Plan Review Details - Permit 20080457
Plan Review Stops For Permit 20080457
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 13:43 Rev Time 0.00
Received By shill Date 2020-09-12 Time 13:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-31 Cont ID  
Sent By cthroop Date 2020-08-31 Time 06:49 Rev Time 0.00
Received By cthroop Date 2020-08-31 Time 06:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-09-29 Cont ID  
Sent By ccole Date 2020-09-29 Time 07:47 Rev Time 0.00
Received By ccole Date 2020-09-29 Time 07:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-09-23 Cont ID  
Sent By ccole Date 2020-09-23 Time 08:40 Rev Time 0.00
Received By ccole Date 2020-09-23 Time 06:54 Sent To  
Notes
2020-09-23 08:44:303RD REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20080457
 9/23/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
 COMMENTS LISTED BELOW FROM THE PREVIOUS REVIEW ARE
 MARKED AS PASSED OR FAILED. COMMENT NOTES IN CAP
 LETTERS HAVE BEEN ADDED FOR FAILED COMMENTS.
  
 1) GAS RISER:
  
 A) FAILED. TOTAL DEVELOPED LENGTH OF THE SYSTEM NOT
 SHOWN- SECTION G2413.4.(1) FBC RES. THE 1-IN. SCHEDULE
 40 PIPE SUPPLYING 785,000 BTUH IS UNDERSIZED PER TABLE
 G2413.1(4) FBC RES. BECAUSE THE 1-IN. PIPE IS THE MAIN
 PIPE SUPPLYING THE ENTIRE SYSTEM, THE TOTAL DEVELOPED
 LENGTH FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 APPLIANCE SHALL BE PROVIDED WHETHER IT IS A NEW
 APPLIANCE, OR AN EXISTING APPLIANCE ON AN EXISTING
 BRANCH LINE. PLEASE NOTE THAT PIPE SIZING FOR
 RESIDENTIAL SYSTEMS SHALL BE IN ACCORDANCE WITH SECTION
 G2413.3(402.3) SIZING FBC RES.
 GAS PIPING SHALL BE SIZED IN ACCORDANCE WITH ONE OF THE
 FOLLOWING:
 1. 1.PIPE SIZING TABLES OR SIZING EQUATIONS IN
 ACCORDANCE WITH SECTION G2413.4.
 2. 2.THE SIZING TABLES INCLUDED IN A LISTED PIPING
 SYSTEM'S MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 3. 3.OTHER APPROVED ENGINEERING METHOD
  
 B) FAILED. TOTAL BRANCH LENGTHS TO GENERATOR, EXISTING
 INTERIOR APPLIANCES, AND EXTERIOR POOL HEATER NOT
 SHOWN- SECTION G2413.4.2. SEE COMMENT #1 REMARKS ABOVE.
  
 C) FAILED. TYPES AND SIZES OF BRANCH PIPING NOT SHOWN-
 SECTION G2413.3. NOT PROVIDED- SEE COMMENT #1 REMARKS.
  
 D) FAILED. PIPE SIZING TABLES NOT PROVIDED- TABLES
 G2413.4(1)- G2413.4(8). NOT PROVIDED- SEE COMMENT #1
 REMARKS. PLEASE NOTE THAT NFPA 54 IS NOT A REFERENCED
 STANDARD IN THE FBC RES.-17 CODE. REFER TO GAS PIPE
 SIZING METHODS LISTED UNDER COMMENT #1 ABOVE. TABLE
 G2413.4(1) IS THE EQUIVALENT SCHED. 40 METALLIC PIPE
 SIZING TABLE FOR SUBMITTED TABLE 6.2)B) FROM NFPA 54.
 YOU HAVE MARKED UP THE TABLE TO INDICATE A 2-IN.
 MANIFOLD PIPE AT THE METER HOWEVER THE RISER DRAWING
 DOES NOT SHOW THAT. PLEASE LIOST ALL PIPE SIZING TABLES
 ON THE DRAWING AS PREVIOUSLY REQUESTED.
  
 E) PASSED. THE NOTE SHOWING NEW 1.25 PE GAS LINE TO
 GENERATOR NOTE CONFLICTS WITH THE DRAWING THAT SHOWS
 METALLIC PIPING RUN SHOWN TO GENERATOR- SECTION 107.2.1
 WPB.
  
 F) FAILED. ESTIMATED LOAD A TO B INDICATES 1.25 IN PIPE
 REQUIRED, BUT 1 IN. IS SHOWN ON DRAWING- 107.2.1 WPB.
 NO CHANGES MADE TO THE DRAWING.
  
 G) FAILED ESTIMATED LOAD B TO C NOT SHOWN AND ESTIMATED
 LOAD C TO D APPEARS TO BE MISLABELED- THERE IS NO D ON
 DRAWING- 107.2.1. LOCATION OF D NOT PROVIDED.
  
 H) FAILED. INDICATE HOW THE PE PIPING RISER WILL
 CONNECT TO THE SCHEDULE 40 METALLIC PIPE PER SECTIONS
 G2415.17.1 & G2415.17.2 FBC RES. PLEASE NOTE THAT SPECS
 FOR ANODELESS RISERS AND PE/METALLIC PIPE CONNECTORS
 SHALL BE LISTED AND LABELED AND SHALL BE ONSITE AT TIME
 OF INSPECTION. NOT PROVIDED, HOWEVER DEFERRED
 SUBMITTALS ARE ACCEPTABLE.
  
 I) FAILED. PROVIDE THE MAKE AND MODEL NUMBER OF THE
 REGULATOR, AND SHOW THE REQUIRED PIPE UNION LOCATIONS
 AT EACH SIDE OF THE REGULATOR SECTION G2421.2. NOT
 PROVIDED, HOWEVER DEFERRED SUBMITTALS ARE ACCEPTABLE.
  
 2) PASSED. REVISE THE MARKED-UP SURVEY TO SHOW THE UG
 PE RUN- SECTION 107.2.1 WPB. PLEASE NOTE THE GENERATOR
 SHALL BE INSTALLED A MINIMUM OF 5 FT. FROM COMBUSTIBLE
 WALLS. THE 18 IN. CLEARANCE DISTANCE SHALL BE PERMITTED
 IF THE HOUSE WALL HAS A 1-HR. FIRE RESISTANCE RATING,
 OR THE GENERATOR HAS A WEATHERPROOF ENCLOSURE
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE ENCLOSURE WILL
 NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE OF THE
 ENCLOSURE- SECTION 4.1.4 NFPA 37. THE SUBMITTED GENERIC
 GUIDELINES INDICATE LOCAL CODES TAKE PRECEDENCE. PLEASE
 ADD THE REQUIRED 10 FT. CLEARANCE FROM THE GENERATOR TO
 MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND DOOR
 OPENINGS) INTO THE BUILDING PER SECTION R303.5.1 FBC
 RES.
  
 3) FAILED THE SIGNATURE OF FL. LICENSED GAS CONTRACTOR
 AND LICENSE NUMBER SHALL BE ON THE GAS RISER DRAWING
 PER SECTION 107.2.1 WPB, AND FL. STATURES 471.003 &
 471.025. THE DIGITAL SIGNATURE ON THE PLAN DOES NOT
 INCLUDE FUEL GAS LICENSING INFORMATION- SECTION 107.2.1
 WPB, AND FL. STATUTES 471.993 & 471.025.
  
 PLEASE NOTE THAT THIS IS THE 3RD FAILED REVIEW OF THE
 PLANS. PLEASE CONTACT ME AT YOUR EARLIEST CONVENIENCE
 TO DISCUSS THE COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-09-17 Cont ID  
Sent By ccole Date 2020-09-17 Time 16:47 Rev Time 0.00
Received By ccole Date 2020-09-17 Time 12:01 Sent To  
Notes
2020-09-17 16:47:561ST REVIEW FBC-2017 RES.
 PERMIT- 20080457
 9/10/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER:
 A) TOTAL DEVELOPED LENGTH OF THE SYSTEM NOT SHOWN-
 SECTION G2413.4.1 FBC RES.
 B) TOTAL BRANCH LENGTHS TO GENERATOR, EXISTING INTERIOR
 APPLIANCES, AND EXTERIOR POOL HEATER NOT SHOWN- SECTION
 G2413.4.2
 C) TYPES AND SIZES OF BRANCH PIPING NOT SHOWN- SECTION
 G2413.3.
 D) PIPE SIZING TABLES NOT PROVIDED- TABLES G2413.4(1)-
 G2413.4(8).
 E) THE NOTE SHOWING NEW 1.25 PE GAS LINE TO GENERATOR
 NOTE CONFLICTS WITH THE DRAWING THAT SHOWS METALLIC
 PIPING RUN SHOWN TO GENERATOR- SECTION 107.2.1 WPB
 F) ESTIMATED LOAD A TO B INDICATES 1.25 IN PIPE
 REQUIRED, BUT 1 IN. IS SHOWN ON DRAWING- 107.2.1.
 G) ESTIMATED LOAD B TO C NOT SHOWN AND ESTIMATED LOAD C
 TO D APPEARS TO BE MISLABELED- THERE IS NO D ON
 DRAWING- 107.2.1.
 H) INDICATE HOW THE PE PIPING RISER WILL CONNECT TO THE
 SCHEDULE 40 METALLIC PIPE PER SECTIONS G2415.17.1 &
 G2415.17.2 FBC RES. PLEASE NOTE THAT SPECS FOR
 ANODELESS RISERS AND PE/METALLIC PIPE CONNECTORS SHALL
 BE LISTED AND LABELED AND SHALL BE ONSITE ART TIME OF
 INSPECTION
 I) PROVIDE THE MAKE AND MODEL NUMBER OF THE REGULATOR,
 AND SHOW THE REQUIRED PIPE UNION LOCATIONS AT EACH SIDE
 OF THE REGULATOR SECTION G2421.2.
  
 2) REVISE THE MARKED-UP SURVEY TO SHOW THE UG PE RUN-
 SECTION 107.2.1 WPB. PLEASE NOTE THE GENERATOR SHALL BE
 INSTALLED A MINIMUM OF 5 FT. FROM COMBUSTIBLE WALLS.
 THE 18 IN. CLEARANCE DISTANCE SHALL BE PERMITTED IF THE
 HOUSE WALL HAS A 1-HR. FIRE RESISTANCE RATING, OR THE
 GENERATOR HAS A WEATHERPROOF ENCLOSURE CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE OF THE ENCLOSURE- SECTION
 4.1.4 NFPA 37. THE SUBMITTED GENERIC GUIDELINES
 INDICATE LOCAL CODES TAKE PRECEDENCE.
  
 3) THE SIGNATURE OF FL. LICENSED GAS CONTRACTOR AND
 LICENSE NUMBER SHALL BE ON THE GAS RISER DRAWING PER
 SECTION 107.2.1 WPB, AND FL. STATURES 471.003 &
 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-09-10 Cont ID  
Sent By ccole Date 2020-09-10 Time 10:44 Rev Time 0.00
Received By ccole Date 2020-09-10 Time 09:29 Sent To  
Notes
2020-09-10 10:45:491ST REVIEW FBC-2017 RES.
 PERMIT- 20080457
 9/10/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS ISOMETRIC DRAWING PER SECTION
 107.3.5.3 WPB, AND SECTIONS G2413.4.1 & G2413.4.2 FBC
 RES. BECAUSE A 310,000 BTUH GENERATOR IS BEING ADDED TO
 AN EXISTING GAS PIPING SYSTEM, IN ORDER TO ENSURE A
 SAFE OPERATING SYSTEM, THE ISOMETRIC SHALL BE A
 COMPLETE REPRESENTATION OF THE NEW AND EXISTING GAS
 PIPING SYSTEM INCLUDING ALL PIPING RUNS TO EXISTING GAS
 APPLIANCES INSTALLED UNDER PERMIT #05061739- POOL
 HEATER, BBQ, COOKTOP, WATER HEATER, DRYER; AND ANY
 OTHER APPLIANCES CURRENTLY INSTALLED AT THE RESIDENCE-
 SECTIONS G2412.3 & G2412.4 FBC RES. THE DRAWING SHALL
 SHOW THE TYPES AND SIZES OF PIPING, LONGEST RUN LENGTH
 FROM THE METER TO THE MOST REMOTE OUTLET, BRANCH LENGTH
 SIZES, DELIVERY PRESSURE AT THE METER AND LOCATIONS OF
 REGULATORS AND STEP DOWN PRESSURES, BTUH LOAD OF EACH
 APPLIANCE AND THE TOTAL LOAD OF THE SYSTEM- SECTIONS
 G2413.2, G2413.3, G2413.4, G2413.4.1, G2413.4.2,
 G2414.1, G2420.1, G2421.1 & G2421.2 FBC RES.
  
 2) PLEASE SUBMIT A COMPLETE SPECIFICATION SHEET FOR THE
 FLEX CONNECTOR THAT INDICATES MANUFACTURER AND MODEL,
 LISTING STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1 FBC RES.
  
 3) PLEASE MARK UP THE B42 SERIES REGULATOR SPECS TO
 INDICATE THE MODEL NUMBER, INLET PRESSURE, ORIFICE AND
 SPRING SIZE OF THE SELECTED REGULATOR- SECTION G2421.1
 & G2421.2 FBC RES.
  
 4) SUBMIT INSTALLATION GUIDELINES FROM GENERAC TO
 VERIFY THE ALLOWABLE CLEARANCES FOR THE GENERATOR TO
 THE BUILDING, OPERABLE OPENINGS INTO THE BUILDING, AND
 PROPERTY LINES- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-09-23 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-21 Time 15:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-09-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-16 Time 10:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 13:45 Rev Time 0.00
Received By shill Date 2020-08-27 Time 14:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-09-23 Cont ID  
Sent By ccole Date 2020-09-23 Time 09:06 Rev Time 0.00
Received By ccole Date 2020-09-23 Time 06:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-09-17 Cont ID  
Sent By ccole Date 2020-09-17 Time 16:02 Rev Time 0.00
Received By ccole Date 2020-09-17 Time 12:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-09-10 Cont ID  
Sent By ccole Date 2020-09-10 Time 09:49 Rev Time 0.00
Received By ccole Date 2020-09-10 Time 09:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-09-29 Cont ID  
Sent By ccole Date 2020-09-29 Time 07:50 Rev Time 0.00
Received By ccole Date 2020-09-29 Time 07:50 Sent To  
Notes
2020-09-29 07:54:09THE SIGNATURE REVIEW HAS BEEN PASSED HOWEVER A HOLD HAS
 BEEN PLACED ON INSPECTIONS UNTIL A SIGNED AND SEALED
 COPY OF THE AMERICAST GENERATOR CONCRETE PAD DOCUMENT
 IS SUBMITTED TO THE WPB BUILDING DEPT. PLEASE SEE
 COMMENTS BELOW. CCOLE- 9/29/30
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
  
 IF THIS PERMIT IS CRITICAL PATH, PLEASE ADVISE AND THIS
 CAN BE PASSED WITH PROVISO. AN INSPECTION HOLD WILL BE
 PLACED ON THIS PERMIT.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
 SAMANTHA M. HILL
 CHIEF PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-09-23 Cont ID  
Sent By ccole Date 2020-09-23 Time 09:08 Rev Time 0.00
Received By ccole Date 2020-09-23 Time 09:08 Sent To  
Notes
2020-09-23 09:09:11SIGNATURE REVIEW- 9/23/2020 CCOLE
  
 1) THE SIGNATURE OF FL. LICENSED GAS CONTRACTOR AND
 LICENSE NUMBER SHALL BE ON THE GAS RISER DRAWING PER
 SECTION 107.2.1 WPB, AND FL. STATURES 471.003 &
 471.025.
  
 2) COPIED BELOW ARE THE PREVIOUS SIGNATURE REVIEW
 COMMENTS BY PLAN REVIEWER SAMANTHA HILL CONCERNING THE
 GENERATOR MOUNTING PAD.
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 IF THIS PERMIT IS CRITICAL PATH, PLEASE ADVISE AND THIS
 CAN BE PASSED WITH PROVISO. AN INSPECTION HOLD WILL BE
 PLACED ON THIS PERMIT.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
 SAMANTHA M. HILL
 CHIEF PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-09-17 Cont ID  
Sent By ccole Date 2020-09-17 Time 16:57 Rev Time 0.00
Received By ccole Date 2020-09-17 Time 16:57 Sent To  
Notes
2020-09-17 16:58:24SIGNATURE REVIEW- 9/17/2020 CCOLE
  
 1) THE SIGNATURE OF FL. LICENSED GAS CONTRACTOR AND
 LICENSE NUMBER SHALL BE ON THE GAS RISER DRAWING PER
 SECTION 107.2.1 WPB, AND FL. STATURES 471.003 &
 471.025.
  
 2) COPIED BELOW ARE THE PREVIOUS SIGNATURE REVIEW
 COMMENTS BY PLAN REVIEWER SAMANTHA HILL CONCERNING THE
 GENERATOR MOUNTING PAD.
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 IF THIS PERMIT IS CRITICAL PATH, PLEASE ADVISE AND THIS
 CAN BE PASSED WITH PROVISO. AN INSPECTION HOLD WILL BE
 PLACED ON THIS PERMIT.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
 SAMANTHA M. HILL
 CHIEF PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 13:44 Rev Time 0.00
Received By shill Date 2020-09-12 Time 13:43 Sent To  
Notes
2020-09-12 13:44:45SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
  
 IF THIS PERMIT IS CRITICAL PATH, PLEASE ADVISE AND THIS
 CAN BE PASSED WITH PROVISO. AN INSPECTION HOLD WILL BE
 PLACED ON THIS PERMIT.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
 SAMANTHA M. HILL
 CHIEF PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-08 Cont ID  
Sent By rthermid Date 2020-09-08 Time   Rev Time  
Received By rthermid Date 2020-09-08 Time   Sent To I
Notes
***NONE***