Plan Review Details - Permit 20080531
| Plan Review Stops For Permit 20080531 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-10-01 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2020-10-01 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2020-10-01 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2020-10-01 09:52:18 | NO ELECTRICAL TO REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2020-08-21 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2020-08-21 |
Time |
09:03 |
Sent To |
M |
|
| Notes |
| 2020-08-21 09:08:46 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A | | | DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL | | | CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-10-01 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2020-10-01 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2020-09-29 |
Time |
06:11 |
Sent To |
|
|
| Notes |
| 2020-09-29 06:11:48 | ROUTED TO MECHANICAL INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-08-21 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-08-21 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-08-20 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2020-08-20 15:34:47 | ROUTED TO MECHANICAL BIN |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-09-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-09-29 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-09-29 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2020-09-29 14:19:07 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | MECHANICAL REVIEW DENIED: | | | | | | FBC R M 1401.4, PLEASE PROVIDE THE SIGNED/SEALED | | | ENGINEER APPROVED TIE-DOWN DETAILS FOR BOTH EXTERIOR | | | CONDENSING UNITS. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-08-21 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-08-21 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2020-08-21 14:44:11 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | 1) FBC B & WPB AMENDMENTS 107.2.1, PROVIDE, ON NEW | | | PLANS FOR PROPOSED WORK, THE SIGNATURES OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. WHEN THE PERSON RESPONSIBLE | | | FOR THE SUBMITTED DRAWINGS IS A DESIGN PROFESSIONAL | | | THAT PERSON NEEDS TO PROVIDE SIGNATURES AND SEALS AS | | | PER F.S. 471 AMD 481. | | | 2) FBC R M 1401.4, PROVIDE SIGNED AND SEALED ENGINEER | | | APPROVED TIE DOWN DETAILS FOR BOTH EXTERIOR CONDENSING | | | UNITS. | | | 3) FBC B 107, PROVIDE THE MANUFACTURER'S SPECIFICATIONS | | | FOR ALL NEW UNITS INCLUDING THE MINI-SPLITS WITH (3) | | | AIR HANDLERS AND (1) CONDENSING UNIT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-09-30 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-09-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2020-09-30 |
Time |
|
Sent To |
I |
|
| Notes |
| 2020-09-30 13:48:44 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 9/30/2020 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PLEASE PROVIDE A COMPLETE SURVEY OF THE PROPERTY | | | INDICATING THE SETBACKS OF ALL EXTERIOR EQUIPMENT TO | | | THE PROPERTY LINES. PURSUANT THE CITY OF WEST PALM | | | BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), | | | SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | | [email protected] AND REQUEST TO HAVE YOUR | | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | | ARE FINISHED UPLOADING. | | | | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | TTY: 800.955.8771 | | | E: [email protected] | | | W: WPB.ORG | | | |
|
|
|