Plan Review Details - Permit 20080448
Plan Review Stops For Permit 20080448
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-27 Cont ID  
Sent By rmcdouga Date 2020-08-27 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2020-08-27 Time 10:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-20 Cont ID  
Sent By rmcdouga Date 2020-08-20 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2020-08-20 Time 09:46 Sent To  
Notes
2020-08-19 10:09:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE
 PROPOSED ELEVATOR, THE PROPOSED CONCRETE PAD AND
 WALKWAYS. CITY AMENDMENTS FBC 107.2.1
  
 2) PROVIDE DIMENSIONS AND DETAILS OF THE CONCRETE
 WALKWAYS. CITY AMENDMENTS FBC 107.2.1
  
 3) THE PLANS APPEAR TO INDICATE THAT THIS ELEVATOR WILL
 BE INSTALLED ON THE EXTERIOR OF THE BUILDING. PROVIDE
 AN ELEVATION OF THE BUILDING AND SHOW WHERE THE
 ELEVATOR WILL BE INSTALLED. SHOW WHERE THE SPECIFIED
 LIFT TOWER ATTACHMENTS EVERY 48" TO THE EXISTING
 BUILDING WILL OCCUR. CITY AMENDMENTS FBC 107.2.1
  
 4) THE PLANS SHOW A RECESS IN THE CONCRETE AT THE
 EXTERIOR ELEVATOR PAD. SPECIFY HOW WATER WILL BE
 PREVENTED FROM ENTERING OR WILL BE REMOVED FROM THE
 RECESS. CITY AMENDMENTS FBC 107.2.1
  
 5) INDICATE HOW ACCESS FROM THE ELEVATOR CAB TO THE
 BUILDING WILL BE ACCOMPLISHED. CITY AMENDMENTS FBC
 107.2.1
  
 6) PLEASE CLARIFY IF THE USE OF THIS ELEVATOR IS
 SPECIFIC TO ONE UNIT OR ACCESSIBLE TO OTHER RESIDENTS
 OF THE BUILDING. CITY AMENDMENTS FBC 107.2.1
  
 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
  
 8) TO AVOID ADDITIONAL REVIEW COMMENTS AND PROVIDE
 CLARIFICATION, IT MAY BE HELPFUL TO PROVIDE A NARRATIVE
 LETTER EXPLAINING HOW EACH COMMENT HAS BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-18 Cont ID  
Sent By jleahy Date 2020-08-18 Time 09:28 Rev Time 0.00
Received By jleahy Date 2020-08-18 Time 09:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-13 Cont ID  
Sent By jleahy Date 2020-08-13 Time 18:26 Rev Time 0.00
Received By jleahy Date 2020-08-13 Time 18:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-08-31 Cont ID  
Sent By pleduc Date 2020-08-31 Time   Rev Time 0.00
Received By pleduc Date 2020-08-31 Time 13:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-08-24 Cont ID  
Sent By pleduc Date 2020-08-24 Time   Rev Time 0.00
Received By pleduc Date 2020-08-24 Time 10:27 Sent To  
Notes
2020-08-24 10:40:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) ENGINEERING SHEETS - THERE IS NO SITE PLAN THAT
 INDICATES THE LOCATION OF THE PROPOSED.
  
 IS THIS INTERIOR OR EXTERIOR?
  
 PLEASE PROVIDE A DETAILED SITE PLAN.
  
  
  
 2) ENGINEERING SHEETS - THERE ARE NO INDICATIONS OF
 ENTRY THROUGH WALL, INTERIOR/EXTERIO,R SPACES AND
 STURCTURAL/FINISH WORK,
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) THERE DOES NO APPEAR TO BE ANY MANUFACTURES
 SPECIFICATION SHEETS AND OR LISTINGS.
  
 PLEASE PROVIDE TO ENSURE INSTALL IS IN COMPLIANCE WITH
 SPECIFICATIONS.
  
  
  
 4) AS THIS IS FOR A 2ND FLOOR UNIT, WHAT IS THE IMPACT
 TO THE 1ST FLOOR? WHAT IS THE LOCATION OF THE PROPOSED
 TO WINDOW/DOORS ON EACH FLOOR?
  
 PLEASE PROVIDE A HORIZONTAL VIEW WITH ALL DIMENSIONS TO
 OPENINGS.
  
  
  
  
 5) IS THERE AN APPROVAL LETTER FROM THE CONDO
 ASSOCIATION?
  
 PLEASE PROIVDE A COPY FOR THE RECORD.
  
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-31 Cont ID  
Sent By rmcdouga Date 2020-08-31 Time 13:48 Rev Time 0.00
Received By rmcdouga Date 2020-08-26 Time 15:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-25 Cont ID  
Sent By lmarchan Date 2020-08-25 Time 12:03 Rev Time 0.00
Received By lmarchan Date 2020-08-10 Time 14:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-27 Cont ID  
Sent By rmcdouga Date 2020-08-27 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2020-08-27 Time 10:36 Sent To  
Notes
2020-08-26 15:38:17DIGITALLY SIGNED FILE IN 'SIGNATURES' FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-18 Cont ID  
Sent By jleahy Date 2020-08-18 Time 09:28 Rev Time 0.00
Received By jleahy Date 2020-08-18 Time 09:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-13 Cont ID  
Sent By jleahy Date 2020-08-13 Time 18:29 Rev Time 0.00
Received By jleahy Date 2020-08-13 Time 18:27 Sent To  
Notes
2020-08-13 18:28:35FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ELECTRICAL PLAN IS NOT SIGNED.
  
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 OR OWNER BUILDER IN THIS CASE PRINT NAME, SIGN NAME,
 DATE

Review Stop Z ZONING
Rev No 2 Status P Date 2020-08-31 Cont ID  
Sent By ajones Date 2020-08-31 Time 13:46 Rev Time 0.00
Received By ajones Date 2020-08-31 Time 13:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-25 Cont ID  
Sent By ajones Date 2020-08-25 Time 11:59 Rev Time 0.00
Received By ajones Date 2020-08-25 Time 11:59 Sent To  
Notes
2020-08-25 12:02:048/25/20- FAILED- PLEASE PROVIDE A SITE PLAN SHOWING THE
 LOCATION OF THE ELEVATOR AS IT RELEATES TO THE PROPERTY
 LINES.
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]
  