Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-08-25 Cont ID  
Sent By lcrespo Date 2020-08-25 Time 10:26 Rev Time 0.00
Received By lcrespo Date 2020-08-25 Time 10:24 Sent To  
Notes
2020-08-25 10:25:2708/25/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-08-11 Cont ID  
Sent By medwards Date 2020-08-11 Time 15:10 Rev Time 0.00
Received By medwards Date 2020-08-11 Time 14:34 Sent To  
Notes
2020-08-11 15:10:452ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20071207
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ON THE GAS RISER DIAGRAM IN THIS SUBMITTAL IT
 INDICATES THE PIPE LEAVING THE GAS METER SERVICING THE
 ENTIRE SYSTEM IS A ?? PIPE. YOU ALSO INDICATE THAT THE
 PRESSURE OF THIS SYSTEM IS 12? WC. YOU USED TABLE
 402.4(21) TO SIZE THE PE PIPE TO THE GENERATOR. WITH
 THE INFORMATION THAT YOU HAVE PROVIDED, THE PIPE
 LEAVING THE GAS METER TO SUPPLY THE ENTIRE SYSTEM IS A
 ?? GALVANIZED PIPE FEEDING A LOW PRESSURE SYSTEM. WITH
 THE ADDITION OF 327,000 BTU TO THE ORIGINAL LOW
 PRESSURE SYSTEM WITH A LONGEST LENGTH NOW BECOMING 28?
 THIS ORIGINAL ?? GALVANIZED PIPE CAN ONLY HOLD A VOLUME
 OF 199,000 BTU AND IS UNDERSIZED. FBC FG TABLE
 402.4(2).
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 10:16 Rev Time 0.00
Received By lcrespo Date 2020-07-30 Time 09:59 Sent To  
Notes
2020-07-30 10:16:5407/30/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 3. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (GENERATOR) TO VERIFY COMPLIANCE WITH 2017 FBC FG
 SEC.305.1 OR 2017 FBC RES. SEC. G2408.1.
  
 4. THE CITY RECORD HAS RECORDS OF AN EXISTING GAS METER
 ON A SYSTEM. THE BTU LOAD OF THE EXISTING GAS SYSTEM
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING THE BTU
 LOAD OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE
 TO EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST
 LENGTH OF PIPING FROM THE POINT OF DELIVERY TO THE MOST
 REMOTE OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2017 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 5. REGULATOR REQUIRED, PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
  
 6. PLEASE SHOW UNION IN FRONT OF REGULATOR 1' OF EITHER
 SIDE AND LABEL ON ISOMETRIC PER THE 2017 FBC RES. SEC
 G2421.2.
  
 7. SHOW DRIP LEG AND LABEL ON ISOMETRIC PER THE 2017
 FBC RES. SEC. G2419.2.
  
 8. SHEETS FOR LOCATION OF GENERATOR AND SURVEY FOR GAS
 LAYOUT ARE ILLEGIBLE. SUBMIT COPIES THAT ARE SCANNED TO
 A PDF FILE, PLASE HAVE CLEAR AND LEGIBLE PLANS FOR
 REVIEW PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-25 Cont ID  
Sent By lcrespo Date 2020-08-25 Time 10:24 Rev Time 0.00
Received By lcrespo Date 2020-08-25 Time 10:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-11 Cont ID  
Sent By lmarchan Date 2020-08-11 Time 15:23 Rev Time 0.00
Received By lmarchan Date 2020-08-10 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 10:22 Rev Time 0.00
Received By lcrespo Date 2020-07-24 Time 14:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-08-25 Cont ID  
Sent By lcrespo Date 2020-08-25 Time 10:24 Rev Time 0.00
Received By lcrespo Date 2020-08-25 Time 10:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-11 Cont ID  
Sent By medwards Date 2020-08-11 Time 15:11 Rev Time 0.00
Received By medwards Date 2020-08-11 Time 15:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 10:21 Rev Time 0.00
Received By lcrespo Date 2020-07-30 Time 10:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 10:21 Rev Time 0.00
Received By lcrespo Date 2020-07-30 Time 10:21 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved