| 2020-09-02 13:42:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE INDICATIONS WTHIN THE BACK UP INFORMATION |
| | THAT THERE ARE TWO DOORS BEING REPLACED "3RD FLOOR AND |
| | 2ND FLOOR LEFT HAND OUTSWING". |
| | |
| | THE APPLICATION STATES "REPLACE 1 HOLLOW METAL DOOR IN |
| | STAIRWELL" |
| | |
| | PLEASE REVIEW AND PROVIDE A DETILED SCOPE OF WORK AND |
| | AN APPLICABLE FLOOR PLAN SHOWING THE EXACT LOCATION OF |
| | THE DOOR(S). |
| | |
| | |
| | |
| | 2) THERE IS AN INDICATION WITHIN THE BACKUP INFORMATION |
| | OF "RE-USING ELECTRIC STRIKE" . |
| | |
| | THERE IS NO ELECTRICAL PERMIT AND ANY WORK INVLOVING |
| | ACCESS CONTROL SHALL BE DONE UNDER SEPARATE PERMIT AND |
| | SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE CLOUDED NOTE. |
| | |
| | |
| | 2A) IF THE ELECTRIC STRIKE IS TIED INO THE FIRE ALARM, |
| | THE FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT |
| | AND SHOP DRAWING BY A CERTIFIED FACONTRACTOR. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE CLOUDED NOTE. |
| | |
| | |
| | |
| | 3) MOST STAIRWELL DOORS ARE INSTALL WITH A FIRE RATING. |
| | THE LOCATIONS OF THESE DOORS CAN NOT BE DETERMINED WITH |
| | WHAT IS PROVIDED TO CONFIRM INTENDED FIRE RATING ON |
| | ORIGINAL BUILDING PERMITS. |
| | |
| | THERE IS NO INDICATION THAT THESE NEW DOORS HAVE THE |
| | REQUIRED FIRE RATING. |
| | |
| | PLEASE REVIEW AND PROVIDE FOR ANY EXISTING FIRE DOOR |
| | RATING WITH THE REQUIRED RATING FOR THE NEW DOORS OR |
| | JUSTIFY WITH SPECIFIC DETAILS OF NONRATED DOORS AND |
| | NARRTIVE. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |