Plan Review Details - Permit 20070903
Plan Review Stops For Permit 20070903
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-28 Cont ID  
Sent By jleahy Date 2020-07-28 Time 07:08 Rev Time 0.00
Received By jleahy Date 2020-07-28 Time 07:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By jleahy Date 2020-07-24 Time 16:51 Rev Time 0.00
Received By jleahy Date 2020-07-24 Time 16:49 Sent To  
Notes
2020-07-24 16:53:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) OUTLETS WITHIN 6' OF SINKS SHALL BE GFCI PROTECTED
 PER 210.8(B)
  
 2) AIC RATING REQUIRED FOR SERVICE AND LABELS 110.9,
 110,10, 110.24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2020-07-28 Cont ID  
Sent By tklarge Date 2020-07-28 Time 12:18 Rev Time 0.00
Received By tklarge Date 2020-07-23 Time 08:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-07-28 Cont ID  
Sent By jesmith Date 2020-07-28 Time 12:18 Rev Time 0.00
Received By tklarge Date 2020-07-28 Time 11:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-28 Cont ID  
Sent By jleahy Date 2020-07-28 Time 07:08 Rev Time 0.00
Received By jleahy Date 2020-07-28 Time 07:08 Sent To  
Notes
***NONE***