Plan Review Details - Permit 20080099
Plan Review Stops For Permit 20080099
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-05 Cont ID  
Sent By jgomez Date 2020-11-05 Time 17:44 Rev Time 0.00
Received By jgomez Date 2020-11-05 Time 17:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-30 Cont ID  
Sent By jwitmer Date 2020-09-30 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2020-09-30 Time 13:44 Sent To  
Notes
2020-09-30 14:23:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20080099
 ADD: 5600 N. FLAGLER DR. # 2207
 CONT: CODE GLASS & WINDOWS INC.
 TEL: 561-248-2528
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE, BUILDING W 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SEPT. 30TH/ 2020
 ACTION: DENIED
  
 1A) THE ENGINEERING DOCUMENTS LOOKS LIKE IT MAYBE A
 PAPER ORIGINAL THAT HAS BEEN UPLOADED TO PROJECT DOX.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 1B) PLEASE NOTE WHOEVER IS UPLOADING THE PLAN DOCUMENTS
 THE 13-PAGE DOCUMENT AND THE 4 PAGE SHOP DRAWING ARE
 LOADING THEM INTO THE SUPPORTING DOCUMENT FOLDER. THESE
 DOCUMENTS THAT HAVE DIGITAL SIGNATURES CAN NOT BE
 OPENED TO VERIFY THEY HAVE NOT BEEN PRINTED OUT AND
 THEN SCANNED AND UPLOADED. THE DOCUMENTS IN QUESTION
 NEED TO BE LOADED IN THE DRAWING FOLDER, THERE WE WILL
 BE ABLE TO VERIFY THE ELECTRONIC SIGNATURE, WE CAN NOT
 VERIFY SIGNATURE IN THE SUPPORTING DOCUMENT FOLDER.
 THANK YOU FOR YOUR HELP IN THIS MATTER.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 08:49 Rev Time 0.00
Received By shill Date 2020-09-12 Time 08:49 Sent To  
Notes
2020-09-12 08:52:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PERMIT DOCUMENTS FROM ANOTHER PROJECT WERE SUBMITTED
 (20020416). AS THIS ENGINEERING IS SITE SPECIFIC TO THE
 UNIT THIS CANNOT BE USED FOR THIS PROJECT, FBC B 1609.
 PROVIDE ENGINEERING TO SPECIFY WIND DESIGN LOAD
 REQUIREMENTS FOR THIS UNIT.
  
 2. PAGES 1 THROUGH 7 (AND OTHER PAGES AFTER THE SITE
 SPECIFIC ENGINEERING) OF THE PDF UPLOADED APPEAR TO BE
 A PART OF A PRODUCT APPROVAL. PLEASE PROVIDE THE
 PRODUCT APPROVAL IN ITS ENTIRETY, WITH ALL PAGES IN
 ORDER. ALL PAGES ARE REQUIRED TO SHOW CODE COMPLIANCE,
 FBC B 1609.
  
 3. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED
 INSTALLATION, INCLUDING DISTANCE TO THE CORNER OF THE
 BUILDING, IF IT'S A CORNER UNIT, FBC B 1609.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-05 Cont ID  
Sent By jgomez Date 2020-11-05 Time 17:44 Rev Time 0.00
Received By jgomez Date 2020-10-21 Time 11:10 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-09-30 Time 14:27 Rev Time 0.00
Received By lmarchan Date 2020-09-22 Time 10:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 08:56 Rev Time 0.00
Received By shill Date 2020-08-24 Time 09:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-30 Cont ID  
Sent By jgomez Date 2020-10-30 Time 11:11 Rev Time 0.00
Received By jgomez Date 2020-10-30 Time 11:10 Sent To  
Notes
2020-10-30 11:14:38HARD COPY OF ENGINEERED DRAWINGS (4 OF 4)HAVE ORIGINAL
 SEAL/SIGNATURE AND WERE UPLOADED TO PROJECTDOX IN THE
 DRAWINGS FOLDER. JG.
 ALL THE ENGINEER DOCUMENTS UPLOADED IN THE SUPPORTING
 DOCUMENTS FOLDER HAVE A VALID ENGINEER'S DIGITAL
 SIGNATURE. JG.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time 14:27 Rev Time 0.00
Received By jwitmer Date 2020-09-30 Time 13:44 Sent To  
Notes
2020-09-30 14:23:371A) THE ENGINEERING DOCUMENTS LOOKS LIKE IT MAYBE A
 PAPER ORIGINAL THAT HAS BEEN UPLOADED TO PROJECT DOX.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 1B) PLEASE NOTE WHOEVER IS UPLOADING THE PLAN DOCUMENTS
 THE 13-PAGE DOCUMENT AND THE 4 PAGE SHOP DRAWING ARE
 LOADING THEM INTO THE SUPPORTING DOCUMENT FOLDER. THESE
 DOCUMENTS THAT HAVE DIGITAL SIGNATURES CAN NOT BE
 OPENED TO VERIFY THEY HAVE NOT BEEN PRINTED OUT AND
 THEN SCANNED AND UPLOADED. THE DOCUMENTS IN QUESTION
 NEED TO BE LOADED IN THE DRAWING FOLDER, THERE WE WILL
 BE ABLE TO VERIFY THE ELECTRONIC SIGNATURE, WE CAN NOT
 VERIFY SIGNATURE IN THE SUPPORTING DOCUMENT FOLDER.
 THANK YOU FOR YOUR HELP IN THIS MATTER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-12 Cont ID  
Sent By shill Date 2020-09-12 Time 08:54 Rev Time 0.00
Received By shill Date 2020-09-12 Time 08:54 Sent To  
Notes
2020-09-12 08:56:45SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
  
 IF THIS PERMIT IS CRITICAL PATH, PLEASE ADVISE AND THIS
 CAN BE PASSED WITH PROVISO. AN INSPECTION HOLD WILL BE
 PLACED ON THIS PERMIT.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL ONE ORIGINAL SIGNED AND SEALED
 PAPER ORIGINAL WITH A WET SIGNATURE TO:
  
 SAMANTHA M. HILL
 CHIEF PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.
  
  
  
  