| 2020-09-14 15:33:24 | PLAN REVIEW / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NEC 2014 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. THE FOLLOWING TEST REPORTS ARE REQUIRED FOR THE |
| | FLOORING UNDERLAYMENT. MANUFACTURER SPEC SHEETS ARE NOT |
| | ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC |
| | SHEETS/BROCHURES AND TEST REPORTS FOR SOME |
| | MANUFACTURERS |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE |
| | AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT |
| | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 492. |
| | |
| | FBC 603.1 FLAME SPREAD |
| | FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 |
| | FBC 804.4.1 TEST REQUIREMENT. |
| | IN ALL OCCUPANCIES, INTERIOR FLOOR COVERING MATERIALS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE DOC FF-1 |
| | ?PILL TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D2859 |
| | |
| | NOTE: PROVIDE NAME OF PROPOSED UNDERLAYMENT. WE MAY |
| | HAVE THE TEST REPORTS AVAILABLE. |
| | |
| | |