| 2020-08-05 15:17:12 | 08/05/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| | PALM BEACH ORD #2853-95. A DUAL CHECK VALVE MAY BE USED |
| | IF NO POOL FILL IS INSTALLED AT THE METER AND INSTALLED |
| | BY UTILITIES WHICH DO NOT REQUIRE A PERMIT SO PLEASE |
| | CONTACT THE CITY OF WPB UTILITIES AT 561-822-2240 FOR |
| | FURTHER DIRECTIONS. |
| | |
| | 2. THE HAZEN WILLIAMS EQUATION IS NOT AN ACCEPTABLE |
| | CALCULATION FOR SYSTEM FLOW PLEASE REFER TO THE TOTAL |
| | DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW. |
| | THE MAXIMUM FLOW OF THE PUMP FROM ITS PUMP CURVE IS NO |
| | LONGER ALLOWED TO BE USED IN DETERMINING THE MAXIMUM |
| | SYSTEM FLOW RATE PER ANSI/APSP/ICC 7 - 2013 SECS. |
| | 4.4.9, 4.4.9.1. THE 2013 EDITION ADDRESSES THE FLOW |
| | RATE IN GALLONS PER MINUTE (GPM). IT REQUIRES THAT THE |
| | MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED |
| | MAXIMUM FLOW RATE OF THE SUCTION OUTLET FITTING |
| | ASSEMBLY (DRAIN COVER). THE TDH CALCULATIONS MUST |
| | INCLUDE ALL THE SYSTEM COMPONENTS INCLUDING SUCTION AND |
| | RETURN PIPING, FITTINGS, VALVES, HEATER, FILTER, AND |
| | CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT THE PUMP. |
| | |
| | 3. SUBMIT SPECS FOR THE PUMP AND ON IT SHOW THE POOL |
| | PUMP CURVE. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY |
| | IS SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. |
| | THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM |
| | THE TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 |
| | SECS. 4.4.9, 4.4.9.1. |
| | 4. SHOW THE POOL PIPING LAYOUT ON THE PLANS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 5. SHOWS A VELOCITY CHART PER ANSI/APSP -7 SEC. 4.4. I |
| | COULD NOT FIND THIS CHART IN APSP-7 2013 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 6. INDICATE ON THE PLANS IF THE POOL IS EQUIPPED WITH |
| | AN AUTOFILL PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. SUBMIT SPECIFICATIONS FOR THE CARTRIDGE FILTER PER |
| | THE WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 8. ALL HOSE BIBBS EXPOSED TO THE POOL AREA SHALL BE |
| | EQUIPPED WITH A VACUUM BREAKER PER THE 2017 FBC |
| | R4501.9. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |