Plan Review Details - Permit 20071423
Plan Review Stops For Permit 20071423
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By cthroop Date 2020-11-20 Time 08:52 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 06:36 Sent To  
Notes
2020-11-20 08:57:26PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SURVEY/SITE PLAN. IDETIFY LOCATION OF
 GENERATOR.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
  
 2. GENERATOR SPECIFICATIONS SUBMITTED FOR REVIEW ARE
 FROM 2017. PROVIDE CURRENT GENERATOR SPECIFICATIONS.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE STRUCTURAL PAD DESIGN FOR GENERATOR. IF
 EXISTING, STATE EXISTING ON SURVEY/SITE PLAN. CITY
 INSPECTOR WILL VERIFY.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By equinone Date 2020-11-20 Time 15:25 Rev Time 0.00
Received By equinone Date 2020-11-20 Time 15:25 Sent To  
Notes
2020-11-20 15:29:05CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) PLEASE PROVIDE ELECTRICAL RISER DIAGRAM SHOWING
 GENERATOR, CONDUCTOR SIZES AND WHAT ELEMENTS ARE NEW
 AND WHICH ONES ARE EXISTING TO REMAIN. FPC 107
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By ccole Date 2020-11-20 Time 10:20 Rev Time 0.00
Received By ccole Date 2020-11-20 Time 09:45 Sent To  
Notes
2020-11-20 10:20:561ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20071423
 11/20/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WPB BUILDING DEPT. PLAN RECORDS FOR PERMIT 19041488
 INDICATE AN EXISTING 16 KW AT 309,000 BTUS. THE NEW
 GENERATOR PER THE SPECS IS LISTED AT 492,000. IN ORDER
 TO ENSURE A SAFE OPERATING SYSTEM PLEASE PROVIDE AN
 UPDATED AND COMPLETE GAS RISER DRAWING SHOWING THE
 EXISTING GAS PIPING AND APPLIANCES- SECTIONS G2412.3 &
 G2412.4 FBC RES. PLEASE INCLUDE THE FOLLOWING
 INFORMATION ON THE RISER:
  
 A) SHOW THE TOTAL LOAD AND THE INDIVIDUAL LOADS OF THE
 SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES.
  
 B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE
 PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND
 THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND
 G2413.4.2 FBC RES.
  
 C) CLARIFY IF A NEW REGULATOR IS TO BE INSTALLED AS
 PART OF THE UPGRADE. PLEASE NOTE THE SPECS FOR THE NEW
 GENERATOR INDICATE GAS INPUT PRESSURE OF 5- 14 IN. W.C.
 INDICATE THE MAKE AND MODEL OF THE EXISTING OR NEW
 REGULATOR AND NOTE THE INLET AND OUTLET PRESSURE ON THE
 RISER DRAWING- SECTION G2421.1 & G2421.2. SUBMIT MARKED
 UP OR HIGHLIGHTED SPECS SHOWING THE SELECTED MODEL, THE
 MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA,
 AND ORIFICE SIZE. THE SPECS MAY BE DEFERRED AND BE
 ONSITE FOR INSPECTION.
  
 D) SHOW AN EXISTING OR NEW DRIP LEG AND FLEX CONNECTOR
 FOR THE GAS SUPPLY TO THE GENERATOR- SECTIONS- G2419.3
 & G2422.1 FBC RES.
  
 2) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 11:17 Rev Time 0.00
Received By equinone Date 2020-09-11 Time 19:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-11-20 Cont ID  
Sent By ccole Date 2020-11-20 Time 10:22 Rev Time 0.00
Received By ccole Date 2020-11-20 Time 09:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By cthroop Date 2020-11-20 Time 08:57 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 06:36 Sent To  
Notes
2020-11-20 09:01:29PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SIGNATURE REVIEW CANNOT BE COMPLETED AT THIS TIME.
  
 PROVIDE THE FOLLOWING DOCUMENTS FOR REVIEW.
  
 1. STRUCTURAL PAD DESIGN. SEE COMMENTS UNDER BUILDING
 REVIEW.
 2. ELECTRICAL RISER DIAGRAHM.
 3. GAS RISER DIAGRAHM.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By rthermid Date 2020-12-01 Time   Rev Time  
Received By rthermid Date 2020-12-01 Time   Sent To I
Notes
2020-12-01 11:22:00ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 12/1/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A SURVEY OF THE PROPERTY INDICATING
 THE LOCATION OF THE PROPOSED GENERATOR AS WELL AS THE
 SETBACKS TO ALL PROPERTY LINES. PURSUANT THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDR), SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved