| Plan Review Stops For Permit 20080693 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2020-11-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-11-05 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-11-05 |
Time |
14:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2020-11-03 |
|
|
Cont ID |
|
| Sent By |
jbrooks |
Date |
2020-11-03 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
jbrooks |
Date |
2020-11-03 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2020-11-03 12:15:56 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. PLEASE ADDRESS PREVIOUS COMMENTS DATED 10/27/2020. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
jbrooks |
Date |
2020-10-27 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
jbrooks |
Date |
2020-10-27 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2020-10-27 10:06:06 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION | | | OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL | | | INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL | | | SPREADSHEET): | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS?PAGE=2 | | | 2. FBC B 107.2.1. REVISE PLAN/ SCHEDULE TO SHOW OVERALL | | | DIMENSIONS OF DOOR OPENING #2. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-10-08 |
|
|
Cont ID |
|
| Sent By |
jbrooks |
Date |
2020-10-08 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
jbrooks |
Date |
2020-10-08 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2020-10-08 10:08:19 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL | | | FL23505-R2 IS INCOMPLETE, PROVIDE THE FOLLOWING | | | ADDITIONAL INFORMATION: COVER SHEET | | | (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE | | | VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL | | | INFORMATION ABOUT THE PRODUCT) EVALUATION REPORT. | | | PROVIDE A COMPLETE SET FOR THE PROPOSED SINGLE HUNG | | | WINDOWS USED. | | | 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF PRODUCT | | | APPROVALS/NOA'S FOR THE PROPOSED EXTERIOR DOORS TO BE | | | USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE | | | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. | | | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN | | | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. | | | SECOND REQUEST. | | | 3. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF PRODUCT | | | APPROVALS/NOA'S FOR THE PROPOSED MULLION BARS TO BE | | | USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE | | | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. | | | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN | | | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. | | | SECOND REQUEST. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-09-17 |
|
|
Cont ID |
|
| Sent By |
jbrooks |
Date |
2020-09-17 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
jbrooks |
Date |
2020-09-17 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2020-09-17 14:05:24 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3. PROVIDE TWO SETS OF PRODUCT | | | APPROVALS/NOA'S FOR THE PROPOSED WINDOWS TO BE USED. | | | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS | | | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT | | | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER | | | RULE 61G20-3 | | | 2. FBC R 301 FAC9N-3. PROVIDE TWO SETS OF PRODUCT | | | APPROVALS/NOA'S FOR THE PROPOSED DOORS TO BE USED. ALL | | | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS | | | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT | | | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER | | | RULE 61G20-3 | | | 3. FBC R 301 FAC9N-3. PROVIDE TWO SETS OF PRODUCT | | | APPROVALS/NOA'S FOR THE PROPOSED MULLION BARS TO BE | | | USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE | | | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. | | | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN | | | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. | | | AS PER RULE 61G20-3 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
P |
Date |
2020-11-04 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2020-11-04 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2020-11-04 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2020-11-04 15:32:48 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | | CONDITION(S): | | | 1. EXTERIOR WINDOW FRAME COLOR SHALL BE WHITE. | | | 2. ALL WINDOWS SHALL BE SIZED TO FIT THE ORIGINAL | | | OPENING FRAME (X-AXIS AND Y-AXIS) AND MATCH THE | | | DEPTH/PLACEMENT (Z-AXIS) OF THE ORIGINAL WINDOWS WITHIN | | | THE WINDOW FRAME OPENING. | | | 3. THE REPLACED MULLION SHALL MATCH THE EXISTING | | | MULLION'S WIDTH AND PLACEMENT. | | | 4. THE 6/6 WINDOWS SHALL HAVE AN EXTERNAL DIMENSIONAL | | | OGEE MUNITN PROFILE. | | | 5. THE EXISTING WOOD SASHES SHALL BE RECYCLED, DONATED, | | | OR STORED ON SITE TO PRESERVE AN IRREPARABLE HISTORIC | | | RESOURCE. | | | ADDITIONAL INFORMATION: | | | THE REPLACEMENT WINDOWS TOP SASH SHALL BE ROUGHLY | | | LOCATED IN THE SAME PLANE (Z-AXIS) AS THE EXISTING | | | ORIGINAL WOOD WINDOWS. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
F |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2020-10-27 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2020-10-27 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2020-10-27 10:35:03 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | | 1. REVISE FLOOR PLAN TO REFLECT DOUBLE-HUNG AND NOT | | | SINGLE-HUNG WINDOWS. | | | 2. PROVIDE GRAPHIC OF THE PROPOSED DOORS INCLUDING | | | COLOR. | | | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE. | | | 1. EXTERIOR WINDOW FRAME COLOR SHALL BE WHITE. | | | 2. ALL WINDOWS SHALL BE SIZED TO FIT THE ORIGINAL | | | OPENING FRAME (X-AXIS AND Y-AXIS) AND MATCH THE | | | DEPTH/PLACEMENT (Z-AXIS) OF THE ORIGINAL WINDOWS WITHIN | | | THE WINDOW FRAME OPENING. | | | 3. THE REPLACED MULLION SHALL MATCH THE EXISTING | | | MULLION'S WIDTH AND PLACEMENT. | | | | | | ADDITIONAL INFORMATION: | | | THE REPLACEMENT WINDOWS TOP SASH SHALL BE ROUGHLY | | | LOCATED IN THE SAME PLANE (Z-AXIS) AS THE EXISTING | | | ORIGINAL WOOD WINDOWS. | | | | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-10-08 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2020-10-08 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2020-10-08 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2020-10-08 12:39:06 | COMMENTS IN THE PREVIOUS RESUBMITTAL WERE NOT | | | ADDRESSED. | | | | | | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | | 1. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE | | | WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF | | | AT [email protected] TO REQUEST THE EXAMPLE. AT | | | MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND | | | THE PROPOSED WINDOWS EXTERIOR FRAME COLOR, GLASS | | | GLAZING, LITE PATTERN, MUNTIN PROFILE AND MULLION | | | WIDTH. A PHOTO OF EACH ELEVATION WITH EACH WINDOW | | | MARKED. | | | 2. PROVIDE A PHOTO OF THE EXISTING DOORS AND A GRAPHIC | | | OF THE PROPOSED DOORS. | | | 3. PROVIDE PRODUCT APPROVALS FOR ALL PRODUCTS. | | | 4. ENSURE THE SITE PLAN, WINDOW SCHEDULE, AND ALL OTHER | | | INFORMATION COMPLIES WITH HISTORIC PRESERVATION BOARD | | | CASE NO. 20-45. DECISION LETTER. PLEASE EMAIL STAFF AT | | | [email protected] IF A COPY OF THE DECISION LETTER IS | | | REQUIRED. | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-09-25 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2020-09-25 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2020-09-25 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2020-09-25 09:55:12 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | | 1. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE | | | WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF | | | AT [email protected] TO REQUEST THE EXAMPLE. AT | | | MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND | | | THE PROPOSED WINDOWS EXTERIOR FRAME COLOR, GLASS | | | GLAZING, LITE PATTERN, MUNTIN PROFILE AND MULLION | | | WIDTH. A PHOTO OF EACH ELEVATION WITH EACH WINDOW | | | MARKED. | | | 2. PROVIDE A PHOTO OF THE EXISTING DOORS AND A GRAPHIC | | | OF THE PROPOSED DOORS. | | | 3. PROVIDE PRODUCT APPROVALS FOR ALL PRODUCTS. | | | 4. ENSURE THE SITE PLAN, WINDOW SCHEDULE, AND ALL OTHER | | | INFORMATION COMPLIES WITH HISTORIC PRESERVATION BOARD | | | CASE NO. 20-45. DECISION LETTER. PLEASE EMAIL STAFF AT | | | [email protected] IF A COPY OF THE DECISION LETTER IS | | | REQUIRED. | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-11-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-11-05 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-11-02 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-10-27 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-10-21 |
Time |
07:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-10-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-16 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-06 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-09-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-09-25 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-09-15 |
Time |
14:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2020-09-17 |
|
|
Cont ID |
|
| Sent By |
jbrooks |
Date |
2020-09-17 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
jbrooks |
Date |
2020-09-17 |
Time |
13:32 |
Sent To |
|
|
| Notes |
|
|