Plan Review Details - Permit 20071347
Plan Review Stops For Permit 20071347
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-09 Cont ID  
Sent By jwitmer Date 2020-09-09 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2020-09-09 Time 07:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-08-02 Cont ID  
Sent By jwitmer Date 2020-08-02 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2020-08-02 Time 10:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-11 Cont ID  
Sent By jleahy Date 2020-08-11 Time 16:40 Rev Time 0.00
Received By jleahy Date 2020-08-11 Time 16:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-29 Cont ID  
Sent By pleduc Date 2020-07-29 Time   Rev Time 0.00
Received By pleduc Date 2020-07-29 Time 12:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-09-08 Cont ID  
Sent By lcrespo Date 2020-09-08 Time 16:15 Rev Time 0.00
Received By lcrespo Date 2020-09-08 Time 16:15 Sent To  
Notes
2020-09-08 16:17:0009/08/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By ccole Date 2020-08-05 Time 11:39 Rev Time 0.00
Received By ccole Date 2020-08-05 Time 11:39 Sent To  
Notes
2020-08-05 11:43:051ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20071347
 8/5/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P3 GAS RISER: PROVIDE THE SIZING TABLE FOR THE
 0.5" WC PRESSURE PIPING- SECTION 402.4 FBC FG.
  
 2) P3 GAS RISER: SHOW THE LOCATIONS OF REQUIRED UNIONS
 AT THE MP REGULATORS- SECTION 410.2 (7) FBC FG.
  
 3) P3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CHINESE RANGE WOK- SECTION 623.1 FBC FG. THE SPECS WERE
 NOT SUBMITTED WITH THE PLANS AND SPECS UNDER PERMIT
 20010651.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-09 Cont ID  
Sent By jwitmer Date 2020-09-09 Time 08:17 Rev Time 0.00
Received By jwitmer Date 2020-09-04 Time 11:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-31 Cont ID  
Sent By lmarchan Date 2020-08-31 Time 13:39 Rev Time 0.00
Received By lmarchan Date 2020-07-28 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-08-04 Cont ID  
Sent By medwards Date 2020-08-04 Time 13:33 Rev Time 0.00
Received By hmoser Date 2020-08-04 Time 12:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-08 Cont ID  
Sent By lcrespo Date 2020-09-08 Time 16:17 Rev Time 0.00
Received By lcrespo Date 2020-09-08 Time 16:17 Sent To  
Notes
2020-09-08 16:17:2609/08/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By ccole Date 2020-08-05 Time 11:33 Rev Time 0.00
Received By ccole Date 2020-08-05 Time 07:22 Sent To  
Notes
2020-08-05 11:34:031ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20071347
 8/5/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED."
 1) SHEET A-1: THE 4'8" DEPTH SHOWN FOR THE STANDARD
 WATER CLOSET COMPARTMENT IN THE MEN'S RESTROOM IS NOT
 IN COMPLIANCE WITH SECTION 405.33.1 FBC P. THE REQUIRED
 DEPTH IS 60" FOR TANK TOILETS. PLEASE SHOW THE DEPTH
 MEASUREMENTS IN THE WOMEN'S RESTROOMS.
  
 2) P1 & P1.1: PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION. A
 PRIMARY PERMIT APPLICATION BY A FL. LICENSED PLUMBER
 AND COMPLETE PLUMBING PLANS, SIZING CALCULATIONS, AND
 SPECIFICATIONS SHALL BE SUBMITTED- SECTION 107.2.1 WPB.
  
 3) P1: REMOVE THE GRAVITY GREASE INTERCEPTOR
 CALCULATION TABLE FORM THE PLAN TO AVOID CONFUSION. THE
 NEW SELECTED SCHIER GREAT BASIN INTERCEPTORS ARE
 HYDROMECHANICAL AND SHALL BE SIZED IN ACCORDANCE WITH
 SECTION 1003.3.4 FBC P. PROVIDE REVISED CALCULATIONS ON
 THE PLAN USING THE REQUIRED METHOD.
  
 4) P2: PLEASE CORRECTLY LABEL THE LOCATION OF THE TMV
 IN THE WATER HEATING PIPING DETAIL- SEE BALANCING VALVE
 INSTRUCTIONS IN THE DETAIL. PLEASE NOTE THAT WHERE A
 THERMOSTATIC MIXING VALVE IS USED IN A SYSTEM WITH A
 HOT WATER RECIRCULATING PUMP, THE HOT WATER OR TEMPERED
 WATER RETURN LINE SHALL BE ROUTED TO THE COLD WATER
 INLET PIPE OF THE WATER HEATER AND THE COLD WATER INLET
 PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE. A) THE LOCATION OF THE
 CIRCULATION PUMP IS INCORRECTLY SHOWN ON THE HW SUPPLY
 LINE ON THE FLOOR PLAN.
  
 5) P2.1 PLEASE CLARIFY WHICH LINE THE CIRCULATION PUMP
 IS BEING INSTALLED ON- SEE COMMENT #4 ABOVE. A) SHOW
 THE LOCATIONS OF REQUIRED MIXING VALVES AT THE PUBLIC
 LAVATORIES- SECTION 416.5 FBC P. B) SHOW THE LOCATIONS
 OF BACKFLOW PREVENTERS FOR SUPPLY LINES TO THE SODA
 DISPENSERS AND GUNS, ICE MAKERS, ICE STORAGE BINS,
 STEAMER, MOP SINK, AND ALL OTHER SUPPLY LINES TO
 APPLIANCES OR EQUIPMENT PROVIDING A SPECIAL FUNCTION-
 SECTION 608.3. C) SHOW THE LOCATIONS OF REQUIRED WATER
 HAMMER ARRESTORS- SECTION 604.9. D) PROVIDE A DEVICE
 SCHEDULE THAT INCLUDES THE TYPE OF BACKFLOW PREVENTER
 TO BE INSTALLED AT EACH LOCATION- SEE TABLE 608.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status P Date 2020-09-08 Cont ID  
Sent By lcrespo Date 2020-09-08 Time 13:36 Rev Time 0.00
Received By lcrespo Date 2020-09-08 Time 13:36 Sent To  
Notes
2020-09-08 16:16:2109/08/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING/GREASE
 TRAP)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By ccole Date 2020-08-05 Time 12:12 Rev Time 0.00
Received By ccole Date 2020-08-05 Time 07:22 Sent To  
Notes
2020-08-05 12:15:041ST REVIEW FBC-2017 PLUMBING/GREASE INTERCEPTOR
 PERMIT- 20071347
 8/5/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 1) P1 & P1.1: PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION. A
 PRIMARY PERMIT APPLICATION BY A FL. LICENSED PLUMBER
 AND COMPLETE PLUMBING PLANS, SIZING CALCULATIONS, AND
 SPECIFICATIONS SHALL BE SUBMITTED- SECTION 107.2.1 WPB.
  
 2) P1: REMOVE THE GRAVITY GREASE INTERCEPTOR
 CALCULATION TABLE FORM THE PLAN TO AVOID CONFUSION. THE
 NEW SELECTED SCHIER GREAT BASIN INTERCEPTORS ARE
 HYDROMECHANICAL AND SHALL BE SIZED IN ACCORDANCE WITH
 SECTION 1003.3.4 FBC P. PROVIDE REVISED CALCULATIONS ON
 THE PLAN USING THE REQUIRED METHOD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-09 Cont ID  
Sent By jwitmer Date 2020-09-09 Time 08:16 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-11 Cont ID  
Sent By jleahy Date 2020-08-11 Time 16:40 Rev Time 0.00
Received By jleahy Date 2020-08-11 Time 16:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-31 Cont ID  
Sent By eschneid Date 2020-08-31 Time 12:05 Rev Time 0.25
Received By eschneid Date 2020-08-31 Time 12:05 Sent To  
Notes
***NONE***