Plan Review Details - Permit 20071146
Plan Review Stops For Permit 20071146
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By rmcphers Date 2020-08-18 Time 09:05 Rev Time 0.00
Received By rmcphers Date 2020-08-18 Time 08:06 Sent To  
Notes
2020-08-18 09:05:35STORAGE BLDG - ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) RECORDS DO NOT SHOW A BUILDING PERMIT FOR THE
 STORAGE BUILDING CHANGE TO LIVING SPACE. A BUILDING
 PERMIT IS REQUIRED TO CONVERT THE STORAGE SPACE TO
 LIVING SPACE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By fgiaquin Date 2020-08-18 Time 20:30 Rev Time 0.00
Received By fgiaquin Date 2020-08-18 Time 19:47 Sent To  
Notes
2020-08-18 20:30:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PERMIT APPLICATION DESCRIPTION DOES NOT MATCH PLAN.
 SHOW ALL WORK TO BE DONE ON PLAN OR UPDATE PERMIT
 APPLICATION. NO LIGHTS NO FANS SHOWN ON PLAN. FBC
 107.2.1
  
 2. VALUE LOW FOR AMOUNT OF WORK SHOWN. VALUE FOR MASTER
 PERMIT IS LOW AND VALUE FOR ELECTRICAL WORK IS LOW.
 PROVIDE CONTRACT WITH ACCURATE VALUE TO INCLUDE ALL
 MATERIALS AND LABOR; SIGNED BY BOTH OWNER AND
 CONTRACTOR. FBC 109.3
  
 3. PROVIDE LOAD CALCULATION AND RISER DIAGRAM FOR
 EXISTING SERVICE TO INCLUDE ALL NEW LOADS. NEC 220
  
 4. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED (DIGITALLY WITH THIRD PARTY VERIFICATION)
 BY A DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-15 Cont ID  
Sent By shill Date 2020-09-15 Time 14:58 Rev Time 0.00
Received By shill Date 2020-07-24 Time 11:25 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By rmcphers Date 2020-08-18 Time 09:06 Rev Time 0.00
Received By rmcphers Date 2020-08-18 Time 09:06 Sent To  
Notes
2020-08-18 09:08:50PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-08-18 Cont ID  
Sent By medwards Date 2020-08-18 Time 07:11 Rev Time 0.00
Received By medwards Date 2020-08-18 Time 07:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2020-08-17 Time   Rev Time 0.00
Received By lcrespo Date 2020-08-17 Time 10:47 Sent To  
Notes
2020-08-17 12:07:5908/17/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING UNIT HAVING A PLUMBING PERMIT FOR WORK ON THE
 EFFICIENCY GARAGE A FULL EVALUATION AND RESEARCH MAY BE
 REQUIRED. ANY WORK THAT DOES NOT HAVE A PERMIT MAY ALSO
 NEED TO BE BOUGHT UP TO CODE COMPLIANCE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. PLEASE GIVE DIMENSION OF THE SHOWER, 900 SQUARE
 INCHES ARE REQUIRED PER 2017 FBC RE. SEC. 2708.1.
  
 3. PLUMBING RISER DIAGRAM MAY BE REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING. THIS IS DUE TO PENDING INFORMATION ON PERMIT
 CLARIFICATION.
  
 4. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. PLANS THAT ARE NOT DESIGNED BY ARCHITECTS OR
 ENGINEERS BUT BY CONTRACTORS MUST COMPLY WITH THE
 FOLLOWING REQUIREMENTS. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH
 TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER
 THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE
 DRAWN BY ONE INDIVIDUAL, THEY WOULD HAVE TO BE LICENSED
 AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO
 SUBMIT ALL THESE TRADES UNDER ONE SHEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By rmcphers Date 2020-08-18 Time 09:05 Rev Time 0.00
Received By rmcphers Date 2020-08-18 Time 09:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By rthermid Date 2020-09-15 Time   Rev Time 0.00
Received By rthermid Date 2020-09-15 Time   Sent To I
Notes
***NONE***