Plan Review Details - Permit 20071186
Plan Review Stops For Permit 20071186
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-29 Cont ID  
Sent By jbrooks Date 2020-09-29 Time 12:04 Rev Time 0.00
Received By jbrooks Date 2020-09-29 Time 12:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-22 Cont ID  
Sent By jbrooks Date 2020-09-22 Time 11:36 Rev Time 0.00
Received By jbrooks Date 2020-09-22 Time 11:09 Sent To  
Notes
2020-09-22 11:37:14JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. FBC B 1207.2 & 1207.3. SUBMITTED TEST
 REPORTS (STC) AND (IIC) FOR ECLIPSE II ACOUSTICAL
 UNDERLAYMENT FOR FLOATING/LAMINATE/ENGINEERED WOOD
 FLOORS/WPC (SOLID CORE VINYL PLANKS) WITH MOISTURE
 BARRIER CONTAIN DROP CEILINGS IN THE TEST ASSEMBLY.
 TEST REPORTS CANNOT INCLUDE DROPPED GYPSUM CEILINGS.
 PLEASE PROVIDE TWO SETS OF TEST REPORTS WITHOUT DROPPED
 GYPSUM CEILINGS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By jbrooks Date 2020-07-30 Time 10:58 Rev Time 0.00
Received By jbrooks Date 2020-07-30 Time 10:58 Sent To  
Notes
2020-07-30 10:58:52JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. CLARIFY FLOORING MATERIALS AND
 PROVIDE BRIEF DESCRIPTION OF PRODUCTS.
 2. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
 3. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING.PROVIDE A COPY OF THE TEST REPORT.
 4. FBC B 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 5. PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) 1910
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-29 Cont ID  
Sent By jbrooks Date 2020-09-29 Time 12:04 Rev Time 0.00
Received By jbrooks Date 2020-09-29 Time 12:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-22 Cont ID  
Sent By jbrooks Date 2020-09-22 Time 11:37 Rev Time 0.00
Received By jbrooks Date 2020-09-22 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-30 Cont ID  
Sent By jbrooks Date 2020-07-30 Time 10:59 Rev Time 0.00
Received By jbrooks Date 2020-07-28 Time 07:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2020-08-04 Cont ID  
Sent By rsklarew Date 2020-08-04 Time 13:37 Rev Time 0.00
Received By rsklarew Date 2020-08-04 Time 13:37 Sent To  
Notes
***NONE***