| 2020-07-30 08:50:27 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1.PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET |
| | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE |
| | SIGNED AND SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY |
| | THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE |
| | CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 |
| | 2.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE |
| | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| | BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). |
| | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| | 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC |
| | 107.2.1 CONFLICTS ON PLANS |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | PHIL PETTY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6742 |
| | [email protected] |
| | |
| | |