE WITH THIS PROJECT ON ALL PLUMBING
 PAGES PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-07 Cont ID  
Sent By medwards Date 2020-09-07 Time 08:38 Rev Time 0.00
Received By medwards Date 2020-09-07 Time 08:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-01 Cont ID  
Sent By jwitmer Date 2020-09-01 Time 09:16 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***