| 2020-07-22 14:21:08 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL |
| | FL12328-R8 SUBMITTED CAN NOT BE USED FOR THE PROPOSED |
| | INSTALLATION. THE PROPOSED ROOF TILE INSTALLATION IS |
| | USING TILE ADHESIVE. ACCORDING TO THE LAST NOTE UNDER |
| | APPLICATION METHOD ON PAGE 2 OF 4 OF PRODUCT APPROVAL |
| | SUBMITTED "ALL ROOF COVERINGS SHALL BE MECHANICALLY |
| | FASTENED THROUGH THE UNDERLAYMENT TO THE ROOF DECK". |
| | THEREFORE, NEED TO PROVIDE UNDERLAYMENT PRODUCT |
| | APPROVAL THAT IS DESIGNED FOR ROOF TILE ADHESIVE |
| | APPLICATIONS. |
| | FAC 61G20-3.001. |
| | |
| | 2- ROOF TILE FL7473-R8 AND ROOF TILE ADHESIVE FL6332-R8 |
| | SUBMITTED: CLEARLY MARK ADHESIVE PADDY SIZE TO BE USED |
| | AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 3- SPECIFY ROOF PITCH, BUILDING MEAN HEIGHT AS REQUIRED |
| | BY CITY POLICY FOR ALL ROOFING PERMITS AND SEC. |
| | 107.02.1 CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |