| 2020-07-28 09:09:32 | 07/28/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ALL COOPER LINE THAT ARE UNDERGROUND SHALL BE |
| | SLEEVED AND SHOWN ON ISOMETRIC PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 2. PLEASE PROVIDE LISTING RATINGS FOR TIKI TORCHES AND |
| | LANTERNS AS APPLIANCES SHALL BE LISTED AND LABELED PER |
| | THE 2017 FBC FG SECS. 402.2 AND 301.3. |
| | |
| | 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC FG SEC. 410.1. |
| | |
| | 4. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 6. PLEASE PROVIDE A LAYOUT SHOWING THE LOCATION SHOWING |
| | THE LOCATION OF THE TANKLESS WATER HEATER AND THE |
| | LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS |
| | IN RELATION TO THE WATER HEATER AND ALL OTHER |
| | APPLIANCES, IF APPLICABLE SUBMIT A DETAIL SHOWING THE |
| | TYPE, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE |
| | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER |
| | THE 2017 FBC FG SECS. 502 THRU 505. (PRINT OUT THE |
| | LAYOUT OF THE BUILDING I AND SEND YOU A PDF FILE IF YOU |
| | LIKE, JUST EMAIL ME A REQUEST, THIS SHOULD ALSO SHOW |
| | DISTANCES FROM TIKI TORCH AND LANTERNS TO ANY |
| | COMBUSTION STRUCTURES, VEGETATION AND OR TREES). |
| | |
| | 7. PLEASE SHOW AND LABEL DRIP LEG, UNIONS ON TANKLESS |
| | AND LABEL REGULATOR AND ON ISOMETRIC PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 8. THE OLD RANGE HAS A 50 BTU'S BUT THE NEW ONE HAS 150 |
| | BTU'S SO' PLEASE PROVIDE NEW SPECS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 9. ON ISOMETRIC PLEASE LABEL ALL BTU'S ON A LIST AND |
| | SHOW THEM BROKEN DOWN ON A SCHEDULE TYPE FORMAT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. PLEASE CLEAN UP ISOMETRIC SO IT |
| | IS LEGIBLE OUT IN FIELD AS IT IS CONGESTED WITH NUMBERS |
| | AND CONFUSING TO THE EYE, THANKS |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |