| 2020-08-18 15:05:01 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20080653 2921 N AUSTRALIAN AVE |
| | |
| | A PLUMBING PERMIT IS REQUIRED |
| | RECORDS (SEE MASTER PERMIT 19070042) INDICATE THAT THE |
| | LAST RECORDED LOCATION OF AND TYPE OF WATER HEATER IS |
| | AN ELECTRIC TANK TYPE WATER HEATER LOCATED WELL INTO |
| | THE INTERIOR OF THE BUILDING. PER CONVERSATION WITH THE |
| | PERMIT APPLICANT, APPLICATION IS BEING MADE FOR PROPANE |
| | TANKS AND PIPING TO CONNECT TO GAS TANK-LESS WATER |
| | HEATER FURNISHED AND INSTALLED BY OTHERS ON THE |
| | EXTERIOR OF THE BUILDING. THERE DOES NOT APPEAR TO BE A |
| | PLUMBING PERMIT APPLIED FOR THIS. PER WPB FBC 105.1, A |
| | PLUMBING PERMIT IS REQUIRED FOR THE PIPING AND |
| | INSTALLATION OF THE NEW GAS TANK-LESS WATER HEATER. |
| | PROVIDE PAN VIEW AND RISER DIAGRAM AS WELL AS |
| | MANUFACTURER?S SPECIFICATION/INSTALLATION MANUAL AS |
| | REQUIRED IN ACCORDANCE WITH WPB FBC 107.2.1 AND |
| | 107.3.5.1.3. |
| | |
| | |
| | GAS COMMENTS: DENIED |
| | 1. TABLE PROVIDED 402.4(35) IS FOR PE AT 11 INCH WC AND |
| | THERE DOES NOT APPEAR TO BE ANY PIPING IN THE SYSTEM |
| | THAT MEETS THAT CRITERIA.PER WPB FBC 107.2.1, PROVIDE |
| | THE FOLLOWNG: |
| | A. MANUFACTURER?S DATA/TABLE FOR 10 PSI PE PIPING (NONE |
| | SHOWN IN FBC FG OR NFPA 54) |
| | B. TABLE FOR 10 PSI GALVANIZED PIPING |
| | C. TABLE FOR GALVANIZED PIPING AT 11 INCH WC |
| | |
| | 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR TANKLESS WATER HEATER TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG |
| | 402.2 AND 301.3. GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | 3. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER FGC FG 410.1. |
| | 4. ABOVE GROUND TANK ENGINEERING ANCHOR SPEC DOCUMENT |
| | SHALL BEAR FLORIDA PE SIGNED STAMP/SEAL. |
| | 5. ANCHOR SPECS FOR STORAGE SHED DO NOT REFLECT TANK |
| | TIE DOWN. PER WPB FBC 107.2.1, CLARIFY. |
| | 6. PER FBC FG 407.17.3, A YELLOW INSULATED COPPER |
| | TRACER WIRE OR OTHER APPROVED CONDUCTOR SHALL BE |
| | INSTALLED ADJACENT TO UNDERGROUND NONMETALLIC PIPING. |
| | ACCESS SHALL BE PROVIDED TO THE TRACER WIRE OR THE |
| | TRACER WIRE SHALL TERMINATE ABOVE GROUND AT EACH END OF |
| | THE NONMETALLIC PIPING. THE TRACER WIRE SIZE SHALL BE |
| | NOT LESS THAN 18 AWG AND THE INSULATION TYPE SHALL BE |
| | SUITABLE FOR DIRECT BURIAL. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20080653 2921 N AUSTRALIAN AVE |
| | |