Plan Review Details - Permit 20080481
Plan Review Stops For Permit 20080481
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-30 Cont ID  
Sent By jgomez Date 2020-11-30 Time 11:03 Rev Time 0.00
Received By jgomez Date 2020-11-30 Time 09:40 Sent To  
Notes
2020-11-30 11:04:16BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE AND SPECIFY FASTENING. IF USING SCREWS,
 SPECIFY SIZE & NUMBER.
 B)ROOF TILE ADHESIVE IF SPECIFIED ABOVE.
 C)FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED. NOTE: RAS
 117 CALCULATIONS IF REQUIRED.
 D)ENTRY DOOR.
 E)LAUNDRY DOOR.
 F)SLIDING GLASS DOORS.
 G)FIXED WINDOWS.
 H)HORIZONTAL SLIDING WINDOWS.
 I)CASEMENT WINDOWS.
 I)OVERHEAD GARAGE DOOR.
  
 2 DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By jgomez Date 2020-09-21 Time 17:58 Rev Time 0.00
Received By jgomez Date 2020-09-21 Time 10:19 Sent To  
Notes
2020-09-21 17:59:47RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 IMPORTANT:
 THE ENERGY CALCULATIONS NEED TO BE SIGNED BY THE OWNER,
 ARCHITECT OR LEGALLY DESIGNATED AGENT PRIOR TO RECEIVE
 THE PERMIT. SEE ITEM #5(A) BELOW.
  
  
 1- ALL THE ARCHITECTURAL WALL SECTIONS SHOW R30 BATT
 INSULATION IN THE CEILING AREA. ARCHITECTURAL AND
 STRUCTURAL PLANS SHOW THAT THE CEILING INSULATION WILL
 BE FIT BETWEEN THE 2X6 PURLINS. R30 BATT INSULATION
 DOESN'T FIT IN THE SPACE PROVIDED BY THE 2X6 PURLINS.
 R30 BAT INSULATION IS 9-1/2" THICK +/-. NEED TO REVISE
 AS REQUIRED.
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE AND SPECIFY FASTENING. IF SPECIFYING ROOF
 TILE ADHESIVE, THEN PROVIDE PRODUCT APPROVAL. IF
 SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER
 OF SCREWS.
  
 B)ROOF TILE ADHESIVE. SEE ROOF TILE NOA SUBMITTED FOR
 LISTED ADHESIVES. AND CLEARLY MARK PADDY SIZE AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
  
 C)FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 D)ENTRY DOOR.
 E)LAUNDRY DOOR.
 F)SLIDING GLASS DOORS.
 G)FIXED WINDOWS.
 H)HORIZONTAL SLIDING WINDOWS.
 I)CASEMENT WINDOWS.
 I)OVERHEAD GARAGE DOOR.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4-FRAMED GABLE ENDS:
 A)NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS
 REQUIRED BY TABLE R702.1(1) FBC-RESIDENTIAL
  
 B) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL ON THE
 WOOD FRAMED WALL.
  
 5- ENERGY CALCULATIONS:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
  
 B)REVISE THE DESIGN LOCATION SPECIFIED ON TOP OF FORM
 SUBMITTED. THIS IS CITY OF WEST PALM BEACH NOT MIAMI.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE CORRECT ZIP CODE FOR THIS ADDRESS IS 33405
 NOT 33145. ALSO, REVISE THE DESIGN LOCATION. THIS IS
 CITY OF WEST PALM BEACH NOT MIAMI. ALSO, PROVIDE THE
 BUILDER NAME, PERMIT OFFICE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 D)ITEM #8A ON PAGE 1 OF 5 SPECIFIES R3 SLAB ON GRADE
 EDGE INSULATION. PLANS DON'T SPECIFY ANY SLAB EDGE
 INSULATION. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E)INFORMATION AND INSULATION SPECIFIED ON ITEMS #9A,
 #9B AND #9C DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 THERE IS NOT CONCRETE BLOCK EXTERIOR INSULATION AND
 THERE IS NOT FACE BRICK. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 F)CEILING INFORMATION ON ITEM #10 NEEDS TO BE
 COORDINATED WITH THE REVISED ARCHITECTURAL PLANS. SEE
 ITEM #1 ABOVE. COORDINATE WITH ARCHITECT TO AVOID
 CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 G)REVISE CLIMATE INFORMATION ON PAGE 2 OF 5. DESIGN
 LOCATION IS WEST PALM BEACH NOT MIAMI. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)REVISE ROOF TYPE ON PAGE 2 OF 5. PLANS DON'T SPECIFY
 SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)REVISE DOORS INFORMATION ON PAGE 3 OF 5. PLANS DON'T
 SPECIFY WOOD DOORS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 J)REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-01 Cont ID  
Sent By cthroop Date 2020-09-01 Time 15:34 Rev Time 0.00
Received By cthroop Date 2020-09-01 Time 13:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By lcrespo Date 2020-11-16 Time 14:00 Rev Time 0.00
Received By lcrespo Date 2020-11-16 Time 14:00 Sent To  
Notes
2020-11-16 14:01:1511/16/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-08-26 Cont ID  
Sent By lcrespo Date 2020-08-26 Time 17:21 Rev Time 0.00
Received By lcrespo Date 2020-08-26 Time 17:21 Sent To  
Notes
2020-08-26 17:38:4108/26/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER
 2017 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, FOR EACH PIPE SIZE ON ISOMETRIC PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. MOST TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND
 THE SERVICE METER DISCHARGES IS A 2 PSI REQUIRING A
 REGULATOR FOR THIS UNIT AS PER MANUFACTURER'S
 SPECIFICATION. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR STOVE PER
 THE FBC RES. SEC. G2407.1 AND G2439.4
  
 6. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR STOVE AND TANKLESS
 HEATER EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC
 RES. SEC. G2408.1.
  
 7. PLEASE LABEL AND SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC
 G2421.2 OR 2017 FBC FG SEC 410.2.
  
 8. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 9. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT
 INSTALLED PER THE 2017 FBC RES. SEC. G2419.
  
 10. IF THIS UNIT REQUIRES CONDENSATE IT MUST BE 1' AWAY
 FROM STRUCTURE PER THE 2017 FBC SEC R318.5.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-30 Cont ID  
Sent By jgomez Date 2020-11-30 Time 11:05 Rev Time 0.00
Received By jgomez Date 2020-11-13 Time 11:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-21 Cont ID  
Sent By jgomez Date 2020-09-21 Time 18:06 Rev Time 0.00
Received By jgomez Date 2020-08-17 Time 08:25 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-12-29 Cont ID  
Sent By lmarchan Date 2020-12-29 Time 09:24 Rev Time 0.00
Received By lmarchan Date 2020-12-03 Time 10:28 Sent To  
Notes
2020-12-29 09:24:05RECEIPT MU-2020-47470 - $2430.79 - PAID
2020-12-03 10:28:4812/3/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By jgomez Date 2020-09-21 Time 18:01 Rev Time 0.00
Received By jgomez Date 2020-09-21 Time 17:59 Sent To  
Notes
2020-09-21 18:01:13IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-11-18 Cont ID  
Sent By medwards Date 2020-11-18 Time 11:01 Rev Time 0.00
Received By medwards Date 2020-11-18 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-08-20 Cont ID  
Sent By hmoser Date 2020-08-20 Time 14:40 Rev Time 0.00
Received By hmoser Date 2020-08-20 Time 14:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By lcrespo Date 2020-11-16 Time 14:00 Rev Time 0.00
Received By lcrespo Date 2020-11-16 Time 13:43 Sent To  
Notes
2020-11-16 14:01:3811/16/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-26 Cont ID  
Sent By lcrespo Date 2020-08-26 Time 17:19 Rev Time 0.00
Received By lcrespo Date 2020-08-26 Time 17:19 Sent To  
Notes
2020-08-26 17:19:5708/26/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. ON SHEET 300 PLEASE SHOW BOTH CLEANOUTS ON ISOMETRIC
 DRAWING PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. WATER RUNNING UNDER SLAB MUST BE INSULATED WITH AN
 R-3 PER 2017 FBC SEC. RE 403.5.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2020-11-30 Cont ID  
Sent By jgomez Date 2020-11-30 Time 11:04 Rev Time 0.00
Received By jgomez Date 2020-11-30 Time 11:04 Sent To  
Notes
2020-11-30 11:05:22REVIEW APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE AND SPECIFY FASTENING. IF USING SCREWS,
 SPECIFY SIZE & NUMBER.
 B)ROOF TILE ADHESIVE IF SPECIFIED ABOVE.
 C)FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED. NOTE: RAS
 117 CALCULATIONS IF REQUIRED.
  
 2 DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By jgomez Date 2020-09-21 Time 18:01 Rev Time 0.00
Received By jgomez Date 2020-09-21 Time 18:01 Sent To  
Notes
2020-09-21 18:02:411-- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE AND SPECIFY FASTENING. IF SPECIFYING ROOF
 TILE ADHESIVE, THEN PROVIDE PRODUCT APPROVAL. IF
 SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER
 OF SCREWS.
  
 B)ROOF TILE ADHESIVE. SEE ROOF TILE NOA SUBMITTED FOR
 LISTED ADHESIVES. AND CLEARLY MARK PADDY SIZE AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
  
 C)FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-18 Cont ID  
Sent By medwards Date 2020-11-18 Time 11:05 Rev Time 0.00
Received By medwards Date 2020-11-18 Time 11:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-21 Cont ID  
Sent By jgomez Date 2020-09-21 Time 18:02 Rev Time 0.00
Received By jgomez Date 2020-09-21 Time 18:02 Sent To  
Notes
2020-09-21 18:06:34STRUCTURAL ENGINEER SIGNATURE VALIDATED. JG.
2020-09-01 15:26:16DIGITAL SIGNATURE OF PE ON ELECTRICAL PLANS VALIDATED.
 CT

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-23 Cont ID  
Sent By rthermid Date 2020-11-23 Time   Rev Time 0.00
Received By rthermid Date 2020-11-23 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-21 Cont ID  
Sent By rthermid Date 2020-08-21 Time   Rev Time  
Received By rthermid Date 2020-08-21 Time   Sent To I
Notes
***NONE***