Plan Review Details - Permit 20080647
Plan Review Stops For Permit 20080647
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-29 Cont ID  
Sent By cthroop Date 2021-01-29 Time 16:47 Rev Time 0.00
Received By cthroop Date 2021-01-29 Time 16:47 Sent To  
Notes
2021-01-29 16:47:42APPROVED BY SHILL ON 9/1/2020. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-13 Cont ID  
Sent By rmcphers Date 2021-01-13 Time 09:58 Rev Time 0.00
Received By rmcphers Date 2021-01-13 Time 09:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 07:33 Rev Time 0.00
Received By shill Date 2020-09-12 Time 07:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-29 Cont ID  
Sent By cthroop Date 2021-01-29 Time 16:47 Rev Time 0.00
Received By cthroop Date 2021-01-19 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-13 Cont ID  
Sent By rmcphers Date 2021-01-13 Time 09:59 Rev Time 0.00
Received By rmcphers Date 2020-12-18 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-16 Cont ID  
Sent By ccarvaja Date 2020-09-16 Time 15:57 Rev Time 0.00
Received By ccarvaja Date 2020-08-14 Time 13:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-29 Cont ID  
Sent By cthroop Date 2021-01-29 Time 16:47 Rev Time 0.00
Received By cthroop Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-13 Cont ID  
Sent By rmcphers Date 2021-01-13 Time 09:59 Rev Time 0.00
Received By rmcphers Date 2021-01-13 Time 09:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 06:58 Rev Time 0.00
Received By shill Date 2020-09-12 Time 06:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-01-27 Cont ID  
Sent By eschneid Date 2021-01-27 Time 13:07 Rev Time 0.25
Received By eschneid Date 2021-01-26 Time 14:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-01-07 Cont ID  
Sent By eschneid Date 2021-01-07 Time 14:55 Rev Time 0.25
Received By eschneid Date 2021-01-07 Time 14:59 Sent To  
Notes
2021-01-07 15:08:58FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE ROSEMARY SQUARE MASTER SIGN PLAN REQUIRES THAT
 THE TRELLIS (FALLS UNDER THE CANOPY DEFINITION)
 REQUIRES A MINIMUM VERTICAL CLEARANCE OF 10 FEET FROM
 THE SIDEWALK ELEVATION. WHILE THE ISOMETRIC PLAN AND
 THE ELEVATION PLAN WERE UPDATED TO SHOW COMPLIANCE, THE
 UPDATED SECTION VIEW WAS NOT PROVIDED.
  
 2) THE UPDATED SECTION VIEW VERIFYING THAT THE
 ELECTRICAL SUPPLY IS LOCATED WITHIN THE TRELLIS WAS NOT
 PROVIDED (SHEET AOH 6).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By eschneid Date 2020-09-16 Time 14:12 Rev Time 0.25
Received By eschneid Date 2020-09-16 Time 14:12 Sent To  
Notes
2020-09-16 14:16:42FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE PLANS ARE REQUIRED TO HAVE EITHER THE CITYPLACE
 MANAGEMENT APPROVAL STAMP OR A LETTER WITH THE STAMP
 THAT CLEARLY LISTS THE PLANS THAT ARE APPROVED AS PART
 OF THE PERMIT SUBMITTAL.
  
 2) THE ROSEMARY SQUARE MASTER SIGN PLAN REQUIRES THAT
 THE TRELLIS (FALLS UNDER THE CANOPY DEFINITION)
 REQUIRES A MINIMUM VERTICAL CLEARANCE OF 10 FEET FROM
 THE SIDEWALK ELEVATION. THE ISOMETRIC PLAN, THE PLAN
 AND SECTION VIEW, AND THE ELEVATION VIEW LISTS THE
 HEIGHT AS A MINIMUM OF 7.5 FEET. THE EXACT HEIGHT FROM
 GRADE NEEDS TO BE PROVIDED. THE ROSEMARY SQUARE MASTER
 SIGN PLAN DOES NOT PROVIDE FOR A WAIVER OF THIS
 REQUIREMENT.
  
 3) THE ROSEMARY SQUARE MASTER SIGN PLAN REQUIRES THAT
 THE TRELLIS REQUIRES A MINIMUM HORIZONTAL PROJECTION OF
 EIGHT (8) FEET FROM THE FACE OF THE BUILDING. THE PLANS
 SHOW THE TRELLIS ONLY PROJECTING FROM THE WALL FOUR (4)
 FEET. THE ROSEMARY SQUARE MASTER SIGN PLAN PERMITS A
 HORIZONTAL PROJECTION OF BETWEEN 4 AND 8 FEET ONLY IF
 CITYPLACE MANAGEMENT HAS GRANTED A WAIVER I. A WAIVER I
 REQUIRES THE SUBMITTAL OF A LETTER FROM CITYPLACE
 MANAGEMENT ALLOWING THE 4 FOOT HORIZONTAL PROJECTION
 WITH THE BUILDING PERMIT.
  
 4) NOTE: STAFF HAS SEEN A SIGN PERMIT FOR A SIGN THAT
 IS PROPOSED TO BE MOUNTED TO THE TRELLIS WHICH INCLUDES
 ELECTRIC FOR ILLUMINATION OF THE SIGN. THE ROSEMARY
 SQUARE MASTER SIGN PLAN REQUIRES THAT ALL CONDUIT,
 RACEWAYS, CROSSOVERS, WIRING, AND OTHER EQUIPMENT
 NECESSARY FOR THE SIGN'S ELECTRICAL CONNECTION SHALL BE
 CONCEALED AND NOT VISIBLE TO THE PUBLIC. THE DESIGN OF
 THIS TRELLIS DOES NOT ALLOW FOR THE INSTALLATION OF
 ELECTRICAL CONNECTIONS THAT ARE NOT VISIBLE TO THE
 PUBLIC.
  
 5) THE TRELLIS SHOWN AS PART OF THIS PERMIT HAS ALREADY
 BEEN INSTALLED SO A 4 TIMES THE FEE FOR WORK WITHOUT A
 PERMIT HAS BEEN ADDED TO THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]