| Plan Review Stops For Permit 20071369 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
4 |
Status |
P |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-27 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-27 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
F |
Date |
2020-10-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-09 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-09 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2020-10-09 10:35:52 | PLAN REVIEW / ASBESTOS | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC 2014 | | | | | | 3RD REVIEW | | | | | | RESULTS: DENIED | | | | | | COMMENTS FROM 1ST AND 2ND REVIEW HAVE NOT BEEN | | | ADDRESSED. SEE BELOW. | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING: | | | | | | THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2020-10-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-01 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-01 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2020-10-01 14:03:45 | PLAN REVIEW / ASBESTOS | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC 2014 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. SEE | | | BELOW. | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. | | | | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-08-21 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-08-21 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2020-08-21 12:40:04 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-27 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-27 |
Time |
15:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-10-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-09 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-09 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-10-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-01 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-01 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2020-10-01 14:07:41 | PLAN REVIEW / BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC 2014 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | THIS IS A DEMO PERMIT. | | | | | | 1. SUBMIT A DEMO PLAN. | | | PLANS SUBMITTED FOR REVIEW ARE FOR A COMMERCIAL | | | REMODEL. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-08-21 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-08-21 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2020-08-21 12:44:02 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, SCOPE NOT CLEAR. APPLICATION IS FOR "DEMO" | | | BUT DOES NOT STATE IF THIS IS INTERIOR DEMOLITION ONLY | | | OR DEMOLITION OF THE ENTIRE STRUCTURE. | | | | | | SINCE PLANS FOR AN INTERIOR RENOVATION WERE UPLOADED, | | | IT APPEARS THAT THIS MAY BE AN INTERIOR DEMO BUT NO | | | DEMO PLAN WAS SUBMITTED. IF THIS APPLICATION IS FOR | | | INTERIOR DEMO, PLEASE SUBMIT A DEMOLITION PLAN WHICH | | | SHOWS SCOPE OF WORK. ALSO PLEASE SUBMIT AN ELECTRICAL | | | SUB PERMIT APPLICATION. | | | | | | IF YOU PROPOSE TO DEMOLISH THE ENTIRE STRUCTURE, PLEASE | | | EMAIL ME FOR A CHECKLIST. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-27 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-27 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-09-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-09-24 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-09-24 |
Time |
07:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-10-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-10-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-10-07 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2020-10-07 14:14:24 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE DEPARTMENT | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2020-09-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-09-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-09-24 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2020-09-24 10:12:16 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE DEPARTMENT | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-27 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-20 |
Time |
13:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-10-09 |
|
|
Cont ID |
|
| Sent By |
ccarvaja |
Date |
2020-10-09 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
ccarvaja |
Date |
2020-10-06 |
Time |
10:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-10-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-01 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-09-23 |
Time |
07:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-08-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-08-21 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-08-21 |
Time |
12:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-10-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-09 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-09 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-10-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-01 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-01 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2020-10-01 14:05:31 | PLAN REVIEW / SIGNATURES | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET / DIGITAL SIGNATURE IS | | | NOT CONSIDERED A DIGITAL SIGNATURE. | | | | | | EITHER UPLOAD A DIGITALLY SIGNED DOCUMENT OR DROP OFF | | | (OR MAIL) ONE PAPER ORIGINAL WITH A WET SEAL AND | | | SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-08-21 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-08-21 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2020-08-21 13:05:46 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IF A DEMO PLAN PREPARED BY AN ARCHITECT IS SUBMITTED: | | | | | | DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS. A SCAN OF A WET SIGNATURE IS NOT CONSIDERED | | | A DIGITAL SIGNATURE. IF THE ARCHITECT NEEDS ASSISTANCE | | | WITH THE DIGITAL SIGNATURE, PLEASE HAVE HIM CONTACT ME. | | | | | | EITHER UPLOAD A DIGITALLY SIGNED DOCUMENT OR DROP OFF | | | (OR MAIL) ONE PAPER ORIGINAL: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | | | | |
|
|