Plan Review Details - Permit 20071065
Plan Review Stops For Permit 20071065
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 11:58 Rev Time 0.00
Received By jwitmer Date 2020-09-22 Time 11:46 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2020-08-17 Time 13:31 Sent To  
Notes
2020-08-17 14:11:46TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 12:14 Rev Time 0.00
Received By jwitmer Date 2020-09-22 Time 11:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 14:13 Rev Time 0.00
Received By jwitmer Date 2020-08-17 Time 13:31 Sent To  
Notes
2020-08-17 14:10:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20071065
 ADD: 525 S. FLAGLER DR. # 27B
 CONT: THE CASTELLA & GODOY COMPANIES
 TEL: 561-723-4144
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY AUGUST 17TH/ 2020
 ACTION: DENIED
  
 1) THE FLOOR PLAN SHEET 101.2 INDICATES IN THE
 TITLEBLOCK IT WAS DEVELOPED BY THE CONTRACTOR OF
 RECORD, PLEASE FOLLOW THE REQUIREMENTS FOR PLANS
 DESIGNED BY CONTRACTORS.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH
 TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER
 THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE
 DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED
 AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO
 SUBMIT ALL THESE TRADES UNDER ONE SHEET.
  
 2) THE CONTRACTOR HAS NOT INDICATED WHICH METHOD UNDER
 THE 2017 EXISTING BUILDING CODE THE PLANS WERE
 DESIGNED. IF UNDER THE WORK AREA METHOD THIS WOULD BE
 CONSIDERED A LEVEL I.
 2017 EXISTING BUILDING CODE METHOD OF PLAN DEVELOPMENT.
 2017 EXISTING BUILD. CODE SECTION 301.1. THE REPAIRS,
 ALTERATIONS, CHANGE OF OCCUPANCY, ADDITIONS OR
 RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH
 ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE DESIGNER OF RECORD.
 3) SHEET 101.2 NEITHER THE NOTES NOR DETAIL INDICATE IF
 THE ? INCH DENSE-SHIELD AND TILE ARE GOING TO BE
 INSTALLED? SEE THE 2017 FBC-B SHOWERS & TUBS 1210.3.
 SHOWER COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER
 HEADS SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO
 A HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
 4)
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-22 Cont ID  
Sent By lcrespo Date 2020-09-22 Time 17:47 Rev Time 0.00
Received By lcrespo Date 2020-09-17 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-18 Cont ID  
Sent By shill Date 2020-08-18 Time 13:19 Rev Time 0.00
Received By shill Date 2020-07-23 Time 15:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-22 Cont ID  
Sent By lcrespo Date 2020-09-22 Time 17:47 Rev Time 0.00
Received By lcrespo Date 2020-09-22 Time 17:47 Sent To  
Notes
2020-09-22 17:52:1909/22/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By tklarge Date 2020-08-18 Time 12:09 Rev Time 0.00
Received By tklarge Date 2020-08-18 Time 11:42 Sent To  
Notes
2020-08-18 12:09:411) SUBNMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE WATERPROOFING SYSTEM
 TO BE INSTALLED FOR THE SHOWER. THE SYSTEM SHALL COMPLY
 WITH FBC-PLUMBING SEC.417.5.2.5 OR SEC. 417.5.2.6.
 2) SUBMIT AN APPLICATION FROM A LICENSE PLUMBING
 CONTRACTOR FOR THE INSTALLATION OF THE NEW SHOWER AND
 VALVE AND VANITY. THIS WORK MUST BE DONE BY A LICENSED
 PLUMBING CONTRACTOR. A GENERAL CONTRACTOR IS NOT
 AUTHORIZED TO DO THIS SCOPE OF WORK. FL.STATUTE SEC.
 489.103.
 3) THE SHOWER SHALL BE PITCHED 1/4 INCH PER FOOT
 MINIMUM TOWARD THE DRAIN. FBC-PLUMBING SEC.417.5.2.
 4) SUBMIT SPECIFICATIONS FOR THE SHOWER VALVE. THE
 VALVE SHALL COMPLY WITH FBC-PLUMBING SEC.424.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2020-09-23 Cont ID  
Sent By rgathrig Date 2020-09-23 Time 12:47 Rev Time 0.00
Received By rgathrig Date 2020-09-23 Time 12:46 Sent To  
Notes
2020-09-23 12:47:18PRIVATE PROVIDER INSPECTIONS ONLY REVIEWED AND APPROVED
 TEW AND TAYLOR
  
 RICHARD GATHRIGHT

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 11:57 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-09-22 11:57:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20071065
 ADD: 525 S. FLAGLER DR. # 27B
 CONT: THE CASTELLA & GODOY COMPANIES
 TEL: 561-723-4144
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2ND REVIEW
 DATE: TUES. SEPT. 22/2020
 ACTION: DENIED
 1) THE PERMIT APPLICATION INDICATES THE CONTRACTOR HAS
 REQUESTED THE USE OF A PRIVATE PROVIDER, BUT THE
 CONTRACTOR HAS NOT INDICATED ON THE PERMIT APPLICATION
 IF THIS IS FOR PLAN, REVIEW, INSPECTIONS OR IF BOTH?
 THE CONTRACTOR HAS NEGLECTED TO ALSO PROVIDE THE SIGNED
 FORMS PER FLORIDA STATUTE 553.791, EACH PRIVATE
 PROVIDER MUST REGISTER WITH THE CITY OF WEST PALM BEACH
 PRIOR TO PREFORMING SERVICES AND BE COMPLIANT WITH F.
 S. 553.791(1)(I) TO PROVIDE SERVICES.
 PROPER NOTIFICATION MUST BE PROVIDED TO THE CITY OF
 WEST PALM BEACH IN ACCORDANCE WITH SECTION 553.791 (2),
 (3) (4) AND (5). FOR INSPECTIONS, AT LEAST (7) DAYS
 PRIOR TO THE OFFERING OF INSPECTION SERVICES, NOTICE ON
 A FORM THAT CONTAINS THE LANGUAGE FOUND IN THE STATUTE
 MUST BE TURNED IN.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 12:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 14:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-08-17 14:10:291) THE FLOOR PLAN SHEET 101.2 INDICATES IN THE
 TITLEBLOCK IT WAS DEVELOPED BY THE CONTRACTOR OF
 RECORD, PLEASE FOLLOW THE REQUIREMENTS FOR PLANS
 DESIGNED BY CONTRACTORS.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH
 TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER
 THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE
 DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED
 AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO
 SUBMIT ALL THESE TRADES UNDER ONE SHEET.