Plan Review Details - Permit 20071430
Plan Review Stops For Permit 20071430
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-20 Cont ID  
Sent By rmcdouga Date 2020-10-20 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2020-10-20 Time 13:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-09 Cont ID  
Sent By rmcdouga Date 2020-09-09 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2020-09-09 Time 11:29 Sent To  
Notes
2020-09-09 11:37:45PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMMENT NOT ADDRESSED. NOTE: IF SOMETHING ON THE
 DRAWING APPLIES TO THIS PERMIT CROSS OUT THE ITEMS THAT
 DO NOT APPLY TO THIS PERMIT #18100338, THAT YOU WISH TO
 REVISE. THIS IS A REVISION TO PERMIT #18100338, THE
 WALKIN COOLER BUILDING AND DUMPSTER ENCLOSURE ARE NOT
 INCLUDED WITH THIS PERMIT. THE WALKIN COOLER BUILDING
 AND THE DUMPSTER ENCLOSURE DRAWINGS WERE SUBMITTED
 UNDER PERMIT NUMBER 17020359. ANY REVISIONS TO THESE
 TWO STRUCTURES SHOULD BE MADE TO THE PERMIT THEY WERE
 INCLUDED IN. PLEASE REMOVE THESE DRAWINGS FROM THE
 REVISION AND SUBMIT THEM AS A REVISION TO THE
 APPROPRIATE PERMIT. FBC 107.2
  
 2) COMMENT NOT ADDRESSED. REVISED SHEET A-101R NO
 LONGER SHOWS THE ACCESSIBLE PORTION OF THE BAR THAT IS
 REQUIRED BY FBC ACCESSIBILITY SECTION 902.1.
  
 I WAS NOT ABLE TO DETERMINE THAT THESE COMMENTS WERE
 ADDRESSED. PLEASE SUBMIT A NARRAITIVE EXPLAINING HOW
 EACH OF THE COMMENTS HAS BEEN CORRECTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By rmcdouga Date 2020-08-05 Time 14:59 Rev Time 0.00
Received By rmcdouga Date 2020-08-04 Time 17:18 Sent To  
Notes
2020-08-05 15:29:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS IS A REVISION TO PERMIT #18100338, THE WALKIN
 COOLER BUILDING AND DUMPSTER ENCLOSURE ARE NOT INCLUDED
 WITH THIS PERMIT. THE WALKIN COOLER BUILDING AND THE
 DUMPSTER ENCLOSURE DRAWINGS WERE SUBMITTED UNDER PERMIT
 NUMBER 17020359. ANY REVISIONS TO THESE TWO STRUCTURES
 SHOULD BE MADE TO THE PERMIT THEY WERE INCLUDED IN.
 PLEASE REMOVE THESE DRAWINGS FROM THE REVISION AND
 SUBMIT THEM AS A REVISION TO THE APPROPRIATE PERMIT.
 FBC 107.2
  
 2) REVISED SHEET A-101R NO LONGER SHOWS THE ACCESSIBLE
 PORTION OF THE BAR THAT IS REQUIRED BY FBC
 ACCESSIBILITY SECTION 902.1.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-14 Cont ID  
Sent By jleahy Date 2020-08-14 Time 16:51 Rev Time 0.00
Received By jleahy Date 2020-08-14 Time 16:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-10-09 Cont ID  
Sent By pleduc Date 2020-10-09 Time   Rev Time 0.00
Received By pleduc Date 2020-10-09 Time 11:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-31 Cont ID  
Sent By pleduc Date 2020-07-31 Time   Rev Time 0.00
Received By pleduc Date 2020-07-31 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-20 Cont ID  
Sent By rmcdouga Date 2020-10-20 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2020-10-08 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-09 Cont ID  
Sent By rmcdouga Date 2020-09-09 Time 11:39 Rev Time 0.00
Received By rmcdouga Date 2020-08-20 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-14 Cont ID  
Sent By jleahy Date 2020-08-14 Time 16:51 Rev Time 0.00
Received By jleahy Date 2020-07-30 Time 16:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-08-22 Cont ID  
Sent By medwards Date 2020-08-22 Time 10:10 Rev Time 0.00
Received By medwards Date 2020-08-22 Time 10:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By medwards Date 2020-08-05 Time 13:46 Rev Time 0.00
Received By medwards Date 2020-08-05 Time 12:58 Sent To  
Notes
2020-08-05 13:49:32THERE APPEAR TO BE SEVERAL REVISIONS ON THIS PROJECT.
 PLEASE PROVIDE THE LAST PREVIOUSLY APPROVED SHEETS FOR
 THIS PROJECT WITH THE NEXT UPLOAD OF THE MECHANICAL
 SHEETS AS I AM NEW TO THIS PROJECT I NEED TO SEE WHAT
 WAS APPROVED PREVIOUSLY.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-08-05 Cont ID  
Sent By ccole Date 2020-08-05 Time 13:52 Rev Time 0.00
Received By ccole Date 2020-08-05 Time 07:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 12:02 Rev Time 0.00
Received By equinone Date 2020-10-20 Time 12:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-09 Cont ID  
Sent By rmcdouga Date 2020-09-09 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2020-09-09 Time 11:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-05 Cont ID  
Sent By rmcdouga Date 2020-08-05 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2020-08-05 Time 15:38 Sent To  
Notes
***NONE***