Plan Review Details - Permit 20080535
Plan Review Stops For Permit 20080535
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By jleahy Date 2020-09-15 Time 09:34 Rev Time 0.00
Received By jleahy Date 2020-09-15 Time 09:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-02 Cont ID  
Sent By jleahy Date 2020-09-02 Time 08:00 Rev Time 0.00
Received By jleahy Date 2020-09-02 Time 08:00 Sent To  
Notes
2020-09-02 08:06:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 SHOW HOW TERMINATIONS FOR THE 2/0 MEETS THE
 REQUIREMENTS ON 110.14(C)(1)(B) , A 2/0 AT 75 DEGREES
 IS ONLY GOOD FOR 175 AND CAN NOT BE PROTECTED BY A 200A
 FUSE OR BREAKER.
  
 110.14(C)(1)(B) TERMINATION PROVISIONS OF EQUIPMENT FOR
 CIRCUITS RATED OVER 100 AMPERES, OR MARKED FOR
 CONDUCTORS LARGER THAN 1 AWG, SHALL BE USED ONLY FOR
 ONE OF THE FOLLOWING: (1) CONDUCTORS RATED 75?C (167?F)
 (2) CONDUCTORS WITH HIGHER TEMPERATURE RATINGS,
 PROVIDED THE AMPACITY OF SUCH CONDUCTORS DOES NOT
 EXCEED THE 75?C (167?F) AMPACITY OF THE CONDUCTOR SIZE
 USED, OR UP TO THEIR AMPACITY IF THE EQUIPMENT IS
 LISTED AND IDENTIFIED FOR USE WITH SUCH CONDUCTORS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-15 Cont ID  
Sent By jleahy Date 2020-09-15 Time 09:34 Rev Time 0.00
Received By jleahy Date 2020-09-09 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-02 Cont ID  
Sent By jleahy Date 2020-09-02 Time 08:06 Rev Time 0.00
Received By jleahy Date 2020-08-20 Time 15:53 Sent To  
Notes
2020-09-01 18:04:13PLANS NOT VERSIONED, MASTER PERMIT ISSUED AS PAPER
2020-08-20 15:53:34ROUTED TO ELECTRICAL BIN

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By jleahy Date 2020-09-15 Time 09:34 Rev Time 0.00
Received By jleahy Date 2020-09-15 Time 09:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-08 Cont ID  
Sent By jgomez Date 2020-09-08 Time 10:40 Rev Time 0.00
Received By jgomez Date 2020-09-08 Time 10:32 Sent To  
Notes
2020-09-08 11:01:49REVISION WAS CONVERTED TO DIGITAL. ORIGINAL PLAN WITH
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE WAS UPLOADED TO
 PROJECTDOX ON 09/01/2020. BASED ON ON THE ELECTRICAL
 REVIEWER COMMENTS. PLANS WILL NEED TO BE REVISED.
 REVISED PLAN MAY BE RESUBMITTED WITH ENGINEER'S
 ORIGINAL SEAL/SIGNATURE OR PREFERABLY WITH ENGINEER'S
 DIGITAL SIGNATURE VIA PROJECTDOX. JG.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  