Plan Review Details - Permit 20080046
Plan Review Stops For Permit 20080046
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-12-23 Cont ID  
Sent By ccole Date 2020-12-23 Time 18:03 Rev Time 0.00
Received By ccole Date 2020-12-23 Time 18:03 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-11-23 Cont ID  
Sent By jwitmer Date 2020-11-23 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2020-11-23 Time 13:13 Sent To  
Notes
2020-11-23 14:01:50COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jwitmer Date 2020-09-23 Time 09:15 Rev Time 0.00
Received By jwitmer Date 2020-09-23 Time 09:02 Sent To  
Notes
2020-09-23 09:14:24COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-23 Cont ID  
Sent By jwitmer Date 2020-11-23 Time 13:58 Rev Time 0.00
Received By jwitmer Date 2020-11-23 Time 13:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jwitmer Date 2020-09-23 Time 12:13 Rev Time 0.00
Received By jwitmer Date 2020-09-23 Time 09:02 Sent To  
Notes
2020-09-23 12:09:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20080046
 ADD: 5300 EAST AVE.
 CONT: TRILLIUM CONSTRUCTION
 TEL: 561-296-0700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 23RD/ 2020
 ACTION: DENIED
  
 1) PLEASE NOTE THE LIFE SAFETY SHEET REFERENCE THE 2017
 EXISTING BUILDING CODE BUT THERE IS NO REFERENCE TO
 SECTION 301.1 METHODS OR ANY OTHER CODE REFERENCE TO
 THE 2017 EXISTING BUILDING CODE. PLEASE REVIEW SECTION
 101.2 FOR SCOPING AND THE EXCEPTION FOR PUBLIC
 EDUCATIONAL FACILITIES AND STATE LICENSED FACILITIES,
 SEE CHAPTER 4, SPECIAL OCCUPANCY, OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2017 FBC-B 467 HOSPICE INPATIENT FACILITES AND UNITS
 AND HOSPICE RESIDENCES
 427.2.2 CODES AND STANDARDS
 467.2.2.3. IN RENOVATIONS AND ADDITIONS TO EXISTING
 FACILITIES, ONLY THAT PORTION OF THE TOTAL FACILITY
 AFFECTED BY THE PROJECT MUST COMPLY WITH THE APPLICABLE
 SECTIONS OF THE CODES FOR NEW FACILITIES AND UNITS.
 PLEASE SHOW THE RESTROOMS IN EACH HOSPICE ROOM WILL
 MEET THE REQUIREMENTS FOR NEW CONSTRUCTION, 2017
 FBC-ACCESSIBILITY CODE CHAPTER 6. ALSO SEE PLUMBING
 PLAN REVIEW COMMENTS ON ALL ACCESSIBLE REQUIREMENTS
 NOTE # 3.
  
 2) SHEET A-1 ROOM FINISH SCHEDULE INDICATES THAT IN
 BOTH THE FAMILY TOILET ROOMS AND PATIENT TOILET ROOMS
 G. W. B. PAINT/ CT -2/CT-3.
  
 2A) 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 2B) 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 2C) 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 3) SHEET DE-1 NOTES 9 & 19 BOTH REFER TO THE SLIDING
 GLASS DOORS BEING REMOVED. NOTE # 9 REFERS YOU TO SHEET
 A-3 FOR MORE INFORMATION. NO INFORMATION IS PROVIDED.
 SHEET A-1 DOES SHOW A PAIR OF EXTERIOR FRENCH STYLE
 SWING DOORS OPENING INTO THE COURTYARD. THERE IS NO
 INFORMATION IF THIS COURTYARD IS OPEN OR ENCLOSED. FOR
 THE PURPOSES OF THIS REVIEW IT WILL BE CONSIDERED OPEN
 AND FURTHER COMMENTS WILL APPEAR IN REGARD TO THE NEW
 EXTERIOR FRENCH DOORS.
  
 4) 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 4.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 5) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 6) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 8) IDENTIFY GLAZINGS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 9) THRESHOLDS ACCESS. CODE 404.2.5. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 10) HABITAL SPACES/ 1710.5.1.1FBC-B EXTERIOR WINDOWS
 AND DOORS. (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED
 WHERE THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN
 1 NEED NOT BE TESTED FOR WATER INFILTRATION. THE
 OVERHANG RATIO SHALL BE CALCULATED BY THE FOLLOWING
 EQUATION:
 OH RATIO = OH LENGTH/OH HEIGHT
 WHERE:
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-09-14 Cont ID  
Sent By jleahy Date 2020-09-14 Time 09:05 Rev Time 0.00
Received By jleahy Date 2020-09-14 Time 07:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-20 Cont ID  
Sent By pleduc Date 2020-11-20 Time   Rev Time 0.00
Received By pleduc Date 2020-11-20 Time 12:36 Sent To  
Notes
2020-11-20 12:37:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-08-14 Cont ID  
Sent By pleduc Date 2020-08-14 Time   Rev Time 0.00
Received By pleduc Date 2020-08-13 Time 16:12 Sent To  
Notes
2020-08-14 13:48:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-12-23 Time   Rev Time 0.00
Received By ccarvaja Date 2020-12-21 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-24 Cont ID  
Sent By lmarchan Date 2020-11-24 Time 08:54 Rev Time 0.00
Received By lmarchan Date 2020-11-19 Time 16:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-09-23 Time 12:13 Rev Time 0.00
Received By ccarvaja Date 2020-08-12 Time 19:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-09-23 Cont ID  
Sent By jwitmer Date 2020-09-23 Time 09:11 Rev Time 0.00
Received By jwitmer Date 2020-09-23 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-11-21 Cont ID  
Sent By medwards Date 2020-11-21 Time 08:22 Rev Time 0.00
Received By medwards Date 2020-11-21 Time 08:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-10 Cont ID  
Sent By medwards Date 2020-09-10 Time 07:22 Rev Time 0.00
Received By medwards Date 2020-09-09 Time 13:37 Sent To  
Notes
2020-09-09 16:23:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20080046
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: REGISTERS IN THE RESIDENT AND FAMILY ROOMS
 ARE SYMBOL (C) IN THE DIFFUSER AND REGISTER SCHEDULE ON
 SHEET M0 INDICATING THEY ARE FOR SUPPLY AIR. IN THE
 HVAC LEGEND THE SYMBOL USED INDICATES THIS IS A
 RETURN/EXHAUST GRILLE, PLEASE BE CONSISTENT AND LABEL
 CORRECTLY. FBC FS 107.2.1
  
 2) SHEET M1: THE NEW DUCTWORK IN THE RESIDENTIAL AND
 FAMILY ROOMS ARE SMALLER THAN THE DUCT WORK THAT WAS
 EXISTING. PLEASE SHOW CALCULATIONS SHOWING WE ARE
 GETTING THE SAME ACH IN THESE AREAS. FBC M 407; ASHRAE
 170
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2021-01-06 Cont ID  
Sent By tklarge Date 2021-01-06 Time 10:08 Rev Time 0.00
Received By tklarge Date 2021-01-06 Time 10:08 Sent To  
Notes
2021-01-06 10:09:37THE MEDICAL GAS SHOULD HAVE BEEN REVIEWED AND PASSED
 UNDER PREVIOUS REVIEW.

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status N Date 2020-11-24 Cont ID  
Sent By ccole Date 2020-11-24 Time 08:35 Rev Time 0.00
Received By ccole Date 2020-11-24 Time 08:35 Sent To  
Notes
2020-11-24 08:36:30A SEPARATE PERMIT AND PLAN REVIEW ARE REQUIRED FOR THE
 MED GAS SYSTEM ALTERATION. A COMPLETE REVIEW HAS NOT
 BEEN PERFORMED UNDER THIS PERMIT.
 CCOLE- 11/24/20

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2020-09-23 Cont ID  
Sent By jwitmer Date 2020-09-23 Time 09:11 Rev Time 0.00
Received By jwitmer Date 2020-09-23 Time 09:09 Sent To  
Notes
2020-09-23 09:11:28THE LOT HAS A FLOOD ZONES ON THE PROPERTY BUT ALL OF
 THE BUILDINGS ARE OUT OF THE FLOOD ZONE BUILDINGS ARE
 LOCATED IN FLOOD ZONE X. JIM WITMER 9/23/2020.

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-12-23 Cont ID  
Sent By ccole Date 2020-12-23 Time 17:44 Rev Time 0.00
Received By ccole Date 2020-12-23 Time 17:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-11-24 Cont ID  
Sent By ccole Date 2020-11-24 Time 08:31 Rev Time 0.00
Received By ccole Date 2020-11-23 Time 10:17 Sent To  
Notes
2020-11-24 08:31:572ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20080046
 11/23/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW ARE MARKED AS PASSED ON
 FAILED. NOTES HAVE BEEN ADDED TO FAILED COMMENTS.
  
 1) PASSED. SHEET P1 WHICH IS LISTED IN THE DRAWING
 SCHEDULE ON THE COVER SHEET WAS NOT UPLOADED FOR
 REVIEW. A THOROUGH REVIEW OF THE PLANS CANNOT BE
 COMPLETED AT THIS TIME. PLEASE PROVIDE THE P1 SHEET FOR
 REVIEW- SECTION 107.2.1 WPB.
  
 2) PASSED. SHEET LS1: REFER TO SECTION 301.1 FBC EX AND
 INDICATE WHICH COMPLIANCE METHOD WILL USED FOR THE
 PROPOSED ALTERATION. A THOROUGH REVIEW OF THE PLANS
 CANNOT BE COMPLETED WITH A COMPLIANCE METHOD INDICATED.
  
 3) FAILED. THE ARCHITECTURAL FLOOR PLAN AND ELEVATION
 SHEETS INDICATE THE ALTERED BATHROOMS ARE NOT IN
 COMPLIANCE WITH FBC ACC. PLEASE SEE SECTION 202.3 WHICH
 REQUIRES COMPLETE ACCESSIBILITY COMPLIANCE FOR BATHROOM
 ALTERATIONS UNDER SECTION 213 AND SECTIONS 603 THROUGH
 610. THERE ARE EXCEPTIONS LISTED UNDER SECTION 213.2
 HOWEVER NO EXCEPTION IS CITED ON THE PLAN AND NO
 EXPLANATION HAS BEEN PROVIDED. UNDERSTANDING THAT SOME
 OF THE REQUIRED ACCESSIBILITY DETAILS ARE SHOWN ON THE
 ADA PLAN SHEETS, INDICATED BELOW ARE PLAN REVIEW
 REQUIREMENTS FOR THE ACCESSIBLE BATHROOMS: IN RESPONSE
 TO THE COMMENT THE ARCHITECT IS CITING THE EXCEPTION
 FOR TECHNICAL INFEASIBILITY WHICH IS EXCEPTION 2 UNDER
 SECTION 202.3, AND ALSO SECTION 202.4.2 WHICH IS THE
 SUB-SECTION FOR DISPROPORTIONATE COSTS. CONCERNING
 TECHNICAL INFEASIBILITY THERE IS NO INFORMATION OR
 EVIDENCE PROVIDED ON THE PLANS TO SUPPORT THE
 EXCEPTION. CONCERNING THE CLAIM OF DISPROPORTIONATE
 COSTS, THERE IS NO ITEMIZED ACCESSIBILITY COST
 BREAKDOWN PROVIDED IN ACCORDANCE WITH THE SECTION. THE
 ARCHITECT ALSO STATES THAT THE BATHROOMS ARE BEING MADE
 ACCESSIBLE TO THE MAXIMUM EXTENT FEASIBLE, HOWEVER THE
 PLANS DO NOT INDICATE THEY ARE BEING MADE ACCESSIBLE TO
 THE MAXIUM EXTENT FEASIBLE, AND IT APPEARS FURTHER
 COMPLIANCES MUST BE MET. PLEASE REVIEW SHEETS A2,
 ADA.1.1, ADA 1.2. REVISE SHEET A2 IN ACCORDANCE WITH
 THE COMMENTS LISTED BELOW TO SHOW COMPLIANCE TO THE
 MAXIMUM EXTENT AND IF A COMPLIANCE IS DEEMED
 TECHNICALLY INFEASIBLE, PLEASE PROVIDE AN EXPLANATION.
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
  
 C) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 NEW SHOWERS PER SECTION 608.2.1 AND FIGURE 608.2.1. THE
 SHOWER COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES
 CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS
 OF OPPOSING SIDES AND SHALL HAVE A 36-INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
  
 D) BATHROOM ENTRY DOOR WIDTHS, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
  
 E) TURNING SPACE DIAMETERS SECTION 304.3.
  
 F) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL-
 SECTION 604.2.
  
 G) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
  
 H) HEIGHTS OF THE FRONT RIMS OF THE LAVATORIES FROM THE
 FINISHED FLOOR- SECTION 606.3.
  
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2 AND 306.
  
 J) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS AT THE WATER CLOSETS- SECTION 604.5 & 609.4.
  
 K) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SECTION
 604.6.
  
 L) LOCATIONS, CLEARANCE, AND MOUNTING HEIGHTS FOR THE
 TOILET PAPER DISPENSERS- SECTION 604.7.
  
 M) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3.
  
 N) NEW SHOWER GRAB BAR AND SHOWER CONTROL LOCATIONS AND
 CLEARANCES PER SECTIONS AND FIGURES 608.3.1 & 608.5.1.
  
 O) LOCATION AND DETAILS FOR INSTALLATION OF THE
 REQUIRED SEAT IN THE SHOWER- SECTION 608.4 & 610.3.
  
 REFER TO SECTIONS 467.2.3.21.3 & 467.2.4.6 FBC-17
 BUILDING PRINTED BELOW CONCERNING RESIDENT BATHROOMS IN
 HOSPICE INPATIENT FACILITIES.
 467.2.3.21.3
 ALL SHOWERS LOCATED IN BATHING ROOMS CONNECTED DIRECTLY
 TO THE RESIDENT ROOMS SHALL BE DESIGNED SO THAT A
 SHOWER CHAIR CAN BE EASILY ROLLED IN AND OUT OF THE
 SHOWER AREA.
 467.2.4.6
 GRAB BARS SHALL BE PROVIDED AT ALL PATIENT TOILETS,
 SHOWERS, AND TUBS. THE BARS SHALL HAVE A CLEARANCE OF
 11/2 INCHES (38 MM) TO THE WALLS AND SHALL BE
 SUFFICIENTLY ANCHORED TO SUSTAIN A CONCENTRATED APPLIED
 LOAD OF NOT LESS THAN 250 POUNDS (113 KG).
  
 4) PASSED. SHEET A1: A FORWARD APPROACH IS INDICATED
 FOR THE HAND SINK IN THE FAMILY ROOM. PLEASE PROVIDE A
 DETAIL INDICATING THE REQUIRED KNEE AND TOE CLEARANCES
 PER SECTIONS 606.2 AND 306.
  
 5) PASSED. PLEASE NOTE THAT SANITARY AND WATER
 DISTRIBUTION RISERS AND FLAT LINE DRAWINGS WILL BE
 REQUIRED FOR REVIEW. PLEASE REFER TO SECTION
 107.3.5.1.3 WPB FOR PLUMBING PLAN REVIEW REQUIREMENTS.
  
 NEW COMMENTS.
  
 6) SHEET P1: IT APPEARS THAT KEYNOTE 8 SHOULD REPLACE
 KEYNOTE 5 AT THE SHOWER LOCATIONS- SECTION 107.2.1 WPB.
  
 7) P1: PROVIDE A SHOWER PAN AND DRAIN DETAIL- SECTIONS
 417.5.2.1, 417.5.2.6, AND 1002.1 FBC P.
  
 8) P1: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB.
  
 9) P1: PROVIDE A WATER HAMMER ARRESTOR AND BACKFLOW
 PREVENTER FOR THE ICE MAKER- SECTIONS 604.9 AND 608.3
 FBC P.
  
 10) P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE ICE MAKER
 AND SHOW HOW CONDENSATION OR DRAINAGE FROM THE ICE
 MAKER WILL BE DISPOSED OF PER SECTION 314.2 FBC P.
  
 11) PLEASE NOTE THAT A SEPARATE PERMIT AND PLANS ARE
 REQUIRED FOR THE MED GAS SYSTEM ALTERATION. A COMPLETE
 REVIEW HAS NOT BEEN PERFORMED UNDER THIS PERMIT.
  
 12) SUBMIT A SUB-PERMIT APPLICATION FOR PLUMBING-
 SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-28 Cont ID  
Sent By ccole Date 2020-08-28 Time 15:59 Rev Time 0.00
Received By ccole Date 2020-08-28 Time 13:58 Sent To  
Notes
2020-08-28 15:59:331ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20080046
 8/28/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1 WHICH IS LISTED IN THE DRAWING SCHEDULE ON
 THE COVER SHEET WAS NOT UPLOADED FOR REVIEW. A THOROUGH
 REVIEW OF THE PLANS CANNOT BE COMPLETED AT THIS TIME.
 PLEASE PROVIDE THE P1 SHEET FOR REVIEW- SECTION 107.2.1
 WPB.
  
 2) SHEET LS1: REFER TO SECTION 301.1 FBC EX AND
 INDICATE WHICH COMPLIANCE METHOD WILL USED FOR THE
 PROPOSED ALTERATION. A THOROUGH REVIEW OF THE PLANS
 CANNOT BE COMPLETED WITH A COMPLIANCE METHOD INDICATED.
  
 3) THE ARCHITECTURAL FLOOR PLAN AND ELEVATION SHEETS
 INDICATE THE ALTERED BATHROOMS ARE NOT IN COMPLIANCE
 WITH FBC ACC. PLEASE SEE SECTION 202.3 WHICH REQUIRES
 COMPLETE ACCESSIBILITY COMPLIANCE FOR BATHROOM
 ALTERATIONS UNDER SECTION 213 AND SECTIONS 603 THROUGH
 610. THERE ARE EXCEPTIONS LISTED UNDER SECTION 213.2
 HOWEVER NO EXCEPTION IS CITED ON THE PLAN AND NO
 EXPLANATION HAS BEEN PROVIDED. UNDERSTANDING THAT SOME
 OF THE REQUIRED ACCESSIBILITY DETAILS ARE SHOWN ON THE
 ADA PLAN SHEETS, INDICATED BELOW ARE TYPICAL PLAN
 REVIEW REQUIREMENTS FOR THE ACCESSIBLE BATHROOMS:
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 NEW SHOWERS PER SECTION 608.2.1 AND FIGURE 608.2.1. THE
 SHOWER COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES
 CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS
 OF OPPOSING SIDES AND SHALL HAVE A 36-INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
 D) BATHROOM ENTRY DOOR WIDTHS, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
 E) TURNING SPACE DIAMETERS SECTION 304.3.
 F) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL-
 SECTION 604.2.
 G) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
 H) HEIGHTS OF THE FRONT RIMS OF THE LAVATORIES FROM THE
 FINISHED FLOOR- SECTION 606.3
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2 AND 306.
 J) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5 & 609.4.
 K) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SECTION
 604.6.
 L) LOCATIONS, CLEARANCE, AND MOUNTING HEIGHTS FOR THE
 TOILET PAPER DISPENSERS- SECTION 604.7.
 M) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3
 N) NEW SHOWER GRAB BAR AND SHOWER CONTROL LOCATIONS AND
 CLEARANCES PER SECTIONS AND FIGURES 608.3.1 & 608.5.1.
 O) LOCATION AND DETAILS FOR INSTALLATION OF THE
 REQUIRED SEAT IN THE SHOWER- SECTION 608.4 & 610.3.
  
 4) SHEET A1: A FORWARD APPROACH IS INDICATED FOR THE
 HAND SINK IN THE FAMILY ROOM. PLEASE PROVIDE A DETAIL
 INDICATING THE REQUIRED KNEE AND TOE CLEARANCES PER
 SECTIONS 606.2 AND 306.
  
 5) PLEASE NOTE THAT SANITARY AND WATER DISTRIBUTION
 RISERS AND FLAT LINE DRAWINGS WILL BE REQUIRED FOR
 REVIEW. PLEASE REFER TO SECTION 107.3.5.1.3 WPB FOR
 PLUMBING PLAN REVIEW REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By medwards Date 2020-12-21 Time 16:14 Rev Time 0.00
Received By medwards Date 2020-12-21 Time 16:14 Sent To  
Notes
2020-12-21 16:15:50SHEETS P0 AND P1 ARE SIGNED AND SEALED PAPER DRAWINGS.
 ROUTED TO STORAGE. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-20 Cont ID  
Sent By medwards Date 2020-11-20 Time 07:08 Rev Time 0.00
Received By medwards Date 2020-11-20 Time 07:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-24 Cont ID  
Sent By llouie Date 2020-11-24 Time   Rev Time 0.00
Received By llouie Date 2020-11-24 Time   Sent To  
Notes
2020-11-24 08:52:42INTERIOR AND COURTYARD MODIFICATIONS ONLY; NO
 EXPANSION.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-20 Cont ID  
Sent By llouie Date 2020-08-20 Time   Rev Time  
Received By llouie Date 2020-08-20 Time   Sent To  
Notes
2020-08-20 09:51:22* INTERIOR AND COURTYARD MODIFICATIONS ONLY; NO
 EXPANSION.